3. ASSEMBLY

3.1 GENERAL WARNINGS

In order to avoid all accidents or damage to the product, we 

recommend:

• The unpacking and installation operations must be carried out by at least two person

3.2 ELECTRICAL CONNECTION:

The stove is supplied with a power cable which must be connected to a 230V  50Hz 

socket.

The socket connection is at the rear of the stove

By law, the system must be equipped with grounding and a differential switch.

Make sure that the power supply cable, in its final position, does not come into contact 

with hot parts.

3.3 STOVE FEATURES

The filling compartment is located on the top. The load capacity expressed in the 

technical data is to be considered variable according to the specific weight of the 

pellet. When loading the tank it is necessary to pay particular attention as the pellet 

loading screw is located at the base of the tank.

In no case must foreign substances be introduced.

ATTENTION: it is normal for pellets to remain inside the tank at the end of the 

charge. To access the load compartment it is necessary to lift the tank lid.

Unpack the product taking care not to damage or scratch it, remove all accessories and other 

removable parts

Do not leave the packaging elements within reach of children or unassisted disabled persons 

without assistance

.

Summary of Contents for Perla

Page 1: ...Produzione stufe e termostufe a pellets e policombustibili User manual Perla CpPerla Luna Cp Luna Nina Cp Nina...

Page 2: ...Model N serial number Dealer Purchase date In this space it is advisable to mark the data of the stove in this way you can always have a reference in case of request...

Page 3: ...LCD CONTROL PANEL 5 DISPLAY 5 4 USER MENU 6 7 8 IINTRODUCTION 3 3 4 6 GENERAL DESCRIPTIONS 7 2 1 PACKAGING CONTENT 7 2 2 OPERETING WARNINGS 8 8 9 3 ASSEMBLY 1 3 1 AGENERAL WARNINGS 13 3 2 ELECTRICAL C...

Page 4: ...improper use of the product will be borne by the user Installation maintenance and any repairs must be carried out by professionally qualified personnel In case of repairs only original spare parts s...

Page 5: ...correct draft of the flue obstruction of the same or of the air intake pipe presence of residual material in the brazier that obstructs the holes alters the functioning of the stove which in the ignit...

Page 6: ...he appliance are not followed Modifications to the appliance carried out by the user or whoever on his behalf the use of inappropriate fuels or without the necessary precautions must be considered as...

Page 7: ...Kw Kg but with an advantageous purchase cost compared to traditional fossil fuels MAIS Corn is an ecological fuel renowned for its optimal thermal yield thanks to a lower level of humidity it is easy...

Page 8: ...CIOLINO Deflector ash drawer electrical cable user manual ATTENTION the shape and aesthetic characteristics of the various components may undergo variations CARATTERISTICHE TECNICHE chimney 80 mm Nina...

Page 9: ...al air exchange of an electrical connection that does not comply with the regulations and of inappropriate use of the stove The installation must be performed by a qualified technician who must issue...

Page 10: ...which it is located this air must be reintegrated through an air intake outside the room itself The appliance is equipped with a socket to be able to take the combustion air directly from the outside...

Page 11: ...ust be spaced from combustible or easily flammable materials with an air gap or insulating materials The use of flexible or extensible metal pipes or unsuitable material is not allowed Single or doubl...

Page 12: ...ique for each generator no discharges in the flue shared with other devices are allowed figure 6 figura 7 If the smoke exhaust is inserted inside a pre existing flue this must be certified for solid f...

Page 13: ...haust of fumes is ensured It must prevent the entry of rain snow and be without mechanical suction aids the chimney pot must be positioned in such a way as to exceed the ridge of the roof and must be...

Page 14: ...VE FEATURES The filling compartment is located on the top The load capacity expressed in the technical data is to be considered variable according to the specific weight of the pellet When loading the...

Page 15: ...er than the boiling point it is therefore necessary that the heating system is designed compatibly with the characteristics of the machine During installation and during operation keep in mind that th...

Page 16: ...and to position in the case of assembly with closed vessel an automatic vent valve at the outlet of the thermo stove delivery pipe if the kit is not installed in the appliance ATTENTION IDRO boilers a...

Page 17: ...INDICATIVE ASSEMBLY DIAGRAMS Classic connection diagram with radiators Connection diagram with heat exchanger for direct sanitary Hydro connection diagram with underfloor system...

Page 18: ...nitary boiler Complete hydro connection diagram with solar panel P Circulator S Gate valve RIE Filling Valv Sfiato Vent valve P Circulator already in the boiler AQP Water ELE Electricity Mis Mixer Val...

Page 19: ...r the thermostat is reset manually and must be done by pressing the buttons located on the back of the boiler and covered by screw on caps Info The intervention of the technical assistance center for...

Page 20: ...user manual Motherboard Connections...

Page 21: ...g 3 men access 4 start and stop 5 6 power increase decrease setting tasto 1 tasto 6 tasto 5 tasto 2 tasto 3 tasto 4 AIR FAN IN THE INTERNAL MODEL THERE IS AN AMBIENT FAN IT IS POSSIBLE TO ADJUST THE P...

Page 22: ...e the auger is empty so loading the pellets will take several minutes 4 4 IGNITION AND NORMAL OPERATION Before proceeding with lighting the stove Check that the door is well closed Make sure that the...

Page 23: ...asts about 5 minutes At the end of the stabilization phase FIRE PRESENT the stove passes to the normal working phase WORK As soon as the ignition phase is finished the stove goes into normal working m...

Page 24: ...ues to operate at maximum speed for a minimum time of about 10 minutes to ensure complete cooling of the stove The hot air fan also continues to operate until the stove cools down and turns off ATTENT...

Page 25: ...n the figure The contact to be used is of the NO type Normally open if there is no clean contact place a relay between the thermostat and the terminal board of the machine The connection of unsuitable...

Page 26: ...CONSOLE...

Page 27: ...28...

Page 28: ...5 4 USER MENU...

Page 29: ...USER MENU 09 Technical menu 10 Abilita combustibile 11 Tipo combustibile under key 1 2...

Page 30: ...USER MENU...

Page 31: ...USER MENU...

Page 32: ...and so on up to PROGRAM 4 USER MENU...

Page 33: ...USER MENU...

Page 34: ...his parameter allows the selection between the 2 configurations in the memory Selection after activation 1 or 2 USER MENU usable only by technician under lock and key usable only by technician under l...

Page 35: ...OFF START Operation mode To light the stove press button P4 for a few seconds Display changes the state of all Lighting the Boiler...

Page 36: ...T TEMP MODIFY SET WATER TEMP Ignition failure At the end of the ignition phase the stove goes into the normal working mode Work time To change the temperature ambient please taste the P2 button and af...

Page 37: ...ed Modulation of fan When the temperature of water reach the set value the boiler goes at minimum level This is a step by step phase and terminated itself into MODULATION PHASE Modulation of boiler Th...

Page 38: ...o make the connection on the motherboard instead of the bridge 10 pole terminal block pin 3 4 Stove start when contact is closed free contact Connection and use of external thermostat If the ignition...

Page 39: ...als and with a predetermined duration In this phase the fume extractor will increase the number of revolutions while the fuel drop will be reduced to a minimum to allow cleaning of the brazier and con...

Page 40: ...For safety reasons re ignition of the stove will be possible when the fumes are cold and a pre established technical cooling time has elapsed OFF TIME RE START Re start Stop...

Page 41: ...checks and will continue if the working conditions are valid in the state prior to the power failure as per the following diagram OPERATION STATE ALARM NO FIRE LACK OF ELECTRICITY in all other cases t...

Page 42: ...s case the stove goes into stop Alarm sond fume This error occures when sond of fume is broken or dirty or there are a problem inside the motherbord Alarms If some problems can be appare in the stove...

Page 43: ...tself the stop procedure ALARM STOP DURING WORKING TIME If during normal work of stove the flame turn off and the temperature of fume falls below a determinate threshold of work it s activated the ala...

Page 44: ...Once a week or if there is a lot of residue clean the baffles Before re igniting the stove check that the brazier is inserted correctly and that the hole corresponds to the spark plug the pellet tank...

Page 45: ...e residues of the 18 front tubes will fall into the compartment ash then remove any residues vacuuming everything the residues of the 4 largest pipes will fall into the ash collection compartment whic...

Page 46: ...residues have accumulated inside the tank it is necessary to completely empty the tank and check that there are no residues that obstruct the normal operation of the auger It is also necessary to carr...

Page 47: ...t the product cool down reset the thermostat until the lock goes out and turn the appliance back on if the problem persists contact technical assistance door open or seals worn Close the door and repl...

Page 48: ...is weak Insufficient combustion air Make sure that the air intake in the room is present and free Clean the brazier and check that all the holes are clean Carry out a general cleaning of the combusti...

Page 49: ...pump blocked Unblock the circulator Insufficient water temperature Wait for the temperature to reach 50 The sufa does not ignite Lack of electricity Check that the electrical outlet is plugged in and...

Page 50: ...PR45 PR13 PR46 PR14 PR47 PR15 PR48 PR16 PR49 PR17 PR50 PR18 PR51 PR19 PR52 PR20 PR53 PR21 PR54 PR22 PR55 PR23 PR56 PR24 PR57 PR25 PR58 PR26 PR59 PR27 PR60 PR28 PR61 PR29 PR62 PR30 PR63 PR31 PR64 PR32...

Page 51: ...____________________________________________________________ Eventuali ricambi_______________________________________________________ __________________________________________________________________...

Page 52: ...____________________________________________________________ Eventuali ricambi_______________________________________________________ __________________________________________________________________...

Page 53: ...non originali fa decadere la garanzia 7 Non previsto nessun indennizzo per il periodo di inefficienza della stufa o termostufa in attesa di riparazione 8 La garanzia personale e non cedibile a terzi 9...

Page 54: ...po aver constatato che l installazione stata effettuata in accordo alle normative vigenti certifica di aver effettuato la prima accensione verificando il regolare funzionamento della stufa Il cliente...

Page 55: ...CERTIFICAZIONE AMBIENTALE 4 STELLE...

Page 56: ...MANUALE UTENTE USO E MANUTENZIONE PASIAN SRL SOGLIANO CAVOUR LE Tel Whatsapp 0836 543750 Fax 0836 544431 www pasianpellets it info pasianpellets it info pasian eu...

Reviews: