20
E-GAS outputs
6 Installation
Instruction book, IQAN- XT2
E-GAS outputs
The E-GAS outputs (Electronic Gas) control a motor-type throttle device. Maximum
load should not exceed 2,5 A.
Connecting load to E-GAS output
The load is connected between the +EGAS, -EGAS and the EGAS_RET (feedback
signal dedicated to VIN-A).
For the maximum load per output, see Appendix A, on page 23.
N
OTICE
The working area of the EGAS actuator should be 10%-90% of its travel. The EGAS
actuator must be aligned parallel to the diesel engine injector lever.
Do not exceed maximum torque of the EGAS actuator, see the EGAS manufacturer’s
datasheet for torque specification.
The EGAS mechanical requirements.
EXAMPLE
Positive and negative direction:
Connect the load between the +EGAS, position 8, and the -EGAS, position 9.
EGAS Position feedback:
Connect the EGAS_RET to VIN-A, position 21, the +VREF_EGAS, position 10 and
the-VREF_EGAS, position 11.
Connecting a load to the EGAS outputs.
-VREF_EGAS, pos.11
IQAN-XT2
VIN-A, pos.21
EGAS-, pos. 9
EGAS+, pos. 8
+VREF_EGAS, pos.10
EGAS
E-Gas servo
Diesel injection
>10%
min.
<90%
max.