Maintenance and Troubleshooting
5-5
9121-A2-GB20-20
May 1998
ASCII Alarm Messages
The following messages are sent to an ASCII terminal/printer if
H
One of the following configuration options is set as shown:
Main Menu
→
Configuration
→
Alarm
→
ASCII Alarm Messages
→
Com Port
Main Menu
→
Configuration
→
User Interface
→
Port Use
→
Alarm
Main Menu
→
Configuration
→
User Interface
→
Port Use
→
Terminal
or,
H
The async terminal is inactive (logged off).
When set, an alarm is sent at the start of an alarm condition. An Alarm Cleared
message is sent after all alarm conditions have been corrected. If any other alarm
conditions are present when the original alarm condition is corrected, a new
ASCII message will be sent indicating the current highest-priority alarm condition.
NOTE:
When more than one alarm condition is detected, only the highest priority
message will be sent; other alarm conditions could exist. No other alarms will
be reported until the original alarm condition has been cleared.
Example:
When a 04/10/97 10:26:32 – Frame Relay DLCI number 201 is down on
the Port-1 Interface message is reported, you could also have a Primary or
Secondary Clock Source Failure, as well.
All messages in the following table are listed in order of priority. Each message is
preceded by the name of the access unit ( Device Name), up to 20 characters
( Path: main/control/device name), as well as the date and time that the message
was generated in the month/day/year hour:minute:second (
mm/dd/yy hh:mm:ss)
format.
Message
What It Indicates
What To Do
mm/dd/yy hh:mm:ss –
Power Supply Alarm
condition detected.
A power supply problem
is detected on the
system.
Also indicates a fan tray
problem if using an
access carrier.
1. Check that the power supply
is mounted correctly in the
housing.
2. Check that the fan tray is
mounted correctly, if using an
access carrier.
3. Contact your service
representative.
mm/dd/yy hh:mm:ss –
Alarm Cleared for Power
Alarm condition.
Alarm condition no
longer exists.
No action needed.