Parker EME
Plug and connector assignment Compax3 Fluid
192-121100 N8 September 2014
15
3.2.4.
Analog Input (plug X1)
Connector X1 Pin Description Combicon 3.81mm; female connector
1
24V
Supply Sensor 0
2
GND
Supply Sensor 0
3
IN0+
Signal Sensor 0 +
4
IN0-
Signal Sensor 0 -
5
24V
Supply Sensor 1
6
GND
Supply Sensor 1
7
IN1 +
Signal Sensor 1 +
8
IN1 -
Signal Sensor 1 -
9
24V
Supply Sensor 2
10
GND
Supply Sensor 2
11
IN2 +
Signal Sensor 2 +
12
IN2 -
Signal Sensor 2 -
13
24V
Supply Sensor 3
14
GND
Supply Sensor 3
15
IN3 +
Signal Sensor 3 +
16
IN3-
Signal Sensor 3 -
17
IN4+
+/-10V Input 4
18
IN4-
+/-10V Input 4
19
IN5+
+/-10V Input 5
20
IN5-
+/-10V Input 5
Requirement: Connection cable
Use shielded cables.
Shield connection of the cables
The cable must be fully-screened and connected to the Compax3 housing. Use the
cable clamps/shield connecting terminals furnished with the device.
3.2.4.1
Wiring of the analog current inputs
Input IN0
10pF
200K
Ω
200K
Ω
In0-
200K
Ω
X1/4
200K
Ω
In0+
X1/3
250
Ω
Compax3
IN0 to IN3 do have the same wiring!
Pin assignment
(see on page 15) X1
3.2.4.2
Wiring of the analog voltage inputs
Input IN4
1nF
22.1K
Ω
100K
Ω
In4+
22.1K
Ω
X1/17
100K
Ω
1nF
In4-
X1/18
2.5V
Compax3
IIN4 and IN5 (X11/19 and X11/20) have the same wiring!