Paragon ERC-2 Installation Data Download Page 1

INSTALLATION DATA

ERC-2 

ELECTRONIC REFRIGERATION 

CONTROL

APPLICATION

The Paragon® ERC-2 Electronic Refrigeration Control is a 

microprocessor-based electronic controller designed to control 

both the temperature and the defrost functions of a commercial 

refrigeration unit. It can be powered by 120, 208 or 240V AC  

(50 or 60 Hz). The control comes with four relay outputs: compressor, 

defrost, evaporator fan and alarm.
The ERC-2 includes a digital display module that provides readout of  

the temperature, time and built-in diagnostics. The display module  

can be mounted locally or remotely from the unit and it contains a 

touch keypad for simple programming. For defrost control, it uses a 

real time clock.
This control is NSF certified and it can be applied to many different 

commercial refrigeration applications like reach-ins, walk-ins, 

refrigerated cases or other different products where accurate control of 

refrigerated space and defrost cycles are required.

FeATures / BeNeFITs

•   Multi-function Unit 

Integrates defrost timer, temperature control, defrost termination 

switch, fan delay switch and digital thermometer

•   Display Module for Temperature Readout 

Easy to read display that can be mounted with the unit or remotely. 

Temperature can be displayed in °F or °C

•   Two Temperature Sensors 

For zone temperature and evaporator temperature

•   Choice of Defrost Methods 

Off cycle, hot gas or electric heater with up to 8 defrosts per day  

and duration up to 4 hours

•   Four Relay Outputs 

Compressor, defrost, evaporator fan and alarm

•   Adjustable Short Cycle Protection 

Extra protection for the equipment

•    Non-volatile memory 

The programmed parameters will remain in the memory

•   Capacitor Carry Over for the Clock 

It maintains the correct time-of-day for up to 100 hours

•   Microprocessor-Based Electronics 

High reliability and repeatability

FCC COMPliANCE*

This device complies with CFR 47, Part 15, Class A FCC requirements. 

Operation is subject to the following two conditions (1) This device  

may not cause harmful interference and (2) This device must accept 

any interference received, including interference that may cause 

undesired operation.

CANADiAN COMPliANCE*

This digital apparatus meets all of the Industry Canada, ICES-003, Class A 

requirements (Canadian Interference-Causing Equipment Regulations).

*  Note:

 These compliances apply to NEMA 1 enclosed models only.  

All modular units are the responsibility of the purchaser to obtain 

the compliance.

1

OPERATiON AND FUNCTiONS

The ERC-2 features a simple way to program and operate. Four buttons 

on the display module allow the user to scroll through the functions 

and set the desired parameters. A manual defrost button is used to 

initiate the defrost cycle at any time.
There are two different levels of security to access the programming 

features. The first one will allow the change on the time-of-day and the 

setpoint temperature (cut-out). The other level will allow access to the 

other parameters.
The programmable parameters are:

Clock

•   Clock: allows time-of-day programming and choice of display format 

(12 / 24 hours)

General

•   Display: the display can show time-of-day, zone temperature, 

evaporator temperature and it can also cycle between zone 

temperature and time-of-day

•  Temperature format: the control can use temperatures in °F or °C
•   Fan enable during defrost: to control the fan operation during 

defrost (on or off)

•   Minimum compressor off time: for short cycle protection,  

between 0 and 15 minutes

•  Minimum compressor on time: between 0 and 15 minutes
•   Alarm delay: a time delay can be configured for the alarm to operate, 

between 0 and 59 minutes

 

Summary of Contents for ERC-2

Page 1: ... the Clock It maintains the correct time of day for up to 100 hours Microprocessor Based Electronics High reliability and repeatability FCC Compliance This device complies with CFR 47 Part 15 Class A FCC requirements Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference th...

Page 2: ...ation time amount of time for the defrost duration It also functions as a back up for temperature termination Defrost termination temperature temperature that will cause the defrost to terminate if reached before defrost duration time Fan start temperature temperature that will cause the fan to re start after defrost Setpoint Setpoint temperature cut out a setpoint temperature can be programmed to...

Page 3: ...re in compliance with all federal state and local requirements including without limitation all requirements imposed under the National Electric Code and any applicable building codes CAUTION To prevent possible electric shock or equipment damage disconnect electrical power to the unit before and during installation DO NOT restore electrical power to the unit until the control is properly installe...

Page 4: ...rsion 2 Connect the defrost device heater or hot gas solenoid to the terminal in the control Figs 10 and 11 3 Connect the wire from L1 120V AC or 208 240V AC line to the terminal marked as COM 4 Connect also the fan wires to the terminals marked as FAN 5 Use the alarm connections to connect an alarm to the control as shown in Figures 10 and 11 Figure 10 Load AC Input Connectors Quick Connects Figu...

Page 5: ...displayed Step 4 Press SET to accept the new time Step 5 Press DOWN to go to the next parameter Setpoint Temperature SEt cut out Step 6 Press SET to change the setpoint temperature Step 7 or Press UP or DOWN to go to the desired setpoint The range is 40 to 60 F or 40 to 16 C Step 8 Press SET to accept the change Step 9 Press DOWN to exit the first level of programming Note 1 During programming if ...

Page 6: ...from 0 to 59 minutes Compressor Run Time CPrn Time the compressor will run between defrosts Number of Defrosts nodF Number of defrosts per day from 0 to 8 0 means 1 defrost every 48 hours Defrost Start Time dEF1 8 Start time of each defrost Defrost Duration dEFd Defrost duration time back up for defrost termination temperature Range from 0 minutes to 4 hours Fan Delay FAnd Delay time for the fan a...

Page 7: ...rature Alarm indicates that the temperature has gone above the high alarm setpoint For Error Codes 1 and 2 cut the power to the unit and correct the problem to reset the display For Codes 3 and 4 press the UP or DOWN button on the display to reset the error message If the display still shows the message the sensor must be replaced The Error Codes 6 and 7 will be automatically reset once the temper...

Page 8: ... Ranco Paragon and Uni Line are trademarks of Robertshaw its subsidiaries and or affiliated companies All other brands mentioned may be the trademarks of their respective owners For Technical Service Telephone 1 800 445 8299 TechnicalService robertshaw com www uni line com www robertshaw com 2015 Robertshaw 10 15 7515010 Rev E 8 ...