3.3.6.
C3Sxxx V4
In this chapter you can read about:
Power supply connector X1 for 3AC 400VAC/480VAC-C3S devices................................................31
Braking resistor / high voltage supply connector X2 for 3AC 400VAC/480VAC_C3S devices .........32
Connection of the power voltage of 2 C3S 3AC devices ...................................................................33
3.3.6.1
Power supply connector X1 for 3AC 400VAC/480VAC-C3S
devices
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which will cause a device error.
Therefore please wait at least 2 minutes after switching off before you switch
the device on again!
PIN
Designation
1 L1
2 L2
3 L3
4 PE
Mains connection Compax3SxxxV4 3AC
Controller type
S015V4
S038V4
S075V4
S150V4
S300V4
Supply voltage
Three phase 3*400VAC/480VAC
80-528VAC / 50-60Hz
Input current
3Aeff 6Aeff 10Aeff
16Aeff
22Aeff
6A 10A 16A 20A
25A
Maximum fuse rating per
device(=short circuit
rating)
MTP miniature circuit breaker
D*
* for
UL conform operation
(see page 18): MTP miniature circuit breaker S273-K.
The 3AC V4 – devices must only be operated with three phases!
Always switch devices off before wiring them!
Dangerous voltages are still present until 5 minutes after
switching off the power supply!
Device protection
Caution!