CHECKING AND ADJUSTING PRESSURE REGULATOR 

The combination gas valve (includes pressure regulator) is factory set at 4" W.C. for natural gas and 10" W.C. 

for propane gas. To check the manifold pressure, do the following: 
1. Turn thermostat “OFF” and combination gas valve knob to the “PILOT” setting.
2. Remove pressure tap plug from burner manifold located directly below the burners in the cabinet.
3. Install a fitting appropriate to connect a manometer.
4. Turn combination gas valve to “ON” position and thermostat to “ON.” The burners will ignite. Be certain

that sufficient oil is covering the tubes.

5. With burners on, read manometer.
6. If the manometer does not read 4" W.C. for natural gas, or 10" W.C. for propane gas, adjust regulator.
7. Remove regulator adjustment screw cap (see diagram on page 15).
8. With small screwdriver rotate adjustment screw “CLOCKWISE” to increase or “COUNTERCLOCKWISE”

to decrease pressure. Be sure to adjust with burners “ON.”

9. Turn thermostat “OFF” and set combination gas valve knob to “PILOT” position.
10. Remove manometer and replace pressure tap plug.
11. Replace adjustment screw cap.

CHECKING AND ADJUSTING CALIBRATION OF THERMOSTAT 

All thermostat controls are carefully calibrated at the factory (i.e., the dial is properly set to control appliance 

temperatures accurately). Only a qualified appliance service technician should perform this adjustment. 
1. To  check  appliance  temperatures,  use  a  thermocouple-type  temperature  test  instrument  or  reliable

thermometer. Place the thermocouple of test instrument or thermometer in the center of the frypot.

2. Turn the control dial to the temperature setting requiring the greatest accuracy. Allow enough time for

temperature to stabilize, or until several temperature readings are identical.

3. Recalibrate if setting and actual temperature differ by more than 10

F.

4. Remove dial from dial shaft “B.” Be careful that dial

shaft  does  not  rotate  in  either  direction  (which

would change the dial setting).

5. Hold  dial  shaft  “B”  steady  and  with  a  screwdriver

turn calibration screw “A” clockwise to decrease the

temperature,  or  counterclockwise  to  increase  the

temperature.

6. Replace  dial.  Let  the  appliance  operate  until  the 

temperature  has  stabilized  before  a  final  check  is 

made  to  determine  whether  or  not  the  calibration

has been corrected.

7. Once  correct,  seal  the  calibration  screw  with

glyptol.

Summary of Contents for PT-F3-NG

Page 1: ...E INJURY OR DEATH READ THE INSTALLATION OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT Please call the Service Department and ask for contact informati...

Page 2: ...could result in injury product damage or property damage NOTICE This symbol refers to information that needs special attention or must be fully understood even though not dangerous WARNING FIRE HAZAR...

Page 3: ...of reliable trouble free operation For best results read this manual carefully RETAIN THIS MANUAL FOR FUTURE REFERENCE MODELS This manual is for Gas floor model Fryers with 40 lbs 50 lbs and 90 lbs ca...

Page 4: ...Height in Gas Connection in Total BTU hr Crated Weight lbs A B C D E F G H I 3 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7 0 90 000 150 4 burner fryer 15 5 14 0 30 3 14 0 47 2 34 7 6 0 4 2 7...

Page 5: ...50 000 39 Propane 10 W C 5 30 000 150 000 52 Minimum supply pressure is 4 W C for natural gas and 10 W C for propane Orifice sizes are for units installed at altitudes between 0 and 2000 feet above se...

Page 6: ...are pre mounted on the base plates 1 Raise fryer sufficiently to allow legs or casters to be screwed into the base plate For safety shore up and support the fryer with an adequate blocking arrangemen...

Page 7: ...iance is moved to its original installed position WARNING When this appliance is installed with casters it must be installed with the casters supplied a connector complying with either ANSI Z21 69 or...

Page 8: ...8 Step 3 Flue Installation 1 Unpack the flue box and flue wrap 2 Slide the flue box over the flue and secure it with the two self tapping screws using a 5 16 socket 3 Slide the flue wrap over the flue...

Page 9: ...FLOOR MODEL FRYERS SHALL BE INSTALLED WITH AT LEAST A 16 INCH SPACE BETWEEN THE FRYER AND SURFACE FLAMES FROM ADJACENT EQUIPMENT A FLAME GUARD IS ACCEPTABLE IF ALLOWED UNDER LOCAL CODE No additional s...

Page 10: ...cked at installation and adjusted if necessary For orifice sizes and pressure regulator settings see the chart on page 4 If the fryer is being installed at over 2 000 feet altitude and that informatio...

Page 11: ...SURES IN EXCESS OF 14 WC 1 2 PSIG or 3 45 kPa If the incoming gas pressure is in excess of 14 WC 1 2PSI 3 45 kPa a proper step down regulator will be required See PHOTO 1 for LP application Connect th...

Page 12: ...knob down use a lit match to ignite the pilot Continue to press the knob down for about 30 seconds If the pilot does not stay lit when the knob is released repeat the lighting procedure and keep the k...

Page 13: ...BURNERS WHEN THE FRYPOT IS EMPTY 7 To prevent burning or scorching the solid shortening keep the thermostat set at the lowest temperature until all the solid shortening between and above the tubes has...

Page 14: ...d food CLEANING The equipment is constructed with the best quality materials and is designed to provide durable service when properly maintained To expect the best performance your equipment must be m...

Page 15: ...residue from stainless steel use ordinary soap and water with or without detergent applied with a sponge or cloth Dry thoroughly with a clean cloth Never use vinegar or any corrosive cleaner To remove...

Page 16: ...ontact your Service Representative for reliable service dependable advice or other assistance and for genuine factory parts All units are adjusted at the factory In case of problems in operation at in...

Page 17: ...ace adjustment screw cap CHECKING AND ADJUSTING CALIBRATION OF THERMOSTAT All thermostat controls are carefully calibrated at the factory i e the dial is properly set to control appliance temperatures...

Page 18: ...ed Combination gas valve is in OFF position Pilot gas not adjusted properly Gas supply to unit off Bad thermopile Dirty thermopile connections at combination gas valve or high limit Clogged orifice Dr...

Page 19: ...19 Wiring Diagram...

Page 20: ...cement parts may be ordered either through a Authorized Parts Distributor or a Authorized Service Agency When ordering parts please supply the Model Number Serial Number Part Number and Description In...

Page 21: ...sys 4 PT 400146 1 Combination valve LP _Invensys 4 PT 400242 1 Combination Valve Nat _Honeywell 4 PT 400246 1 Combination valve LP _Honeywell 5 PT 400070 1 Tubing fryer pilot 10 PT 300031 ea Burner Fr...

Page 22: ...T 400076 1 Flue top removable 4 tube fryer PT 400077 1 Flue top removable 5 tube fryer 6 PT 400078 1 Flue wrap top removable 3 and 4 tube fryer PT 400079 1 Flue wrap top removable 5 tube fryer not sho...

Page 23: ...We all recognize however that replacement parts and occasional professional service may be necessary to extend the useful life of this unit When service is needed contact an Authorized Service Agency...

Page 24: ...ntiguous United States Hawaii and metropolitan areas of Alaska and Canada may vary The following conditions are not covered by warranty Equipment failure relating to improper installation improper uti...

Reviews: