Parameter Reference
D-91
AC30V series Variable Speed Drive
Stack Inv Time
Parameters::Motor Control::Stack Inv Time
The purpose of the inverse time is to automatically reduce the drive current limit in response to prolonged overload conditions.
For a short time given by
Stack Short Overl’d Sec
, the drive is able to provide the
Stack Short Overl’d %.
For a long time given by
Stack Long Overl’d Sec
, the drive is able to provide the
Stack Long Overl’d %.
These 2 protections work in parallel, the output limit current is the maximum value if
Stack Inv Time Active
= False. If
Stack Inv Time Active
=
True, the current limit is determined by
Stack Long Overl’d
%.
the current limit is not yet ramped down. If already ramped down, the current limit is due to the long overload.
When the maximum overload value is reached, the inverse time current limit is ramped down. The rate at which the inverse time current limit is
ramped to the
Stack Aiming Point %
is defined by
Inverse Time Down Rate
. When the overload condition disappears, the inverse time current
limit is ramped up. The rate at which the inverse time current limit is ramped to the maximum value is defined by
Inverse Time Up Rate.
% Are all referring to drive/stack ratings.
PNO Parameter Descriptions
100% Stack Current
Stack rating in rms amps corresponding to 100% stack current
Stack Long Overl'd %
Overload value in % of the stack amps for long overload condition
Stack Long Overl'd Sec
Maximum duration under long overload condition (typically 60s)
Stack Short Overl'd %
Overload value in % of the stack amps for short overload condition
Stack Short Overl'd Sec
Maximum duration under short overload condition (typically 3s)
Stack Aiming Point %
Current in % where the power stack can undertake the load current permanently
Stack Inv Time Output %
Actual output current limit as a % of the stack current
Summary of Contents for AC30V Series
Page 34: ...Installation 4 16 AC30V series Variable Speed Drive Basic Speed Control Wiring...
Page 35: ...4 17 Installation AC30V series Variable Speed Drive APPLICATION 1 AUTO MANUAL CONTROL...
Page 36: ...Installation 4 18 AC30V series Variable Speed Drive Auto Manual Control Wiring...
Page 37: ...4 19 Installation AC30V series Variable Speed Drive APPLICATION 2 RAISE LOWER TRIM...
Page 38: ...Installation 4 20 AC30V series Variable Speed Drive Raise Lower Trim Wiring...
Page 39: ...4 21 Installation AC30V series Variable Speed Drive APPLICATION 3 PRESETS SPEEDS...
Page 40: ...Installation 4 22 AC30V series Variable Speed Drive Presets Speeds Wiring...
Page 41: ...4 23 Installation AC30V series Variable Speed Drive APPLICATION 4 PID CONTROL...
Page 42: ...Installation 4 24 AC30V series Variable Speed Drive PID Control Wiring...
Page 162: ...Sequencing Logic B 2 AC30V series Variable Speed Drive SEQUENCING DIAGRAM...
Page 325: ...E 2 E Plan Library AC30V series Variable Speed Drive Which then brings up the E Plan page...