English
5/8
Hyperchiller 450-760
pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 3 bar < P1< 5 bar
- Example n°2.
Conditions:
open circuit, pressure P0 = 0 bar
pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 1 bar < P1 < 3 bar
c) Verify correct operation of the pump similarly under normal run-
ning conditions.
Check also that the amperage of the pump is within the limits indi-
cated on the data plate.
d) Switch off the chiller and proceed to top up the hydraulic circuit at
the “SET” temperature.
e) Check that the temperature of the “treated” water does not fall
below 5 °C and that the ambient temperature in which the hydraulic
circuit operates does not fall below 5 °C. If the temperature is too
low, add the appropriate quantity of glycol, as explained under head-
ing 3.4.2
4.3.2 Adjustments
setpoint
M0
Inlet water 00.08C
Outlet water 00.08C
U1 ON CH
a-MAINTENANCE
i-Input/Output
k-clock
s-Setpoint
Actual setpoint S0
00.08C°
a-MAINTENANCE
i-Input/Output
k-clock
s-Setpoint
Summer S1
Setpoint yy.yyyy
Winter
Setpoint-------
Summer S1
Setpoint 00.008
Winter
Setpoint-------
4.4 Parameter settings
General
Th
ere are two levels of protection for parameters:
a) Direct (D): with immediate access,
User-changeable;
b) Password protected (U): password required for access;
Factory-set
parameters.
4.4.1
Parameter Set point (Diretto)
PARAMETER
Screen
Master
/Slave
Default
Summer setpoint
S1
M/S
12.0
4.4.2
Chiller Parameters (User)
PARAMETER
Screen
Master
/Slave
Default
Enter password.
P0
M/S
1234
Summer setpoint min. limit.
P1
M/S
7.0
Summer setpoint max. limit.
P1
M
17.0
Select adjustment probe.
P3
M
inlet
Type of adjustment with evaporator
inlet probe.
P4
M
proportio-
nal
Summer forced deactivation - outlet
adjustment.
P5
M
5.0
Adjustment range.
P6
M
3.0
Enable remote On/Off Pa
M/S
N
Type of On. Remote Off from
master.
Pa
M
on-off unità
Enable On/Off by supervisor.
Pl
M/S
N
Alarm relay logic.
Pl
M/S
N.A.
Enable language screen at start-up.
Pc
M/S
S
Supervision network card identifi ca-
tion number.
Pj
M/S
1
Supervision network card commu-
nication speed.
Pj
M/S
19200
Select serial communication net-
work.
Pj
M/S
modbus
Select type of unit of measure.
Pm
M
Standard
Enter new password.
Pk
M/S
-
4.5 Alarms management
CODE
Description
RESET
011
Serious Alarm
Manual
012
PhaseMonitor Alarm
Manual
031
Antifreeze Alarm
Manual
001
Unit 1 Offl
ine
Automatic
002
Unit 2 Offl
ine
Automatic
020
Compressor Th
ermal Protection
Manual
015
Diff erential Oil Pressure Switch
Manual
032
Low Pressure Diff erential
Manual
017
Low pressure switch
Manual
016
High pressure switch
Manual
034
Low Transducer Pressure
Manual
033
High Transducer Pressure
Manual
021
Fan 1 Th
ermal Protection
Manual
022
Fan 2 Th
ermal Protection
Manual
035
High delivery temperature
Manual
053
Compressor Maintenance
Manual
060
B1 Probe Fault
Automatic
061
B2 Probe Fault
Automatic
062
B3 Probe Fault
Automatic
063
B4 Probe Fault
Automatic
064
B5 Probe Fault
Automatic
065
B6 Probe Fault
Automatic
066
B7 Probe Fault
Automatic
067
B8 Probe Fault
Automatic
041
32KB Clock Card Fault
Manual
4.6 Automatic restart
In the event of a power failure, when power is restored the chiller will
assume theOn-Off statusheld at themoment the power was lost.