Introduction
20 (109)
192-011006N8 2019-07
09.10.19 09:27
Tightening torque
0.22 ... 0.25 Nm
1.95 ... 2.21 Lb.in
Mains module
X40: Ballast resistor
UL
up to AWG10
CE
up to 6 mm
2
Tightening torque
0.46 ... 0.57 Nm (M3)
4 ... 5 Lb.in
X41: Mains connector
PSD1-M_P010
UL
up to AWG10
CE
up to 6 mm
2
Tightening torque
1,1 ... 1.7 Nm
11 ... 15 Lb.in
X41: Mains connector
PSD1-M_P020
UL
up to AWG6
CE
up to 16 mm
2
Tightening torque
1.7 Nm
15 Lb.in
X9: 24 VDC
Steuerspannung
UL
up to AWG10
CE
up to 6 mm
2
Tightening torque
1.1 ... 1.7 Nm
11 ... 15 Lb.in
DC Bus
UL
-
CE
-
Tightening torque
0.8 Nm
7 Lb.in
*
max 0.5mm
2
ferrule with plastic sleeve
2.10.4.4
Conditions of utilization for CSA certification
External Overvoltage Protection
External overvoltage protection in accordance with Canadian Standards
C22.2-No.274-13 with over-voltage protection device (VZCA2) CSA-certified.
Note the following table:
Mains module Manufacturer
Model No
(Quantity 1)
Maximum
Continuous
Operating
Voltage (Vac)
Voltage
Protection
Rating
(VPR)(Vpk)
Category
/
Nominal earth
leakage current
PSD1-M_P01
0
PSD1-M_P02
0
ABB
Frankreich
(E322885)
OVR T2 3N
40-440 P(TS)U
L-GND
420 Veff Max
L-L
840 Veff Max
L-GND
1500 V Max
L-L
3000 V Max
1
/
10 kA
Cooper Bussmann LLC
(E340782)
BSPM 4480 WY NGR
L-GND
660 Veff Max
L-L
770 Veff Max
L-GND
2500 V Max
L-L
2500 V Max
1
/
20 kA
DEHN + SOEHNE GmbH
+ Co. KG. (E319777)
904 346
Ground rail not sufficient
For CSA approval, earth rail must be replaced by a direct earth connection.
Risk of Electric Shock, wait at least 10 minutes before removing cover.
Removing the earth rail (4) (Right):