Installation
3-13
890GTR Inverter Power Manual HA502996
Wiring Requirements
**WARNING: Parker Inverters must be installed using wiring methods according to the
requirements of ANSI/NFPA 70, Canadian Electrical Code Part I, or other appropriate local or
national electrical codes. It is the responsibility of the installer to ensure installation is designed
and performed in compliance with these standards.
Function
Wire size**
Mating Connector
Notes
DC Ground
Minimum 21.2 mm
2
wire (4 AWG) Wire Lug
Tightening torque 6-7 Nm (4.4-5.2 lb-ft)
AC Ground
Minimum 13.3 mm
2
wire (6 AWG) Wire Lug
Tightening torque 6-7 Nm (4.4-5.2 lb-ft)
DC Bus Connection
Minimum 33.6 mm
2
(2 AWG)
Amphenol Powerlok,
300 Series,
2 Position with X Polarization
Maximum continuous current = 160A
DC
AC Bus Connection
Minimum 33.6 mm
2
(2 AWG)
Amphenol Powerlok,
300 Series,
3 Position with X Polarization
Maximum continuous current = 128A
RMS
HVIL & Emergency Stop Minimum 0.3 mm
2
(22 AWG)
Maximum 0.8 mm
2
(18 AWG)
AMP 172168-1
(Mini Mate-N-Lok Housing)
AMP 770988-1
(crimp socket, 18-22 AWG)
Discrete I/O
Minimum 0.14 mm
2
(28 AWG)
Maximum 1.5 mm
2
(16 AWG)
Phoenix Contact 1803646
(MC 1,5/9-ST-3,81)
Auxiliary Power Out
Minimum 2.1 mm
2
(14 AWG)
IEC type C14 (male)
Rated output = 120V, 750VA, 50/60Hz
Auxiliary Power In
Minimum 2.1 mm
2
(14 AWG)
IEC type C13 (female)
120V (+/-5%), 150VA, 50/60Hz
Communication Port
Cat5 w Shield Ethernet Cable
RJ-45
Programming Port
Mini-USB
Mini-USB
Summary of Contents for 890GTR
Page 2: ......
Page 90: ...8 1 Ethernet 890GTR Inverter Power Manual HA502996 Chapter 8 Ethernet ...
Page 109: ...Compliance C 10 890GTR Inverter Power Manual HA502996 ...
Page 113: ...Compliance C 14 890GTR Inverter Power Manual HA502996 ...
Page 130: ...E 12 Technical Specifications 890GTR Inverter Power Manual HA502996 Earthing Safety Details ...