Signal Tower LA6-POE Operation Manual
5.1.3. STOP/Pulse Input Command
Command Description
When transmitting during the time trigger mode operation, the pattern stop/restart can be controlled.
(STOP Input)
When transmitting during the pulse trigger mode operation, the pattern can be changed. (Pulse Trigger Input)
Transmission Data Format
Product Category
AB
Identifier
P
Open
Data Size
Data Area
1 byte
41H
42H
50H
00H
00H
01H
See Below
Product Category
The product is classified in “AB.”
Identifiers
“P” is used.
Data Area
Data area byte: 1Byte
STOP input ON/Pulse Trigger input: 01H
STOP Input OFF: 00H
Reply Data
Normal Response (1 byte)
Abnormal Response (1 byte)
ACK
NAK
06H
15H
Command Transmission Example
A trigger input is executed.
Product Category
AB
Identifier
P
Open
Data Size
Data Area
1 byte
41H
42H
50H
00H
00H
01H
01H
!
CAUTION
If the STOP input is set to ON with the STOP/Pulse Input Command, the pattern will stop until STOP is
turned off.
MEMO
• It is effective only during the Smart mode operation.
• When a "Clear" command is received or the "Clear" button is pressed, STOP is also turned OFF.
• If it is being controlled by anything other than Smart mode, the STOP will be OFF.