Parker CK-6D Installation, Service And Parts Information Download Page 1

Refrigerating Specialties Division

1

BULLETIN 50-25B

Type CK-6D

CK-6D

Fig 1

Dual  Position

 

Gas  Powered 

Suction

 

Stop Valve

Type CK-6D

Port Size: 50mm to 100mm (2” – 4”)

For Ammonia, R-22 and

other common Refrigerants 

Features

•  Economical Solution to Evaporator Equal-

ization after Defrost

•  Low Pressure Drop

•  Heavy Return Spring

•  Manual Opening Stem

•    Integrated S6B pilot solenoids

•  Standard  Coil  Housing  Meets  NEMA  3R 

and 4 - Rain Tight

•  Normally Open

•  Maximum Rated Pressure (MRP): 27.6 bar 

(400 psig)

Description

The CK-6D is based on the same valve body, principles, 

and  length  dimension  as  the  standard  CK-5  valves 

making for easy field replacements. This heavy duty 

gas-powered  valve  is  suitable  for  ammonia,  R-22, 

and  other  refrigerants,  certain  oils  and  other  fluids 

approved for use in refrigeration. The CK-6D is a pilot 

operated,  dual-position  valve. This valve is equipped 

with a manual opening stem and A2D pressure pilot.  

The  CK-6D  is  a  normally  open  valve  and  will  open 

remain open if open on power failure or open to it's 

intermediate position if closed on power failure and 

the inlet pressure exceeds the set point.

The Type CK-6D Gas-Powered Valve is furnished with 

FPT Internal NPT (U.S. Standard Taper Pipe Thread), 

Socket  Weld,  Weld  Neck  or  ODS  (solders  over  cop-

per tubing of given diameter) connections. The valve 

may be easily removed from between the flanges for 

servicing. 

Purpose

These  valves  are  employed  as  low  pressure  drop, 

gas-powered suction stop valves for low temperature 

evaporators.  Because of the return spring, there is no 

line pressure drop required to open the valve during 

refrigeration.  This allows for a minimal pressure drop 

November 2006

Installation, Service and Parts Information

311447

I S O   9 0 0 1 - 2 0 0 0  C E R T I F I E D

Solenoid #2

Solenoid #1

Primary

Piston

Secondary

Piston

Summary of Contents for CK-6D

Page 1: ...operated dual position valve This valve is equipped with a manual opening stem and A2D pressure pilot The CK 6D is a normally open valve and will open remain open if open on power failure or open to...

Page 2: ...ons The main valve will open to it s intermediate position however since residual pressure in the coil is transmitted through the pilot regulator to the top of the top piston Note The pilot regulator...

Page 3: ...e as stamped on coil The supplycircuitsmustbeproperlysizedtogiveadequate voltage at the coil leads even when other electrical equipment is operating The coil is designed to oper ate with line voltage...

Page 4: ...Refrigerating Specialties Division 4 CK 2D Fig 2...

Page 5: ...Packing Kit 1 202100 202101 21 Solenoid Tube O 1 10 Gasket Adapter 1 29 Seat 1 11 Piston Top 1 29 31 Plunger Seat Kit 1 204707 204707 204707 204707 12 Spacer Piston 3 3 6 10 16 21 25 Gasket O ring Ki...

Page 6: ...0 2 500 4 19 7 139 7 5 5 251 9 9 198 7 8 234 9 2 371 14 6 307 12 1 15 0 6 38 1 5 65 2 5 528 3 20 8 142 2 5 6 251 9 9 224 8 8 246 9 7 401 15 8 331 13 25 1 43 1 7 75 3 624 8 24 6 216 8 5 311 12 2 257 10...

Page 7: ...igerating Specialties Division 7 R S Defrost Controller Wiring Diagram CK 2D CK 6D Line Equilization S4AD Soft Start R S Adjustable Time Delay Wiring Diagram Valve Sequencing Line Equalization on Open...

Page 8: ...person is authorized to give any warranties on behalf of Refrigerating Specialties nor to assume for Refrigerating Specialties any other liability in con nection with any of its products Safe Operati...