Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 100’s digit. 

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds will save the 

set point. The digits will stop blinking.

GAIN or DERI MODE

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds to enable the 

proportional gain set point to be changed. The set point is displayed and 

the 100’s digit will blink. 

Pressing the

 UP

 button will increase the set point by 100 steps per degree.

Pressing the 

DOWN

 button will decrease the set point by 100 steps per 

degree.

Pressing  the 

ENTER

  button  will  change  the  flashing  digit  from  100’s 

digit to the 10’s digit. 

Pressing the 

UP

 button will increase the set point by 10 steps per degree.

Pressing the 

DOWN

 button will decrease the set point by 10 steps per 

degree. 

Pressing the 

ENTER

 button will change the flashing digit from 10’s digit 

to the 1’s digit.

Pressing the 

UP

 button will increase the set point by 1 step per degree.

Pressing  the 

DOWN

  button  will  decrease  the  set  point  by  1  step  per 

degree. 

Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 100’s digit. 

Press and hold 

UP

 button and 

ENTER

 button together for 5 seconds to 

save the set point. The digits will stop blinking.

INTG MODE

 

Press and hold 

UP

 button and 

ENTER

 button for 5 seconds to enable the 

integral set point to be changed. The set point is displayed and the 100’s 

digit will blink. 

Pressing the 

UP

 button will increase the set point by 100 seconds.

Pressing the 

DOWN

 button will decrease the set point by 100 seconds.

Pressing  the 

ENTER

  button  will  change  the  flashing  digit  from  100’s 

digit to the 10’s digit.

Pressing the 

UP

 button will increase the set point by 10 seconds.

Pressing the 

DOWN

 button will decrease the set point by 10 seconds.

Pressing the 

ENTER

 button will change the flashing digit from 10’s digit 

to the 1’s digit.

Pressing the 

UP

 button will increase the set point by 1 second.

Pressing the 

DOWN

 button will decrease the set point by 1 second.

Pressing the 

ENTER

 button will change the flashing digit from 1’s digit 

to the 100’s digit.

Press and hold 

UP

 button and 

ENTER

 button together for 5 seconds to 

save the set point. The digits will stop blinking.

SELECTING REFRIGERANTS

If  display  reads  one  of  the  refrigerants,  press  and  hold 

UP

  button  and 

ENTER

  button  simultaneously  for  5  seconds  to  enable  the  controller 

to change to another type of refrigerant. All 4 digits will start to blink.  

Pressing the 

UP

 button or the 

DOWN

 button will change the display to 

other refrigerants. When the display shows the desired refrigerant, press 

and hold 

UP

 button and 

ENTER

 button for together 5 seconds. The con-

troller will save and use that refrigerant’s table for saturated temperature. 

The digits will stop blinking.

CHANGING VALVE TYPES

If display reads 

LARG

SMAL

, or 

MEDM

, pressing and hold 

UP

 button 

and 

ENTER

 button for 5 seconds will enable the controller to change to 

the other type of valves. All 4 digits will start to blink. Pressing either the 

UP

 button or the 

DOWN

 button will change the display between the dif-

ferent valve types. Press and hold 

UP

 button and 

ENTER

 button together 

for 5 seconds to save the selection. The digits will stop blinking.

Evaporator

DI1

1- 

1S

1+

R = Red

G = Green

W = White

B = Black

TS2 - Temp. Sensor 2

TS1 - Temp. Sensor 1

PB1 PB2

8.8.

Temperature

Sensor

Temperature

Sensor

Subcooled 

Liquid Outlet

ESX, SER, 

SEI, SEH

TS2

TS1

B

W

G

R

1+ 1S

1-

DI1

24 

VA

C

24 VAC

40 VA

Transformer

Pumpdown

Relay

(optional)

Pressure

Transducer

  * 

gray wire for ESX only

 ** 

supplied

  †  ESX

    R  = Orange

    G  = Yellow

    W = Red

    B  = Black

LINE

Mov**

Mov**

*

2.5”

1.98”

1.37”

8.25”

5.0”

.25” typical
.25”

Figure 3

Board Dimensional Drawing

Figure 4

Subcooler Controller Wiring Schematic