Hyperchiller 310-360
perature is too low, add the appropriate quantity of glycol, as
explained under heading 3.4.2
4.2.3 Stop
Water Outlet Temp.
b1 : 7.0 C°
Pump :
Comp 1: Comp 3:
Comp 2: Comp 4:
Press the button
(P2)
to enter in the “main” menu.
Press the button
(P5)
to select the parameter “OFF”
OFF
Press the button
(P6)
to stop.
Warning: Do not turn off the main switch QS [P0] to ensure
that any antifreeze protection devices will still receive elec-
trical power.
4.3 Visualization probes
Water Outlet Temp.
b1 : 7.0 C°
Pump :
Comp 1: Comp 3:
Comp 2: Comp 4:
Press the button
(P5)
to visualize the probes.
Water Outlet Temp.
b2 : 5.0 C°
Pump :
Comp 1: Comp 3:
Comp 2: Comp 4:
After few minutes return to the probe B1.
4.4 Visualization of digital outputs/analog inputs
Press the button
(P5)
for several times to view the digital
outputs and the analog inputs available
DIGITAL OUTPUT
Pump :
Compressor 1 :
Compressor 2 :
Compressor 3 :
Compressor 4 :
DIGITAL OUTPUT
A/Freeze :
Unit Status :
Gen.Alarm :
Fan 1 :
Fan 2 :
Fan 3 :
ANALOG INPUT
b1 : 10.0 C°
b2 : 7.0 C°
b5 : 20.0 C°
P1 : 10.0 bar
P2 : 10.0 bar
4.5 Parameter settings
General
There are three levels of protection for parameters:
a) DirE (D): with immediate access, for user access;
b) User (U): password protected: for sevice technician;
C) Fact (F): factory parameters don’t changeble.
4.6 Direct parameter (DIrE)
Press the button
(P2)
to enter in the “main” menu.
Press the button
(P5)
to select “DIrE”
Press the button
(P6)
to confi rm.
Press the button
(P5)
to scroll the parameter.
Press the button
(P6)
to enter
Press the button
(P4)
or
(P5)
to modify.
Press the button
(P6)
to confi rm
4.6.1 Direct parameter
PARAMETER
CODE
TYPE DEFAULT
Temperature control set point
SEt
D
7.0
Temperature control differential
dIF
D
4.0
High temperature alarm
HA1
D
60.0
Low temperature alarm
LA1
D
-20.0
Chiller hour counter
HU
D
-
Compressor 1 operation hour
counter
H1
D
-
Compressor 2 operation hour
counter
H2
D
-
Compressor 3 operation hour
counter
H3
D
-
Compressor 4 operation hour
counter
H4
D
-