Introduction
Single axis devices
10
192-
120102N23 2016-04
Device:
Compax3S
Limit value
class
Motor cable length
Mains filter
Order No.:
S0xxV2
C2
< 10 m
without
C2
> 10 m, < 100 m
NFI01/01
S1xxV2,
S0xxV4, S150V4
C2
< 10 m
without
C2
> 10 m, < 100 m
NFI01/02
S300V4
C3*
< 7.5 m
without
C2, C3
< 100 m
NFI01/03
* only at standard frequency of the power amplifier
(8
kHz)
.
Connection length: Connection between mains filter and device:
unshielded: < 0.5 m
shielded
< 5 (fully shielded on ground - e.g. ground of control cabinet)
2.7.1.2
Conditions of utilization for cables / motor filter
Motor and Feedback
cable:
Operation of the devices only with motor and feedback cables whose plugs
contain a special full surface area screening.
< 100 m (the cable should not be rolled up!)
A motor output filter is required for motor cables >20 m:
MDR01/04 (max. 6.3 A nominal motor current)
MDR01/01 (max. 16 A nominal motor current)
MDR01/02 (max. 30 A nominal motor current)
Shielding connection of
the motor cable
The cable must be fully-screened and connected to the device housing. Use the
cable clamps/shield connecting terminals furnished with the device.
The shield of the cable must also be connected with the motor housing. The fixing
(via plug or screw in the terminal box) depends on the motor type.
< 100 m
Corresponding to the specifications of the terminal clamp with a temperature range
of up to 60°C.
Cable installation:
Signal lines and power lines should be installed as far apart as possible.
Signal lines should never pass close to excessive sources of interference
(motors, transformers, contactors etc.).
Do not place mains filter output cable parallel to the load cable.
2.7.1.3
Additional conditions of utilization
Motors:
Operation with standard motors.
Control:
Use only with aligned controller (to avoid control loop oscillation).
Grounding:
Connect the filter housing and the device to the cabinet frame, making sure that
the contact area is adequate and that the connection has low resistance and low
inductance.
Never mount the filter housing and the device on paint-coated surfaces!
For CE and UL conform operation of the Compax3S300V4, a mains filter is
compulsory:
400 VAC / 0.740 mH certified in accordance with EN 61558-1 bzw. 61558-2-2
We offer the mains filter as an accessory: LIR01/01
Accessories:
Make sure to use only the accessories recommended by Parker.
Connect all cable shields at both ends, ensuring large contact areas!
This is restricted operation category product according to EN 61800-3. This product
can cause high-frequency disturbance in domestic areas. Users are asked to take
suitable action if this proves to be the case.
Compax3S motor
cable
Feedback cable
Compax3S
Cable
Compax3S300V4