72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx
RL 2022-02-09
Page 4 of 4
Addition of CO2 sensor model for MTA V5.X version (suite)
Manufacturer:
Micro Thermo
Diagram:
CD2RMC Wall Sensor Transmitter 20mA.bmp
Physical type:
Gas Concentration
Electrical type:
4-20mA
Choose Absolute
Time Constant:
2
s
Max Range:
6000
ppm
Min Range:
0
ppm
Max Offset:
±200
ppm
Point 1:
0.02
A at
6000
ppm
Point 2:
0.004
A at
0
ppm
Max send time:
30 s
Min send time:
3
s
Send on delta:
40
ppm
Addition of CO2 sensor model for MTA V6.X version
Create sensor in the menu « Configure-Sensor Model » for the following models
Model on key 341 :023-0388 CO2 6000 ppm (4-20mA)
If « CDD4 Wall Sensor Transmitter 20mA.bmp » is in the folder « Images-Sensor Models » it could be used but is not exactly the
same.
Example in MTA V6.0
Configuration of alarm limits