background image

 
 

 

 

PART NUMBER 

54099314

PARKER HANNIFIN CORPORATION 
VERIFLO DIVISION 
250 CANAL BOULEVARD, P.O. BOX 4034 
RICHMOND, CA 94804-0034 

INSTRUMENTATION 

SCALE:      -------- 

REV. 

A

SHEET     

3

     of     

3

 

VERIFLO 

Example:  SPE coefficient                   = 1 psig per 100 psig 
                Starting supply pressure      = 500 psig 

    Final supply pressure          = 100 psig 
 
    Delivery Pressure decrease=  SPE x (

Starting 

Supply

 Pressure – Final S

upply

 Pressure

 

   =  1x (500-100)= 4 psi  

 
 

SPECIAL INSTRUCTIONS 

 

Preset Regulators: 

Preset regulators do not have an adjusting knob and are set at the factory to provide a specified 

delivery pressure. When pressure is applied to the inlet of the preset regulator, the delivery pressure may exceed the 
specified delivery pressure if the system is not flowing gas. The downstream system must be flowing or vented to reduce 
the pressure to the preset delivery pressure. 
 

Dome Operated Regulators:

  Dome operated regulators do not have an adjusting knob. Regulator delivery pressure is 

controlled by supplying air or nitrogen gas pressure to the 1/8” NPT port in the regulator cap. Delivery pressure is 
increased as dome pressure is increased and decreased as dome pressure is decreased. If gas is not flowing it will be 
necessary to vent the downstream system to reduce the pressure. When using dome operated regulators adhere to the 
following precaution: 

do not allow the dome pressure to exceed 210 psig.  

 
 

MAINTENANCE 

 

 

 

 
IMPROPER REPAIR OR SERVICING OF THIS PRODUCT CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. 
 

Veriflo Division products must pass rigid acceptance tests before leaving the factory. All repairs and servicing of this product must only be performed by 
factory certified personnel and tested for operation and leakage. Veriflo Division cannot assume responsibility for the performance or safety of a 
customer repaired or serviced product or for any damages resulting from failure of a customer repaired or serviced product or otherwise altered product. 

 

Maintenance:

  A pressure regulator should be checked periodically for proper and safe operation. A pressure regulator 

should also be checked after cylinder changes or system maintenance. The user is solely responsible for ensuring that 
the recommended checks can be safely performed and are adequate to ensure proper and safe operation of the user’s 
system. 

A regulator that does not comply with the recommended checks or malfunctions in any manner must be 

immediately removed from service. Do not attempt to repair the regulator.

 

 

Check for regulator seat leak. Fully close the regulator by turning the adjusting knob counter clockwise until the stop is 
reached. Apply pressure to the regulator inlet. Close the upstream supply valve. Monitor the pressure between the 
supply valve and the regulator for 5 minutes. The pressure should not decrease. 

 

Check flow shutoff.  Confirm  after  flow is stopped, that delivery pressure does not exceed the regulator’s maximum 
outlet pressure. 

 

Check the regulator function. Confirm delivery pressure increases when the adjusting knob is turned clockwise or 
dome pressure increased, and decreases when turned counter clockwise or dome pressure decreased. 

 

Check for leaks to atmosphere. There should be no leaks to atmosphere. Use a leak test method compatible with your 
system. 

 

Removing a regulator from service: 

Follow your system safety and maintenance procedures when removing a 

regulator from service. Before removing the regulator, the user must: 

 

Isolate the regulator from all pressure sources upstream and downstream of the regulator by closing the appropriate 
valves.  

 

Lockout valves and other system equipment as required.  

 

Properly purge hazardous gases from the regulator. 

 

Vent all pressure in the regulator. 

 

WARNING

 

Reviews: