background image

GP-M230-BX-010A 

2300 / IO 210 Manual 

    RD: June 2006 

R.L. 10A 

KH 

1.  GENERAL

 

2.  INSTALLATION REQUIREMENTS

 

2.1  MOUNTING CLEARANCES

 

Series 2300 / IO 210 Heaters must be mounted with minimum clearances as shown in Section 
8.4. It should also be located with respect to building construction and equipment so as to pro-
vide sufficient  clearance and accessibility for servicing and cleaning of burners and ignition 
control. Minimum mounting height is to be no less than 96”. Do not store or place anything di-
rectly underneath heater 

2.2  HEATER MOUNTING

 

IMPORTANT:

  

For either horizontal or angle mounting, the long axis of the heater must be 

level.  Use only non-combustible mounting hardware.  Diagram 2 on Page 5 illustrates typical 
suspension hardware that may be used., and provided by Schwank as an optional component.

 

2.3  GAS SUPPLY LINE INSTALLATION

 

All piping must be installed according to local codes. 

An approved flexible connector between the heater and gas piping must be installed.  The 
same is available as an option from Schwank. 

A drip-pocket at the inlet connection must be provided. 

On propane-fired units, a main line filter is recommended. 

Piping joint compounds must be resistant to the action of liquefied petroleum gases. 

All piping joints should be tested for leaks with a soap and water solution. 

Page 1 

Series 2300 / IO 210 Heaters are approved for both horizontal and angle mounting.  When angle 
mounting, the short axis may be rotated to a maximum of 45°; however this may direct a large 
portion of  infrared   heat   above   the   heads  of   seated occupants in many applications. 
Schwank recommends a 30° mounting angle in most applications. Refer to Diagram 8.  Im-
proper angle mounting can result in damage to the heater or unsafe operation, and will void 
warranty.  

The gas fired infra-red combined intensity heaters are suitable to be installed for heating of out-
door and non residential indoor spaces.  These installation instructions are intended for the Se-
ries 2300 / IO 210 Heaters.   
All installations must conform to the following:, all local and national code requirements in-
cluding the current CAN/CGA-B149.1 installation code for gas burning appliances and equip-
ment as well as the Canadian Electrical Code PART 1 CSAC22.1 (latest edition) must be ob-
served. All installations in the   U.S.A. must conform to local and national code requirements 
including, National Fuel Gas code ANSI Z223.1, and the National Electrical Code ANSI/NFPA 
No 70 (latest edition). Due to ever changing standards and requirements, revision to equipment 
and installation procedures may be necessary.  In case of discrepancies, the latest installation 
manual will take priority. 

Summary of Contents for 2300 series

Page 1: ...in the vicinity of this or any other appliance If you smell Gas Shut off gas to the appliance Extinguish any open flames Don t touch electrical switches Call your Gas supplier immediately FIELD CONVER...

Page 2: ...d Infrasave 5285 Bradco Boulevard Mississauga Ontario L4W 2A6 Phone 1 866 INFRASV 463 7278 Fax 905 712 8336 e mail info infrasave com Waynesboro Georgia USA 30830 Customer Service Phone 706 554 6191 F...

Page 3: ...8 3 MOUNTING OPTIONS 6 8 4 MINIMUM CLEARANCES TO COMBUSTABLES 11 8 5 SUGGESTED MOUNTING DISTANCES 12 2300 IO 210 SERIES INFRA RED PORTABLE PATIO HEATER FOR OUTDOOR AND NON RESIDENTIAL INDOOR SPACES T...

Page 4: ...s equipment It is imperative that control compartment burners and circulating air passageways be kept clean and unobstructed Warning Due to the effects of radiant heat upon certain materials it is not...

Page 5: ...s All piping joints should be tested for leaks with a soap and water solution Page 1 Series 2300 IO 210 Heaters are approved for both horizontal and angle mounting When angle mounting the short axis m...

Page 6: ...er loads such as snow c Connect heater to the main gas line An approved 1 2 flexible connector available as an option from the manufacturer must be used to absorb gas line expansion and any vibration...

Page 7: ...noxious fumes cause damage to the heater and will void the warranty Servicing of heater is essential for continued efficient operation Servicing should be carried out annually by qualified and licens...

Page 8: ...n the upper bolt to allow the rotation of the mounting bracket and the heater 2 Remove the lower bolt securing the bracket and rotate the bracket up to the service position 3 Insert the bolt in the up...

Page 9: ...0 VA and each consecutive heater will be sized at 20 VA The sum total will be the required Transformer size If total VA exceeds one size in between sizes se lect the next highest VA rating 8 2 MOUNTIN...

Page 10: ...RACKET WITH GAS HOSE AND WIRING CHAIN HANGING SUPPORT SUPPLIED WITH HEATER POST MOUNTING BRACKET 8 3 MOUNTING OPTIONS FOR THE 2300 SERIES HIGH INTENSITY HEATERS CHAIN HANGING BRACKET SUPPLIED WITH HEA...

Page 11: ...GP M230 BX 010A 2300 IO 210 Manual RD June 2006 R L 10A KH Diagram 4 2300 MOUNTING ARM TEMPLATE Page 7...

Page 12: ...GP M230 BX 010A 2300 IO 210 Manual RD June 2006 R L 10A KH Diagram 5 2300 WALL BRACKET TEMPLATE Page 8...

Page 13: ...ter using four nuts 4 Install the heater bracket to the wall mount bracket and remove the chains from the top of the heater NOTE The heater should be installed with enough slack on the wiring and a fl...

Page 14: ...GP M230 BX 010A 2300 IO 210 Manual RD June 2006 R L 10A KH Page 10 Diagram 7 SERVICING HEATER...

Page 15: ...213 N L INDOOR 6 10 5 14 5 14 5 2 5 26 17 2 5 28 2315 IO 215 N L OUTDOOR 16 8 13 5 10 2 21 12 5 2 24 5 2315 IO 215 N L INDOOR 17 11 19 16 5 3 28 5 18 5 3 30 Diagram 8 MOUNTING CLEARANCES 8 4 MINIMUM C...

Page 16: ...eight to patio floor 6 6 6 6 7 0 7 0 8 0 8 0 C Side distance to patio edge 3 6 3 6 4 0 4 0 5 0 5 0 Y Side distance be tween heaters 6 0 6 0 8 0 8 0 10 0 10 0 W Distance to wall in front 6 0 7 0 7 0 8...

Page 17: ...riod After a 5 minute complete shut off period has expired the heater may be reset manually from the Thermostat Page 13 9 ELECTRICAL REQUIREMENTS AND THERMOSTAT CONTROL All electrical installations mu...

Page 18: ...RD June 2006 R L 10A KH 11 WIRING DIAGRAM FOR 2300 IO 210 SERIES with Honeywell S87C DSI Control See page 18 for FENWAL control wiring If installing remote control JP 1234 RK refer to wiring diagram i...

Page 19: ...rom lockout is 1 5 uAmps microamps The output of the flame sensing circuit cannot be checked directly on the S87C Control body The flame sensing circuit current can be checked by bridging the flame se...

Page 20: ...FROM DSI IGNITION CONTROL TO GAS VALVE RE PLACE WIRES IF NECESSARY PERFORM IGNITION LEAD TEST DESCRIBED IN SPARK IGNITION CIRCUIT CHECK DSI MODULE IGNITION POST FOR DEFECTS SPARK IGNITER MAY BE OUT O...

Page 21: ...APPEARS NORMAL AT THE TIME CHECK FOR PROPER TEMPERATURE CONTROLLER OPERATION CHECK SENSOR FLAME SIGNAL WITH METER FOR 1 5uA MINIMUM STEADY READING REPEAT ABOVE CALL FOR HEAT ENDS SYSTEM SHUTS OFF TROU...

Page 22: ...Ground V1 Valve Power V2 Valve Ground NC Alarm S1 Remote Flame Sensor Fenwal Control Terminal Designation Error Mode LED Indication Internal Control Failure Steady on Flame with No Call for heat 2 fl...

Page 23: ...ng the thermostat or re moving 24 volts for a period of 5 seconds If the thermostat is still calling for heat after one hour the control will automatically reset and attempt to ignite the burner again...

Page 24: ...y to the ignition control GND terminal DO NOT remove the existing ground lead Slowly move the other end of the jumper wire toward the stud terminal on the ignition control to establish a spark 2 Pull...

Page 25: ...TO ENSURE THAT SITE CONDITIONS ARE COMPATIBLE WITH THIS HEATER AND TO ALLEVIATE NUISANCE CALL BACKS FOR THE CONTRACTOR THE FOLLOWING START UP NEEDS TO BE COMPLETED BY THE LICENSED GAS INSTALLER A CON...

Page 26: ...EATER WAS FIELD TEST FIRED WITHOUT ANY MALFUNCTION YES NO INLET GAS SUPPLY PRESSURE WITH HEATER OPERATING WC GAS VALVE OUTLET Manifold PRESSURE WITH HEATER OPERATING WC HAS THE WIRING POLARITY BEEN MA...

Page 27: ...GP M230 BX 010A 2300 IO 210 Manual RD June 2006 R L 10A KH 18 Replacement Parts List Only the following illustrated parts are available For any other parts please contact the manufacturer Page 23...

Page 28: ...GP M230 BX 010A 2300 IO 210 Manual RD June 2006 R L 10A KH...

Page 29: ...cts improperlyinstalled misused exposed to or damaged by neg ligence accident corrosive or contaminating atmosphere water excessive thermal shock impact abrasion normal wear due to use alteration or o...

Reviews: