Parker EME

 

Conditions of utilization 

2.7.3. 

Current on the mains PE (leakage current) 

 

This product can cause a direct current in the protective lead. If a residual current 

device (RCD) is used for protection in the event of direct or indirect contact, only 

a type B (all current sensitive) RCD is permitted on the current supply side of this 

product . Otherwise, a different protective measure must be taken, such as 

separation from the environment by doubled or enforced insulation or separation 

from the mains power supply by means of a transformer. Respect the supplier's 

instructions. 

Mains filters do have high leakage currents due to their internal capacity. An 

internal mains filter is usually integrated into the servo controllers. Additional 

discharge currents are caused by the capacities of the motor cable and the motor 

winding. Due to the high clock frequency of the power output stage, the leakage 

currents do have high-frequency components. Please check if the FI protection 

switch is suitable for the individual application. 

If an external mains filter is used, an additional leakage current will be produced. 

The figure of the leakage current depends on the following factors: 

 

Length and properties of the motor cable

 

Switching frequency

 

Operation with or without external mains filter

 

Motor cable with or without shield network

 

Motor housing grounding (how and where)

Remark: 

 

The leakage current is important with respect to the handling and usage safety of

the device.

 

A pulsing leakage current occurs if the supply voltage is switched on.

Please note: 

The device must be operated with effective grounding connection, which must 

comply with the local regulations for high leakage currents (>3.5 mA). 

Due to the high leakage currents it is not advisable to operate the servo drive with 

an earth leakage circuit breaker. 

 

2.7.4. 

Supply networks 

This product is designed for fixed connection to TN networks (TN-C, TN-C-S or 

TN-S). Please note that the line-earth voltage may not exceed 300VAC.   

 

When grounding the neutral conductor, mains

voltages of up to 480VAC are permitted.

 

When grounding an external conductor (delta

mains, two-phase mains), mains voltages (external

conductor voltages) of up to 240VAC are

permitted.

Devices which are to be connected to an IT network must be provided with a 

separating transformer. Then the devices are operated locally as in a TN network. 

The secondary sided center of the separating transformer must be grounded and 

connected to the PE connector of the device. 

 

192-

120149N12 2017-09

11 

Summary of Contents for C3Manager-Compax3H

Page 1: ...r devices 192 120149 N12 2017 09 Release as from R09 63 We reserve the right to make technical changes 06 09 2017 192 120149N12 2017 09 The data correspond to the current status at the time of printin...

Page 2: ...GmbH Co KG Electromechanical Drives Division EME Robert Bosch Strasse 22 77656 Offenburg Germany Tel 49 0781 509 0 Fax 49 0781 509 98176 Internet www parker com eme http www parker com eme E mail sale...

Page 3: ...32 Bit 64 Bit Browser MS Internet Explorer 8 x or higher Processor Intel AMD Multi core processor 2GHz User 1024MB Hard disk 20GB available memory Monitor Resolution 1024x768 or higher Graphics card...

Page 4: ...eakage current 11 2 7 4 Supply networks 11 2 8 EC declaration of conformity Compax3H 12 3 Mounting and dimensions C3H 13 3 1 Mounting distances air currents Compax3H050V4 14 3 2 Mounting distances air...

Page 5: ...400VAC 480VAC 3 Unique number of the particular device 4 Nominal supply voltage Power Input Input supply data Power Output Output data 5 Designation of the feedback system F10 Resolver F11 SinCos Sing...

Page 6: ...ironmental laws The following table states the materials suitable for recycling and the materials which have to be disposed of separately Material suitable for recycling Disposal Metal yes no Plastic...

Page 7: ...mergency rescue services who have read and will observe the safety instructions who have read and observe the manual or help or the sections pertinent to the work to be carried out This applies to all...

Page 8: ...x the devices according to the mounting instructions see on page 13 We cannot provide any guarantee for other mounting methods Note on exchange of options Device options must be exchanged in the facto...

Page 9: ...ield connecting terminals furnished with the device The shield of the cable must also be connected with the motor housing The fixing via plug or screw in the terminal box depends on the motor type 100...

Page 10: ...4 are not suitable for flat line bars Temperature rating of field installed conductors shall be at least 75 C Do only use copper lines Maximum Surrounding Air Temperature 45 C Motor overtemperature mo...

Page 11: ...on the following factors Length and properties of the motor cable Switching frequency Operation with or without external mains filter Motor cable with or without shield network Motor housing groundin...

Page 12: ...Introduction High power devices 2 8 EC declaration of conformity Compax3H 12 192 120149N12 2017 09...

Page 13: ...tion Please provide for a sufficient mounting distance below and above the device in order to ensure free circulation of the cooling air Please do also respect the recommended distances of other devic...

Page 14: ...nts Compax3H050V4 J I K M L mm I J K L M C3H050V4 15 5 25 70 70 3 2 Mounting distances air currents Compax3H090V4 J I K M L mm I J K L M C3H090V4 0 0 25 70 70 3 3 Mounting distances air currents Compa...

Page 15: ...8VAC 50 60Hz Receiver current consumption 54Arms 82Arms 118Arms 140Arms Output current 43Arms 85Arms 110Arms 132Arms Maximum input fuse rating per device 80A 100A 160A 200A Recommended line protection...

Page 16: ...Technical Data High power devices 16 192 120149N12 2017 09...

Reviews: