Parker 023-0388 Specification & Installation Manual Download Page 4

 

72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx 

RL 2022-02-09 

Page 4 of 4 

Addition of CO2 sensor model for MTA V5.X version (suite)  

 
Manufacturer: 

Micro Thermo

  

Diagram: 

CD2RMC Wall Sensor Transmitter 20mA.bmp 

Physical type: 

Gas Concentration

 

Electrical type: 

4-20mA

 

Choose Absolute 
Time Constant: 

2

 s 

Max Range: 

6000

 ppm 

Min Range: 

0

 ppm 

Max Offset: 

±200

 ppm 

Point 1: 

0.02

A at 

6000

 ppm 

Point 2: 

0.004

A at 

0

 ppm 

Max send time: 

30 s

 

Min send time: 

3

 s 

Send on delta: 

40

 ppm 

 

Addition of CO2 sensor model for MTA V6.X version  

 
Create sensor in the menu « Configure-Sensor Model » for the following models  
Model on key 341 :023-0388 CO2 6000 ppm (4-20mA)  
If « CDD4 Wall Sensor Transmitter 20mA.bmp » is in the folder « Images-Sensor Models » it could be used but is not exactly the 
same.  

 

Example in MTA V6.0 

 

 

Configuration of alarm limits 

 