Programming EVO

1.

Enter section 

[0901]

 - 

[0932]

.

2.

Enter the eight-digit serial number and three-digit output number.

3.

Enter the 3-digit Event Group, Feature Group, Start # and End # 
for PGM activation.

4.

Enter the 3-digit Event Group, Feature Group, Start #, and End# 
for PGM deactivation.

5.

Define the PGM Delay Value (001 to 255 x 1 sec./min.). Default 
set to 5 sec./min.

6.

Set your PGM options, refer to table.

Programming MGSP

1.

Enter section 

[236]

 - 

[251]

2.

Enter the 3-digit Event Group, Sub Group, and Partition for PGM 
activation. 
Section default values are set to 00/00/00 with the exception of 
Section 

[244]

 - activation default values are set to 08/99/01; 

Section 

[246]

 - activation default values are set to 09/99/01. 

3.

Enter the 3-digit Event Group, Sub Group, and Partition for PGM 
deactivation.
Section default values are set to 00/00/00 with the exception of 
Section 

[245]

 - deactivation default values are set to 08/99/01; 

Section 

[247]

 - deactivation default values are set to 09/99/01. 

4.

Enter section 

[269]

 - 

[276]

 to define the PGM Delay Value (001 to 

255 x 1 sec./min.).

5.

Enter section 

[349]

 - 

[356] 

to define your PGM Labels.

6.

Set your PGM options, refer to table below. 

Technical Specifications

OPTION DESCRIPTION

PGM #

OFF

ON

1

PGM deactivation after (OFF = 
deactivation event; ON = PGM timer)

2

PGM base time (OFF = seconds; 
ON = minutes)

3

Flexible PGM deactivation option 
(OFF = PGM timer only; ON = PGM 
timer and/or deactivation event)

4

PGM initial state (OFF = normally open; 
ON = normally closed)

5

PGM Time base (Off = follow option 2, 
1 = hour)

6 to 8

Future use

-

-

OPTION DESCRIPTION

PGM #

OFF

ON

1

PGM base time (OFF = sec., ON = min.)

2

PGM state (OFF = N.O., ON = N.C.)

3

PGM supervision (not applicable to 
SP4000

4

PGM activation mode (OFF = steady, 
ON = pulse)

5

PGM pulse once every 30 seconds, if 
armed

6

PGM pulse on any alarm

7

PGM pulse on any alarm (OFF - partition 
1, ON = partition 2)

8

Flexible PGM deactivation option
(OFF* = PGM delay only, two activation 
events, ON = PGM delay or deactivation 
event, whichever comes first)

* If a PGM delay is programmed (OFF option), the deactivation event 
can be used as a second activation event.

Input Voltage

11 to 16 Vdc

Current Consumption

315 mA max (all PGMs activated)

Number of outputs

8 Form ‘C’ relays

Output

24V, 4A any load

Operating Temperature

-20 C to +50 C (-4 F to 122 F)

Humidity

95% maximum

Box Dimensions 
(H x W x D)

16.5 cm x 10.2 cm x 2.5 cm
(6.5 in x 4 in x 1 in)

Warranty

For complete warranty information on this product, please refer to the Limited 
Warranty Statement is found on the website: 
www.paradox.com/terms or contact your local distributor. Specifications may 
change without prior notice.

Patents

US, Canadian and international patents may apply. Paradox is a trademark or 
registered trademark of Paradox Security Systems (Bahamas) Ltd.

Reviews: