4 - Rev. E

PNC200 - PNC1200 USER GUIDE

•  Air piping must be supported independently of the dryer.

•  A properly sized Parker pre-filter is recommended ahead of the dryer to maintain 

optimal performance and warranty validation. It should be installed as close to the 
dryer as possible.  Any piping between the pre-filter and inlet of the dryer must be 
stainless steel, copper, galvanized, aluminum or other non-corroding material.  A 
union between the pre-filter and the dryer is recommended for ease of assembly 
and change-out of filter element. Please refer to section 10.1 for proper pre-filter 
selection.

•  Direction of the air flow must be observed for proper installation. 

•  Install a bypass line and gate valves to permit isolation of the dryer from the air 

system.  This is done to provide easy service and/or removal of the dryer without 
interruption of air to the system.    

        

•  Make the connection to the draining system, avoiding connection in a closed circuit 

shared by other pressurized discharge lines.  Check the correct flow of condensate 
discharges.  Dispose of all condensate in conformity with current local environment 
regulations.  

•  Set drain time intervals to ensure complete condensate removal from dryer.

 

2.2   

Electrical Connections

To be performed by a qualified person only.  Risk of serious injury or death.  Observe 
Lock out/Tag Out Procedure: Disconnect, lock out and tag all power at source prior 
to attempting repairs or adjustments to rotating machinery and prior to handling any 
ungrounded conductors.   

Provide breach and short circuit protection as well as disconnect means per local and 
national codes.

 

Before connecting electrical power to the dryer check for correct voltage at the 
connection box.  Panel Removal:  To remove front or side panels, remove screws and lift 
panel up, then pull out the bottom.

All units must be externally grounded to protect against severe electrical shock.

1. 

Remove electric box cover from inside unit.

2. 

Locate the wires.

3. 

Locate hole on side of box, place and tighten connector, run wires through  

 

 connector.
4. 

Make sure no bare wire is exposed; replace box cover and screw closed.

5. 

Line input wiring connections are made to line side on compressor contactor

6. 

Should the compressor not start, see start up procedure.  

 

 

Wire the dryer separately from the air compressor.  The dryer must not cycle  

 

 

 

 

with the air compressor.  

     

Crankcase heaters are pre-wired from the factory to the line side of the compressor 
contactor. When power is applied to the dryer, the heater will energize. Heater must be 
energized for 8 hours prior to start–up and after prolonged shut down. The power must 
be left on at all times except when servicing.

Summary of Contents for PNC200

Page 1: ...User Guide Rev E Models PNC200 PNC1200 Parker Non Cycling Refrigerated Dryer Effective September 2015 Supercedes HY25 1890 M1 US June 2015...

Page 2: ...3 Controls Standard on all models 5 4 Start Up Procedures 6 4 1 When Operating Dryer 6 5 Routine Maintenance 7 6 Maintenance Schedule 8 6 1 Maintenance Procedures 8 7 Troubleshooting Service 9 7 1 Ref...

Page 3: ...n ambient temperature between 41 100 F 5 38 C and free from explosive and corrosive fumes Three 3 feet 92cm of space must be allowed between all open grills If the dryer is installed in a confined are...

Page 4: ...ns To be performed by a qualified person only Risk of serious injury or death Observe Lock out Tag Out Procedure Disconnect lock out and tag all power at source prior to attempting repairs or adjustme...

Page 5: ...Standard on all models Dryer ON OFF Switch Dryer POWER Light HIGH REFRIGERANT PRESSURE ALARM LOW REFRIGERANT PRESSURE ALARM DEWPOINT TEMPERATURE INDICATOR Adjustable time drain module mounted directly...

Page 6: ...s may be the result of shipping damage see section 1 0 4 Switch unit on ON OFF indicator will light 5 Do not pass air through the dryer until it stabilizes Typically 5 minutes 6 Once the dryer stabili...

Page 7: ...sis for dirt or debris that might accumulate Remove any debris immediately The strainer should be checked weekly Pre filtration per installation instructions Parker pre filter should be installed dire...

Page 8: ...ndensing coil fins air cooled units only Dryer Compressor oil level sight glass 250 to 1200 SCFM Filtration Depressurized dryer Replace pre and after filter elements Dryer Check for refrigerant leaks...

Page 9: ...loose connection open 3 Check electrical circuit Adjustments should only be made under the guidance of a certified refrigeration technician The controls interact with each other and although the effec...

Page 10: ...1 2 1 5 16 1 25 460 3 60 5 4 23 1 0 6 1 5 7 9 10 575 3 60 5 4 23 1 0 6 1 5 6 3 10 PNC700 230 3 60 15 7 98 1 3 1 2 23 2 35 460 3 60 7 1 38 1 1 5 1 2 11 0 15 575 3 60 7 1 38 1 1 5 1 2 8 8 15 PNC850 230...

Page 11: ...AOP040HNFI P040AO AAP040HNFI P040AA PNC250 AOP040HNFI P040AO AAP040HNFI P040AA PNC325 AOP040HNFI P040AO AAP040HNFI P040AA PNC400 AOP040HNFI P040AO AAP040HNFI P040AA PNC500 AOP04 5INFI P045AO AAP045INF...

Page 12: ...12 Rev E PNC200 PNC1200 USER GUIDE 11 Associated Drawings REF ADE11374 REV E...

Page 13: ...13 Rev E PNC200 PNC1200 USER GUIDE REF ADE11374 REV E...

Page 14: ...14 Rev E PNC200 PNC1200 USER GUIDE REF ADE11374 REV E...

Page 15: ...15 Rev E PNC200 PNC1200 USER GUIDE REF ADE11374 REV E...

Page 16: ...16 Rev E PNC200 PNC1200 USER GUIDE REF ADE11374 REV E...

Page 17: ...17 Rev E PNC200 PNC1200 USER GUIDE REF ADE11374 REV E...

Page 18: ...switch 230v n a DP40080 9C Fan 2 pressure switch 460v 575v n a DP40106 10 High refrigerant pressure switch DP40133 11 Low refrigerant pressure switch DP40026 12 Refrigerant gauge DP42107 13 Timed dra...

Page 19: ...xploded Views DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 200 EXPLODED ASSY AD11511 2 1 1 16...

Page 20: ...CALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 200 EXPLODED ASSY AD11511 2 2 1 16 2014 5 4 6 8 7 14 15 13 SEE...

Page 21: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 250 EXPLODED ASSY AD11510 2 1 1 15 2014 26...

Page 22: ...ZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 250 EXPLODED ASSY AD11510 2 2 1 15 2014 20 21 3 2B 2A 11 10 9A 1C 1B 1A 14 15 13 5...

Page 23: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 325 EXPLODED ASSY AD11509 2 1 1 15 2014 26...

Page 24: ...ZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 325 EXPLODED ASSY AD11509 2 2 1 15 2014 20 21 3 2B 2A 11 10 9A 1C 1B 1A 14 15 13 5...

Page 25: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 400 EXPLODED ASSY AD11508 2 1 1 15 2014 26...

Page 26: ...TLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 400 EXPLODED ASSY AD11508 2 2 1 15 2014 20 21 3 2B 2A 11 10 9A 1C 1B 14 15 1...

Page 27: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 500 EXPLODED ASSY AD11507 2 1 1 14 2014 26...

Page 28: ...TLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 500 EXPLODED ASSY AD11507 2 2 1 14 2014 13 4 8 7 6 14 15 3 2B 2A 21 20 9A 10...

Page 29: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 700 EXPLODED ASSY AD11506 2 1 1 14 2014 12...

Page 30: ...TLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 700 EXPLODED ASSY AD11506 2 2 1 14 2014 8 7 6 5 13 4 SEE CONDENSING UNIT DET...

Page 31: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 850 EXPLODED ASSY AD11505 2 1 1 14 2014 12...

Page 32: ...TLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 15 NON CYCLING 850 EXPLODED ASSY AD11505 2 2 1 14 2014 8 7 6 5 13 4 SEE CONDENSING UNIT DET...

Page 33: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 16 NON CYCLING 1050 EXPLODED ASSY AD11504 2 1 1 14 2014 19...

Page 34: ...E SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 16 NON CYCLING 1050 EXPLODED ASSY AD11504 2 2 1 14 2014 5 13 6 10 7 8 4 2B 1C 9A 9B 21 20 SEE...

Page 35: ...UIDE DRAWN BY DATE SCALE UNITS TITLE SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 16 NON CYCLING 1200 EXPLODED ASSY AD11503 2 1 1 14 2014 19...

Page 36: ...E SIZE SHEET DRAWING NUMBER REVISION PARKER HANNIFIN FAF DIVISION LANCASTER NY 14086 USA INCHES OF B RJS 1 16 NON CYCLING 1200 EXPLODED ASSY AD11503 2 2 1 14 2014 5 13 6 10 7 8 4 2B 1C 9A 9B 21 20 SEE...

Page 37: ...dicate a response on a scale of 1 being the lowest to 5 being the highest Condition of Arrival Ease of Installation Ease of Start Up Product Quality Technical Assistance Clarity of Instruction Warrant...

Page 38: ...s Etten Leur Netherlands 31 76 508 5300 www parker com dhfns Hiross Airtek Essen Germany 49 2054 9340 www parker com hzfd Padova Italy 39 049 9712 111 www parker com hzfd Engine Filtration Water Purif...

Reviews: