2.  Install the Model 571/581 between the incoming UTP line and the

protected equipment (see Figure 3, below).  This installation
requires a 

straight through 

Cat-5 patch cable with modular RJ-45

connectors (supplied with unit). 

Note:

The Model 571/581 provides bi-directional clamping

protection.  Therefore, the network and equipment cables may be
connected to either end.

3. Locate a metal chassis ground on the equipment to be protected.

This is often a hex screw on a D-shell or AUI connector.
Sometimes a metal back panel is attached by screws, one of which
can be used for chassis grounding.  If you cannot locate a chassis
ground connection on your equipment, contact Patton Technical
Support at 

(301) 975-1007

http://www.patton.com

; or,

[email protected]

4.  Connect the braided ground strap directly to the chassis ground

connection you have located (see Figure 3, above).  

Caution:

Surge energy may run

both directions 

on the ground

strap.  To provide the best protection, it is essential that the ground
strap on the Model 571/581 be connected to the chassis ground of
the protected device.  

Do not

lengthen the ground strap of the

Model 571/581 or connect to a ground other than chassis ground
unless instructed to do so by Patton Technical Support.

5

Connection to

chassis  ground

Cat-5 patch cable  to

protected equipment

(6 inches or less)

Cat-5 input

from network

Figure 3.

Installation of Model 571/581 Surge Protectors.  

8

APPENDIX B

MODEL 571/581 INTERNATIONAL ELECTROTECHNICAL

COMMISSION (IEC) COMPLIANCE

Meets IEC standards 801.2, 801.4 and 801.5 (CE Mark)

Effective January 1996 the European Economic Community will

require that all electronic devices be tested and comply with all
applicable International standards relating to the product type and
category of use.  Electromagnetic Compatibility Directive 89/336/EEC
specifically addresses communication line surge protection devices,
since conformity to immunity standard EN50082-1:1992 is mandatory.
The EN50082-1:10992 standard incorporates International
Organization for Standardization (ISO) publications 801.2 and 801.4,
which describe Electrostatic Discharge and Electrical Fast Transient
requirements.  ISO 801.5 describes Surge Immunity Requirements and
is expected to be adopted as a mandatory requirement under
EN50082-1 by the Technical Committee. in 1996.  Any protector sold
into the international community must meet these standards.  This
device has been tested* and found to comply with these standards as
evidenced by its CE mark.

*Note:

All test results are for the Model 571/581 

alone

, not 

including  the standard 6 inch (15.25) patch cable that is  
shipped with the unit.

Class

1

1.0 kV

24 A

2

1.0 kV

24 A

3

2.0 kV

48 A

4

(n/a)
(n/a)

5

4.0 Kv

95 A

Wave 

(1.2 x 50 μs)

Forms

(1.2 x 50 μs)

IEC 801-5 Threat Levels as a Function of Class

Sym. Lines Coupling Mode

Line-GND, Zs=42 Ohms

Table 1.

IEC Threat Levels as a Function of Class. 

Summary of Contents for 571

Page 1: ...571 581 100Base T CAT 5 Surge Protectors SALES OFFICE 301 975 1000 TECHNICAL SUPPORT 301 975 1007 http www patton com Part 07M571 581 A Doc 074300U Rev B Revised 1 22 08 C E R T I F I E D An ISO 9001...

Page 2: ...consequential damages arising from the use of or inability to use this product Patton Electronics specifically disclaims all other warranties expressed or implied and the installation or use of this p...

Page 3: ......

Page 4: ...line for installing the units in your Cat 5 environment 3 1 1 POINT OF USE APPLICATION MODEL 571 The Model 571 is designed for installation on LAN equipment in a typical office environment see Figure...

Page 5: ......

Page 6: ...ate a chassis ground connection on your equipment contact Patton Technical Support at 301 975 1007 http www patton com or support patton com 4 Connect the braided ground strap directly to the chassis...

Page 7: ......

Page 8: ...Hz Model 581 worst pair Better than 43 dB at100 MHz Surge Clamp Voltage Model 571 13 V max with 1 KV Input Model 581 15 V max with 2 KV Input Surge Rating IEC 801 5 Standard Level DC Clamp Voltage Com...

Page 9: ......

Page 10: ...ll Category 5 connecting hardware These standards specify the capacitance and near end cross talk N E X T to insure proper operation of ALL connected equipment Specific test results are shown in the t...

Page 11: ......

Page 12: ...APPENDIX B Continued TSB 40A COMPLIANCE TESTING RESULTS TYPICAL RETURN LOSS MEASUREMENT 11 Copyright Patton Electronics Company AllRightsReserved...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Reviews: