Paragon ERC-2 Installation Data Download Page 2

2

OPERATiON AND FUNCTiONS (Continued)

Defrost

•   Defrost type: it can programmed for hot gas or electric heater 

defrost. An off cycle defrost type can be configured by selecting  

the electric defrost option and not connecting any device to the 

defrost relay.

•   Number of defrosts per day: between 1 and 8. There is also an 

option for 1 defrost every 48 hours.

•   Defrost cycle: a choice among defrost start time (real time clock), 

accumulated compressor run time or temperature initiation defrost

•   Fan delay: amount of time that the fan will remain off after defrost  

is terminated (0 to 15 minutes).

•   Pump down: amount of time the compressor remains on after 

defrost initiates (0 to 59 minutes).

•   Drip time: amount of time the compressor remains off after defrost 

is terminated (0 to 59 minutes).

•   Defrost duration time: amount of time for the defrost duration.  

It also functions as a back-up for temperature termination.

•   Defrost termination temperature: temperature that will cause the 

defrost to terminate (if reached before defrost duration time).

•   Fan start temperature: temperature that will cause the fan to re-start 

after defrost.

Setpoint

•   Setpoint temperature (cut-out): a setpoint temperature can be 

programmed to control the compressor operation. The range is  

-40° to 60°F.

•   Cut-in differential: differential between the cut-out (setpoint) and 

the cut-in temperature. The range is 1° to 25°F.

•   High and low temperature alarm setpoint: high and low alarms for 

the temperature can be set. The ranges are -40° to 60°F for each of 

the alarms (high and low).

GRAPhiC DESCRiPTiON / DiMENSiONS

Display layout

Figure. 1

Relay Board layout

Figure. 2

Overall Dimensions - Models ERC2 – 111xxx and 211xxx 

(Metal Case / integrated Display Module)

Figure. 3

Models ERC-2 – 121xxx and 221xxx 

(Metal Case / Remote Display Module)

Figure. 4

Summary of Contents for ERC-2

Page 1: ... the Clock It maintains the correct time of day for up to 100 hours Microprocessor Based Electronics High reliability and repeatability FCC Compliance This device complies with CFR 47 Part 15 Class A FCC requirements Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference th...

Page 2: ...ation time amount of time for the defrost duration It also functions as a back up for temperature termination Defrost termination temperature temperature that will cause the defrost to terminate if reached before defrost duration time Fan start temperature temperature that will cause the fan to re start after defrost Setpoint Setpoint temperature cut out a setpoint temperature can be programmed to...

Page 3: ...re in compliance with all federal state and local requirements including without limitation all requirements imposed under the National Electric Code and any applicable building codes CAUTION To prevent possible electric shock or equipment damage disconnect electrical power to the unit before and during installation DO NOT restore electrical power to the unit until the control is properly installe...

Page 4: ...rsion 2 Connect the defrost device heater or hot gas solenoid to the terminal in the control Figs 10 and 11 3 Connect the wire from L1 120V AC or 208 240V AC line to the terminal marked as COM 4 Connect also the fan wires to the terminals marked as FAN 5 Use the alarm connections to connect an alarm to the control as shown in Figures 10 and 11 Figure 10 Load AC Input Connectors Quick Connects Figu...

Page 5: ...displayed Step 4 Press SET to accept the new time Step 5 Press DOWN to go to the next parameter Setpoint Temperature SEt cut out Step 6 Press SET to change the setpoint temperature Step 7 or Press UP or DOWN to go to the desired setpoint The range is 40 to 60 F or 40 to 16 C Step 8 Press SET to accept the change Step 9 Press DOWN to exit the first level of programming Note 1 During programming if ...

Page 6: ...from 0 to 59 minutes Compressor Run Time CPrn Time the compressor will run between defrosts Number of Defrosts nodF Number of defrosts per day from 0 to 8 0 means 1 defrost every 48 hours Defrost Start Time dEF1 8 Start time of each defrost Defrost Duration dEFd Defrost duration time back up for defrost termination temperature Range from 0 minutes to 4 hours Fan Delay FAnd Delay time for the fan a...

Page 7: ...rature Alarm indicates that the temperature has gone above the high alarm setpoint For Error Codes 1 and 2 cut the power to the unit and correct the problem to reset the display For Codes 3 and 4 press the UP or DOWN button on the display to reset the error message If the display still shows the message the sensor must be replaced The Error Codes 6 and 7 will be automatically reset once the temper...

Page 8: ... Ranco Paragon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 TechnicalService robertshaw com www uni line com www robertshaw com 2015 Robertshaw 10 15 7515010 Rev E 8 ...

Reviews: