V00028CA Rev03
www.panduit.com
Page
13
of
18
36.
Route the jacketed fiber cable up through the Panduit Duct and through the supplied Tak-Ty indicated on the
Upper Backplane as shown in
Figure 14: Fiber Trunk routing on Upper Backplane
37.
Route the jacketed cable through the loom tubing supplied in the miscellaneous kit. The tubing protects the
fiber from getting pinched in the hinge.
Figure 15: Loom tubing routed around hinge point and rail.
38.
Remove the shipping Tak-Ty from the front of the FRME1U Fiber Enclosure shown in
Figure 16: Shipping tape to be removed from FRME1U.
39.
Install the cable into the FRME1U Fiber Enclosure (RU 23) per FS002C, Opticom Rack Mount Fiber Enclosure
Installation Instructions.
c.
Install fiber adapter panels in the FRME1U. Panduit recommends (3) FAP12WAQDLCZ multi-mode FAPs
for switch connections (ordered separately). (1) FAP is recommended for management ports in the right
FAP position in the enclosure
Shipping Tak-
Ty