Parker 023-0388 Specification & Installation Manual Download Page 1

 
 
 
 

72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx 

RL 2022-02-09 

Page 1 of 4 

Parker Hannifin Canada

 

Micro Thermo Technologies 

TM

 

12855 rue Brault

 

Mirabel, QC J7J 0C4 Canada

 

Office phone 450-668-3033

 

 

Technical Data 

023-0388 Wall mount CO2 Leak Detector  

specification & installation guide 

 

Precision carbon dioxide 

control/sensing 

 

FEATURES: 

• 2 Available Ranges 
• Automatic Calibration Logic Program 
• Easy field adjustment 
• LCD Display and analog out 
• On-board Relay and menu driven set-up 
• Solid-state reliability 
• Small compact size  
• Solid, reliable mounting method 

 
 

DESCRIPTION: 

The CO2 monitor uses a highly accurate and reliable Non-dispersive Infrared (NDIR) sensor with state-of-the-art 
digital linearization and temperature compensated circuitry in an attractive, low profile enclosure for room 
applications to detect CO2 levels and provides a linear analog signal output of 4-20 mA, 0-5 or 0-10 Vdc signals. An 
onboard relay can provide a control signal based on a high limit setting. Parameters are set up via momentary 
pushbutton (keypad) and the LCD display which is also used to display current reading.  
 

SPECIFICATIONS: 

Gas Type Detected  ........................................................................................  Carbon Dioxide (CO

2

Measurement Ranges  ..................................................................................  0 – 2000, 0 – 6000 ppm 
Measurement Type  ...................................................  Dual channel non-dispersive infrared (NDIR) 
Sensor Coverage Area  ...............................................................................  100 m² (1000 ft²) typical 
Sensor Accuracy .............................................................................. 

 

± 30ppm + 3% of reading value 

Relay Trip Point (High or Low) ............  Programmable 500 – 9000 ppm by step of 100 via keypad 
Relay Hysteresis  ..................................................................  Programmable 25-500 ppm via keypad 
Contact Ratings  ...........................  Form A contact (N.O.), 2 Amps @ 140 Vac, 2 Amps @ 30 Vdc 
Reading Resolution  .........................................................................................................  1 ppm CO

2

 

Backlight  ...................................................................................  Auto, Enable or disable via keypad 
Power Supply  ............................  24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified) 
Consumption  ........................................................  75 mA @ 24 Vdc max, 150 mA @ 24 Vac max, 
Output Signals  ..........................  4-20 mA active (sourcing), 0-5 Vdc or 0-10 Vdc (field selectable) 
Output Drive Capability  ........................................  Current: 550 ohms max Voltage: 10k Ohm min 
Output Accuracy  ........................ ±0.25% of span (including linearity, hysteresis and repeatability) 
Response Time  ...................................................................................................... 

 

20 seconds (T63) 

Operating Temperature ...................................................................................  0°- 50°C (32°-122°F) 
Storage Temperature  ..............................................................................  -40 to 70°C (-40 to 158°F) 
Operating and Storage Humidity  ......................................................  5 to 90 %RH, non-condensing 
Sensor Life Expectancy  ........................................................... 

 

>15 years in normal room condition 

Altitude Correction  .........................................................  Programmable from 0-2550 m via keypad 
Screw Terminal Block  ...............................................................................................  14 to 22 AWG 
Enclosure Ratings  ...............................................................................  ABS White, IP30 (NEMA 1) 
External Dimensions  ..................................  84mm W x 119mm H x 29mm D (3.3” x 4.7” x 1.15”) 
Mounting Holes  ...............................................................................................  Multiple possibilities