Patol 5610 Manual Download Page 8

Patol Limited 

 

2.6

 

Operational Programmability - SIL Switch 

 

An eight pole SIL switch is located within the unit which programs the unit’s operation. Most 

of the various option features are for special applications, factory test, commissioning or 
maintenance purpose.  

A summary of the switch functions is as follows:- 

 

2.6.1  LED Operation - Pole 1 

Normally the internal LEDs will only illuminate on ‘Alarm’ signalling. In the case of 

coincident (double knock) operation the LEDs only illuminate when both channels 
have triggered. This is to obviate momentary increases in line current for single 
channel operations. For factory test and maintenance purpose Pole 1 of the switch 
allows the LEDs to individually illuminate irrespective of operating mode. Ref. table 1. 

 

2.6.2  Channel AND / OR selection - Pole 2 

The unit can operate such that detection by either sensor channel results on an 

alarm output  (single knock / OR operation). Alternatively the unit may be set an 
alarm output only occurs on detection by both sensor channels (double knock / 
coincident / AND operation). Refer to table 1 & 2.7.6. 

 

2.6.3  Non-latching option. - Pole 3 

The sensor channels normally latch on detection. A non-latching setting is available 
for maintenance, factory test and special application analysis. Refer to table 1. 

 
2.6.4  Auto Reset operation. - Pole 4 

When in double knock mode an auto reset is applied after a  preset delay .  
This only occurs if only a single channel has operated within the delay time. If both 
channels have operated then the auto reset is prevented. The delay time is in effect 
the scan period for coincidence. An option to auto reset ‘AND alarms’ is provided for 
maintenance test purpose. Refer to table 1, 2.6.5 & 2.7.6. 

 
2.6.5  Auto Reset Delay (Scan Period) - Poles 5 & 6 

The duration is set by these switch poles . Refer to table 2. 

 
2.6.6  Sensitivity. - Poles 7 & 8 

The unit detection level sensitivity is set by these switch poles. The range 
approximates to 10 - 40 

μ

W.  Refer to table 3. 

Pole   

FUNCTION 

OFF 

Channel LED’s only illuminate on alarm 

ON 

Channel  LED’s illuminate before Double Knock alarm  

OFF 

Double Knock - Coincident Output 

ON 

Single Operation - OR - Output 

OFF 

Latching Operation 

ON 

Non-latching Operation 

OFF 

Only single detections auto-reset after scan period 

ON 

All detections auto-reset after scan period 

Pole 

AUTO RESET DELAY  -  SCAN  PERIOD 

5 OFF 

2.6s 

OFF 

1.3s 

ON 

0.9s 

ON 

0.6s 

6 OFF 

ON 

OFF 

ON 

Pole 

SENSITIVITY  (A=Most : D=Least)   

7 OFF 

OFF 

 

ON 

 

ON 

 

OFF ON  OFF ON 

Table 1. 

Table 2. 

Table 3. 

Page  8 of 16 

D1198  -  Issue 1  -  25  September 2013 

Series 5000 - Manual 5610 

Summary of Contents for 5610

Page 1: ...at Detector SPECIFICATION INSTALLATION COMMISSIONING OPERATION MAINTENANCE Document Ref D1198 Issue Change Date Remarks 1 Original 25 09 13 Approved RJJ Rectory Road Padworth Common Reading Berkshire RG7 4JD United Kingdom Tel 44 0 118 9701 701 Fax 44 0 118 9701 700 Email info patol co uk Web www patol co uk Patol Limited ...

Page 2: ... Connections 3 INSTALLATION 3 1 Detection Coverage 3 2 Supply Signal Cable 3 3 Purge Air Supply 4 COMMISSIONING 4 1 Cable Checks 4 2 Unit Set Up 4 3 Power Up Procedure 4 4 Hot Body Simulation Tests 5 OPERATION 5 1 Normal 5 2 Alarm Condition 5 3 Reset 5 4 Fault Warning 5 5 Test 6 MAINTENANCE 6 1 General 6 2 Fault Monitoring Functions 6 3 Infra red Detection Page 2 of 16 D1198 Issue 1 25 September 2...

Page 3: ...t spots Air purged system for Dusty environments Two wire operation Powered by direct connection to standard fire trigger circuits or addressable loop interfaces Signalling mode user configurable to simulate smoke heat detector protocols Volt free relay contact output operation selectable as standard Twin high integrity detection circuit channels for maximum reliability Unique reflective cone lens...

Page 4: ...ir pressure is maintained around the unit s sensor windows There is a continuous air flow from the optical path visor which stops dust settling on the sensor glazed optical aperture The air purging is essential in dusty environments such as coal conveyors and is recommended in even relatively clean applications The unit may be user selected to either of two principal operating settings which are r...

Page 5: ...unit will signal Normal Fire Fault conditions by line current levels in a manner that permits the unit to be connected directly to fire control panels via alarm trigger circuits or to the monitored inputs of addressable loop interface modules The unit can also be employed with the two wire connection to a remote Patol signal relay module Refer to figures 4 5 Patol Limited ALARM FAULT SUPPLY 5610 S...

Page 6: ... is terminated at screw terminals 2 5 Specification 2 5 1 General a Outer Case Material Aluminium Alloy Finish Red RAL 3020 b Termination Rising clamp terminals Cable Core Size 2 5mm 14AWG c Temperature 20 C to 60 C d Weight 3 kg e Purge Air Supply Pressure 175 to 700 mBar 2 5 psi to 10 psi Minimum Delivery 30 litres min Input Fitting 10mm Compressed Air Hose Adaptor Fig 6 Ø146 141 48 150 FACSIA Ø...

Page 7: ...witch Sensitivity 4 Levels SIL 8 Way Alarm Operation OR AND Latching Auto Reset Auto Reset Timer 4 Settings 2 5 3 Relay Mode Direct Supply Relays Enabled a Supply Voltage 20 to 30 Vdc b Supply Current Standby 9 mA Fire Alarm 24 mA max c Alarm Output Fire Relay Contact 1 pole change over 30 Vdc 500 mA Normally De energised c Monitor Output Fault Relay Contact 1 pole change over 30 Vdc 500 mA Energi...

Page 8: ...hing setting is available for maintenance factory test and special application analysis Refer to table 1 2 6 4 Auto Reset operation Pole 4 When in double knock mode an auto reset is applied after a preset delay This only occurs if only a single channel has operated within the delay time If both channels have operated then the auto reset is prevented The delay time is in effect the scan period for ...

Page 9: ...n 24Vdc POWER SUPPLY REMOTE TEST OPTIONAL FIRE FAULT SHOWN IN FAULT SHOWN NORMAL TRIP 1 ALARM 2 CONTACTS ENABLED 23 24 27 28 19 20 21 22 25 26 24V RESET ALERT 0V LED Pressure Switch LED Operation Selection Patol Limited 2 7 Connections 2 7 1 Relay Mode Direct Supply Relays Enabled 2 7 2 Low Power Mode Relays Disabled Fig 8 Fig 9 Refer 2 7 3 to 2 7 6 Refer 2 7 3 to 2 7 6 Page 9 of 16 D1198 Issue 1 ...

Page 10: ...t terminals 20 22 The signal at terminal 22 is switch low 0V 2 7 6 Alert Output A signal at terminal 21 is in effect an open collector switch low 0V on either channel detection This output occurs even if the unit is set for coincident alarm operation and may be considered as an Alert which will operate for the duration of the scan period with auto reset if coincident condition does not occur Also ...

Page 11: ...l Cable The Type 5610 Detector outer case has 3 x 20mm cable entries as standard Cable terminations are made at rising clamp screw terminal connectors located within the inner module The terminals accept wires of up to 1 5mm 15AWG Refer to section 2 7 for connections To access the terminals it is necessary to remove the lid fascia and the internal detector assembly This is achieved by releasing th...

Page 12: ...r connection to a 10mm compressed air flexible hose The air supply must be capable of delivering at least 30 ltrs min at this connection and have a pressure of 175 to 700 mBar 2 5 to 10 psi Fig 13 To remove lid unscrew anti clockwise Fixings A and B External viewing apertures Sensors 10mm compressed air inlet 3mm hex locking screw Page 12 of 16 D1198 Issue 1 25 September 2013 Series 5000 Manual 56...

Page 13: ...cuit Note 2 The tests of 4 3 2 4 3 3 can only be conducted with the enclosure lid fascia open This may not be permissible in hazardous areas in which case go straight to 4 3 4 4 3 1 Apply power to the detector Connect supply or trigger circuit Check supply 20 to 30 Vdc for relay mode or 13 to 30 Vdc for relay mode 4 3 2 Operate detector Test PB Check Detector Alarm LEDs A B illuminate Operate dete...

Page 14: ...fire panel via a conventional trigger circuit or addressable loop detector interface latched 5610 detections are normalized by Alarm Reset operation at the fire panel Similarly when in relay mode reset is conducted by momentary supply interruption by an external push button or other means Field of view test confirmation which requires a number of alarm triggers may more easily be conducted when th...

Page 15: ... via a trigger circuit or addressable loop interface this condition will occur on fire panel reset operation A local or remote normally closed push button may also be implemented Operation of the internal Reset push button 5 4 Fault Warning Relay Mode Fault relay de energized LP Mode End of line resistor disconnected from trigger circuit A fault warning may occur for any of the following Low faile...

Page 16: ...al Alarm operation It is preferable that the test target is of sufficient size and temperature to enable simulation at the plane of the monitored path conveyor in order to validate the view field of the Sensor Smaller and or cooler test targets may be used closer to the Sensor so as to at least confirm basic operation of the Sensor Fig 7 in Section 2 5 indicates the relationship between the surfac...

Reviews: