DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
62 (125)
DOC-0017-03-EN-B 04.04.2023
9 Basic Drive Operation
9.1 ‘Local’ Operation
To run the drive using either the onboard keypad, or the 6901 remote keypad, the following steps need to
be followed.
Note: This sequence assumes that the power connections (ac line supply & motor output
connections) have already been connected as per the installation instructions.
Minimum Connections
The minimum control connections required to run the drive in ‘
Local
’ mode, are shown below.
The motor thermistor needs to be connected (or linked out), and the STO function needs to be disabled i.e.,
drive operational.
Configuration Setup:
TH1
Motor Thermistor ‘+’ connection (link to TH2 if no motor thermistor fitted)
TH2
Motor Thermistor ‘-’ connection
STO
STO
DISABLED
(drive operational)