background image

 

Room Thermostat

High Limit 

Thermostat 

90°C

Circulating Pump

Low Limit Thermostat (45°C)

Time Switch

Drain Cock

 

Room Thermostat

High Limit 

Thermostat 

90°C

Circulating Pump

Low Limit Thermostat (45°C)

Time Switch

Drain Cock

Injector Tee

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Wiring Diagram for general guidance only 
 

All electrical work must be carried out by a competent 
electrician in accordance with the rules in force and the 
instructions provided by the circulating pump and 
heating controls manufacturer 

Two Tapping System 

Four Tapping System 

Summary of Contents for consort 9 CE V.II

Page 1: ...lation and Operating Instructions An accredited competent person must carry out the installation of this appliance alternatively your local Building Control Officer can approve the completed installation should a non accredited engineer undertake the installation It is an offence under UK law not to comply with this advice Please hand these instructions to the stove user when the installation is c...

Page 2: ... CO Emission at 13 O2 0 52 Mean Flue Gas Temperature 283 C Flue Gas Mass Flow 8 9 g s Ancit Total Efficiency 71 4 Nominal Heat Output 8 0 KW Output to Water 6 3 KW Output to Room 1 7 KW Mean CO Emission at 13 O2 0 30 Mean Flue Gas Temperature 257 C Flue Gas Mass Flow 9 8 g s This appliance is not suitable for use in a shared flue This appliance is suitable for continuous burning ...

Page 3: ...mit fumes into the room Flue Collar Place the Flue Gasket on the top or rear outlet as required Place the Flue Collar on top of the Gasket Secure to the four locating tabs inside the flue outlet using the M6 screws Fit the 2 M8 carriage bolts washers nuts into the Damper Holes located on each side of the Flue Collar Blanking Plate Fit the Flue Gasket and Blanking Plate on the remaining free outlet...

Page 4: ...ocal building control department must approve the installation Scheme Web address Telephone APHC Association of Plumbing and Heating Contractors Certification Limited www aphc co uk 02476 470 626 Building Engineering Services Competence Accreditation BESCA Limited www hvca org uk www besca org uk 0800 652 5533 HETAS Ltd Heating Equipment Testing and Approval Scheme www hetas co uk 01462 634721 NAP...

Page 5: ...he flue draught should be checked under fire at high output If it exceeds the recommended maximum a draught stabiliser must be fitted so that the rate of burning can be controlled and to prevent over firing If the reading is less than the recommended minimum then the performance of the appliance will be compromised Connection to the Chimney An existing fireplace opening can be bricked up or sealed...

Page 6: ...mm thick and should be in accordance with the current building regulations Care should be taken to level the stove using the adjusting screws in the feet The appliance shall be installed on a floor with adequate load bearing capacity If the existing construction does not meet this prerequisite suitable measures e g load distributing plate should be taken to achieve it MINIMUM DISTANCE TO COMBUSTIB...

Page 7: ...boiler If a common flow and return is used these should also be taken from diagonally opposite sides of a wraparound boiler and plugs inserted into the sockets not used Systems using a common flow and return to the boiler should incorporate an injector tee on the primary return connection from the central heating pump see diagram A HIGH LIMIT thermostat should be fitted to the gravity flow pipe cl...

Page 8: ... Circulating Pump Low Limit Thermostat 45 C Time Switch Drain Cock Injector Tee Wiring Diagram for general guidance only All electrical work must be carried out by a competent electrician in accordance with the rules in force and the instructions provided by the circulating pump and heating controls manufacturer Two Tapping System Four Tapping System ...

Page 9: ...Primary Air The thermostat at the rear of the stove controls the primary air The door sliders should be kept closed or the thermostat will not be able to control the fire Secondary Air Secondary air is controlled via the slider above the doors it is this Airwash that keeps a clean and uninterrupted view of the fire Damper Assembly Optional When the damper is set in the open position the chimney dr...

Page 10: ... when burning more reactive fuels to leave the grate in a neutral position thus directing some under fire air and some over fire air to the firebed Notes on solid mineral fuel burning Solid mineral fuel should be placed in the stove so that there is no more than a 30 incline of the fuel bed from front to back It should not be stacked above the bottom of the baffle as this may result in damage to t...

Page 11: ...toxic but for your comfort we would suggest that during this period you leave all doors and windows open First load the fire with starting fuel i e paper dry sticks and or firelighters in the mode chosen either wood or solid mineral fuel Light the fire at the base leaving all air controls open Allow the fuel to reach a steady glow and build the fire up gradually Once you have a good fire establish...

Page 12: ...ny part of the stove starts to glow red the fire is in an overfire situation and the controls should be adjusted accordingly Never leave the stove unattended for long periods without first adjusting the controls to a safe setting careful air supply control should be exercised at all times WARNING FUME EMISSION Properly installed and operated this appliance will not emit fumes Occasional fumes from...

Page 13: ...ded as these can scratch the glass and make subsequent cleaning more difficult Wet logs on heated glass a badly aimed poker or heavy slamming of the doors could crack the glass panels The glass will not fracture from heat Firebricks In normal use these can last for many years It is possible however to crack them if logs are continually jammed against them or if they are frequently struck with a po...

Page 14: ...e stove and the open fire Gaskets All gasket used on this appliance are produced from a heat resistant material called Manniglas Over time you may find that the gasket changes colour This is due to a reduction in the pigment used in the manufacture of the product and is no cause for concern Troubleshooting Fire will not burn Check that 1 The air inlet is not obstructed in any way 2 Chimneys and fl...

Page 15: ...08 Catch HMSS04 037 Glass Clip HHR08 046 Glass Clip Screw FSJM05008SS Door Glass CH08 028 Glass Gasket CH08 029 Right Hand Door CH08 004 Door Slider CH06 006 Slider Knob HHR08 045 Left Hand Door CH08 005 Glass Clip HHR08 046 Glass Clip Screw FSJM05008SS Door Slider CH06 006 Slider Knob HHR08 045 Door Glass CH08 028 Glass Gasket CH08 029 ...

Page 16: ...ing Bar Upper CNS09 016 Flue Collar CH08 030 Flue Cover CH08 031 Primary Air Deflector Multifuel HHR08 088 Riddling Support CNS09 027 Catch Bar Drop in CNS09 004 Ashpan HHR08 032 Side Brick HHR08 116 Primary Air Deflector Wood HHR08 157 Log Catch Bar CNS09 014 Top Air Controls Top Air Deflector HHR08 026 Top Air Slider CNS09 010 Slider Knob HHR08 045 ...

Reviews: