background image

I N T RO D U C T I O N

The EC7000, EC7004 and EC7005 are single-channel, electronic
time control that provides simple, inexpensive control of lighting,
heating, ventilation, air-conditioning, security systems, motors,
pumps, fans or any load with a time-of-day schedule. The control
may be utilized as a 24-hour or 7-day control. as a 24-hour control,
the same ON/OFF program is utilized each day of the week.
Saturday and/or Sunday, or any other day may be skipped. When
schedules vary from day to day, the 7-day programming capability
allows a different schedule for each day of the week. With 16 set-
points available, this time control provides programming versatility.

The EC7001 provides two individually programmable durations of
1-59 seconds in addition to the maintained ON and OFF setpoints.
This provides ideal control for the ringing chimes, school bells, fac-
tory bells, remote animal feeders, and air and water purity sam-
plers. On events can be combined with duration events to obtain
to-the-second ON times such as one minute and fifteen seconds
or two minutes and thirty seconds, providing excellent control for
loads that require precise ON durations longer then 59 seconds.

EC7000, EC7004 and EC7005

Single Channel 

Electronic Time  Controls

GENERAL INSTRUCTIONS

S P E C I F I C   C A PA B I L I T I E S

16 Setpoints - A setpoint defines the type of
event (ON, OFF or duration) as well as the
time and day(s) on which the event will occur.

24-hour or 7-day Programming - Allows the
same schedule or a different schedule for
each day of the week.

Selectable Clock Format - 12 hour (AM/PM)
or 24 hour format.

Manual Override - Reverses current output
state; begins immediately when initiated and
remains until overridden again or until next
setpoint is reached.

N

L

(24, 120 or 277)

L2

L1

(208 or 240)

N

L

(120 or 277V)

L2

L1

(208 or 240V)

EC7000 SPDT

EC7004 SPST

EC7005 SPST

C O N TAC T   R AT I N G S

Output 
UL Ratings

CSA Ratings

EC7000

EC7000

Normally open contacts:

Normally open contacts:

20 amp resistive at 24-240 Vac

10 amp resistive at 24-240 Vac

1 Hp at 120 Vac

1/2 Hp at 120 Vac

2 Hp at 240 Vac

1 Hp at 240 Vac

5 amp tungsten at 120-240 Vac

5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

Normally closed contacts:

Normally closed contacts:

10 amp resistive at 24-240 Vac

10 amp resistive at 24-240 Vac

1/4 Hp at 120 Vac

1/4 Hp at 120 Vac

1/2 Hp at 240 Vac

1/2 Hp at 240 Vac

3 amp tungsten at 120-240 Vac

3 amp tungsten at 120-240 Vac

3 amp ballast at 120-277 Vac

3 amp ballast at 120-277 Vac

EC7004

EC7004

Normally open contacts:

Normally open contacts:

30 amp resistive at 24-240 Vac

30 amp resistive at 120 Vac

1 Hp at 120 Vac

10 amp resistive at 240 Vac

2 Hp at 240 Vac

1 Hp at 120 Vac

5 amp tungsten at 120-240 Vac

2 Hp at 240 Vac

6 amp ballast at 120-277 Vac

5 amp tungsten at 120-240 Vac
6 amp ballast at 277 Vac

EC7005
Please refer to inner door instructions on unit or contact factory

NOTE: Paragon solid state controls utilize dry contacts, input
power enables the control to keep time, store programmed infor-
mation and carry out instructions but input power 

does not power

the load.

To make circuits function, you must provide power to

the contacts.

WIRING

Terminals can accommodate 10-16 AWG wire.

POWER OUTAGE CARRY-OVER

The program and time-of-day are maintained during a power out-
age for a minimum of 4 days. A built-in special capacitor elimi-
nates the inconvenience of battery replacement.

ENVIRONMENTAL

EC7000 & EC7004 should be mounted indoors in an environ-
ment that is free from excessive contaminants such as oil, mois-
ture and dirt. EC7005 is suitable for both indoor and outdoor use.

PHYSICAL

EC7000 and EC7004 Monuting- EC7005 Mounting-
NEMA 1 enclosure mounting

NEMA 3 enclosure mounting

Weight - Approx. 2 lbs.(0.9kg)

Weight - Approx. 3 lbs.(1.4kg)

Dimensions-

Dimensions-

Width 10.8 cm (4-1/4”)

Width 16.7 cm (6-9/16”)

Height 20.0 cm (7-7/8”)

Height 23.1 cm (8-1/8”)

Depth 7.6 cm (3”)

Depth 9.8 cm (3-7/8”)

EC7000 Bracket Mounting
Dimensions-

Width 10.4 cm (4-1/8”)
Height19 cm (7-1/2”)
Depth 6.7 cm (2-5/8”)

K E Y PA D   D E S C R I P T I O N

RUN-

Returns timer to the RUN mode. The timer will
only control the load when in the RUN mode.

MODE-

Advances from one programming mode to the
next. the order of programming modes is as
follows: Clock Format Select, Run, Set Time,
Setpoint Programming, Set Duration 1 and Set
Duration 2. After the last mode, the control will
loop back to the Run Mode.

"

Rolls through the parameter currently being 
programmed.

ENTER-

In all programming modes, what is shown in
the display is what exists in memory. Pressing
the ENTER key simply advances to the next
parameter to be programmed. (i.e. hours to
minutes).

EC7000, EC7004 and EC7005

1

4

1

2

3

4

3

2

120V jumpers

208 or 240V jumpers

See jumpers below

L

N (120v)

L1

L2 (208 or 240V)

L

N (277V no

jumpers needed)

 

 

http://waterheatertimer.org/Paragon-timers-and-manuals.html#EC

Replacement timer

http://waterheatertimer.org/Intermatic-ET-series-timers-and-manuals.html#ET1700

Summary of Contents for EC7000 Series

Page 1: ... 3 amp tungsten at 120 240 Vac 3 amp tungsten at 120 240 Vac 3 amp ballast at 120 277 Vac 3 amp ballast at 120 277 Vac EC7004 EC7004 Normally open contacts Normally open contacts 30 amp resistive at 24 240 Vac 30 amp resistive at 120 Vac 1 Hp at 120 Vac 10 amp resistive at 240 Vac 2 Hp at 240 Vac 1 Hp at 120 Vac 5 amp tungsten at 120 240 Vac 2 Hp at 240 Vac 6 amp ballast at 120 277 Vac 5 amp tungs...

Page 2: ...240 Vac 1 4 Hp at 120 Vac 1 4 Hp at 120 Vac 1 2 Hp at 240 Vac 1 2 Hp at 240 Vac 3 amp tungsten at 120 240 Vac 3 amp tungsten at 120 240 Vac 3 amp ballast at 120 277 Vac 3 amp ballast at 120 277 Vac EC7004 EC7004 Normally open contacts Normally open contacts 30 amp resistive at 24 240 Vac 30 amp resistive at 120 Vac 1 Hp at 120 Vac 10 amp resistive at 240 Vac 2 Hp at 240 Vac 1 Hp at 120 Vac 5 amp t...

Page 3: ...240 Vac 1 4 Hp at 120 Vac 1 4 Hp at 120 Vac 1 2 Hp at 240 Vac 1 2 Hp at 240 Vac 3 amp tungsten at 120 240 Vac 3 amp tungsten at 120 240 Vac 3 amp ballast at 120 277 Vac 3 amp ballast at 120 277 Vac EC7004 EC7004 Normally open contacts Normally open contacts 30 amp resistive at 24 240 Vac 30 amp resistive at 120 Vac 1 Hp at 120 Vac 10 amp resistive at 240 Vac 2 Hp at 240 Vac 1 Hp at 120 Vac 5 amp t...

Page 4: ...240 Vac 1 4 Hp at 120 Vac 1 4 Hp at 120 Vac 1 2 Hp at 240 Vac 1 2 Hp at 240 Vac 3 amp tungsten at 120 240 Vac 3 amp tungsten at 120 240 Vac 3 amp ballast at 120 277 Vac 3 amp ballast at 120 277 Vac EC7004 EC7004 Normally open contacts Normally open contacts 30 amp resistive at 24 240 Vac 30 amp resistive at 120 Vac 1 Hp at 120 Vac 10 amp resistive at 240 Vac 2 Hp at 240 Vac 1 Hp at 120 Vac 5 amp t...

Page 5: ...240 Vac 1 4 Hp at 120 Vac 1 4 Hp at 120 Vac 1 2 Hp at 240 Vac 1 2 Hp at 240 Vac 3 amp tungsten at 120 240 Vac 3 amp tungsten at 120 240 Vac 3 amp ballast at 120 277 Vac 3 amp ballast at 120 277 Vac EC7004 EC7004 Normally open contacts Normally open contacts 30 amp resistive at 24 240 Vac 30 amp resistive at 120 Vac 1 Hp at 120 Vac 10 amp resistive at 240 Vac 2 Hp at 240 Vac 1 Hp at 120 Vac 5 amp t...

Page 6: ...and no Repeat steps 3 and 4 to select which day s to include in the setpoint After pro gramming Saturday the display will show the setpoint with the hours flashing Dashes in the hour location indicate that the setpoint is still clear 5 Advance to desired hour 6 ENTER Minutes begin flashing 7 Advance to desired minute 8 ENTER Event type begins flashing 9 Display toggles between ON and OFF event typ...

Page 7: ...and no Repeat steps 3 and 4 to select which day s to include in the setpoint After pro gramming Saturday the display will show the setpoint with the hours flashing Dashes in the hour location indicate that the setpoint is still clear 5 Advance to desired hour 6 ENTER Minutes begin flashing 7 Advance to desired minute 8 ENTER Event type begins flashing 9 Display toggles between ON and OFF event typ...

Page 8: ...and no Repeat steps 3 and 4 to select which day s to include in the setpoint After pro gramming Saturday the display will show the setpoint with the hours flashing Dashes in the hour location indicate that the setpoint is still clear 5 Advance to desired hour 6 ENTER Minutes begin flashing 7 Advance to desired minute 8 ENTER Event type begins flashing 9 Display toggles between ON and OFF event typ...

Page 9: ...and no Repeat steps 3 and 4 to select which day s to include in the setpoint After pro gramming Saturday the display will show the setpoint with the hours flashing Dashes in the hour location indicate that the setpoint is still clear 5 Advance to desired hour 6 ENTER Minutes begin flashing 7 Advance to desired minute 8 ENTER Event type begins flashing 9 Display toggles between ON and OFF event typ...

Page 10: ...and no Repeat steps 3 and 4 to select which day s to include in the setpoint After pro gramming Saturday the display will show the setpoint with the hours flashing Dashes in the hour location indicate that the setpoint is still clear 5 Advance to desired hour 6 ENTER Minutes begin flashing 7 Advance to desired minute 8 ENTER Event type begins flashing 9 Display toggles between ON and OFF event typ...

Reviews: