Parker Sporlan S3C Startup Manual Download Page 2

SD-476 / 92021 

© 2021 Parker Hannifin Corporation

Parker Hannifin Corporation

Sporlan Division

206 Lange Drive • Washington, MO 63090 USA
phone   636 239 1111
fax  

636 239 9130

www.sporlan.com

CAT5

CAT5

RS-485

RS-485

Alternate

Location #1

Alternate

Location #2

NOTE: 

Each comm port 

on BAS may need 

a specific RS-485 

address.

NETWORK DIAGRAM 

(BAS & RS-485 cables are not required.)

 

 

representative and the iOS 

 

 

mobile device of the technician  

  

on site to connect with S3C Case  

 

 

Control via Bluetooth. 

 

ii.  Allows the approval of certain  

 

 

changes to S3C parameters but  

 

 

will not override any existing  

 

 

supervisory controller (BAS).

d.  S3C Display Module
 

i.  Instructions for the menu may  

 

 

be found in Sporlan S3C I/O  

 

 

Manual Bulletin 100-50-9.1

 

ii.  Allows users with Technician  

 

 

level or Administrative level  

 

 

password to make changes on  

 

 

their authority level.

 

iii.  Find manual at http://solutions. 

 

 parker.com/literature-100.

 

iv.  Other product literature found  

 

 

at: solutions.parker.com/ 

 

 sporlanliterature

5. RESOURCES

Sporlan Technical Support
a.   E-mail: [email protected]

b.   Phone: 

888-920-6284

 

i.  Extensive emergency support  

 

 

for S3C Controls.

 

ii.  Toll free in U.S.

 

iii.  Dispatcher will send your  

 

 

contact info to a Sporlan  

 

 

representative that will call the  

 

 

number you provide. 

 

 

  a.   Please offer First   

 

 

 

   and Last name, Phone  

 

 

 

   number, Store Number,  

 

 

 

   City, and State along  

 

 

 

   with brief explanation  

 

 

 

   of the issue.  

6. QUICK TIPS

 

-

For viewing settings, changing modes, 

and other technician-level options, press 

the service (wrench) button and enter the 

Technician-level password. For setting 

up the system or making configuration 

changes, press the wrench button and 

enter the administrative-level password.

 

-

Depending on the firmware revision of 

the S3C Controller, the administrative 

-level passwords may change daily. 

Contact Sporlan for assistance.

 

-

To manually exit “Test” or “Charge 

Pro” mode press the “ESC” button on 

the S3C Display Module for 5 seconds.

 

-

To connect to S3C controller via 

Bluetooth, hold down “     ” button for 

5 seconds until signal indicator begins 

flashing.

 

-

To initiate a manual defrost, press the 

snowflake button and enter the  

technician-level password. Then set DEF 

to ON.

Figure above: Store network showing 4 comm loops into one BAS. A BAS is not required. Sporlan S3C controls can 

operate cases and/or walk-ins as “stand-alone” controllers.

If multiple comm loops are attached to a single BAS, the RS-485 addresses will need to be determined from store 

drawings or BAS provider. Default RS-485 address in S3C Controllers is “7”, but OEMs or technicians may need to 

change to “8”, “9”, etc., as shown above.