Panduit VS-AVT-C02-L03 Instruction Manual Download Page 13

© Panduit Corp. 2018 

INSTRUCTION MANUAL 

VeriSafe AVT 

 

B21052_08 

Page: 12 of 20 

7-2018 

Termination Recommendations 

The VeriSafe AVT is provided with a total of (8) 14 AWG (2 mm

2

) sensor leads (two sensor leads for each phase conductor and ground 

connection point). Sensor leads for each phase and ground must not be mechanically connected to each other for the AVT to function properly 

(see step 7 in the Installation Instructions). The second lead on each phase provides the ability for the AVT to verify that it is in contact with 

the circuit conductors (each phase and ground) when the absence of voltage test takes place. It is also part of the mechanism that is used to 

“test-the-tester” to validate that the AVT is functioning. There is no maximum distance limitation between the two leads on each phase, 

however there should not be any circuit elements installed between them. Do not extend the sensor leads with a splice. Use approved 

connection methods and follow local codes and standards when terminating the sensor leads.  

 

Terminations should be made via a tap to the circuit conductor using connectors, terminal strips, or power distribution blocks, etc. which are 

rated for the application.  It is generally preferred to use connection methods that do not pierce or otherwise compromise the integrity of 

the conductor. Connectors that require conductors to be cut or spliced can be used but may limit the SCCR. 

 

Connectivity Test 

Each time the absence of voltage test is initiated, the VeriSafe AVT performs a series of diagnostics and checks in addition to testing for 

absence of voltage.  One step in this sequence involves a “connectivity test.”  The purpose of the connectivity test is to ensure that each 

detection lead is in contact with a conductor. 

 

The VeriSafe AVT is designed with two Sensor Leads for each phase conductor.  The two leads in each color set have different functions.  The 
Detection Lead is used to detect voltage and the Termination Lead is used to verify that the Detection Lead is in contact with a conductor.  
The Termination Lead does not detect voltage.  There are no labels distinguishing the Detection and Termination Leads because it is critical 
that they are both properly terminated.  If the Detection Lead is not contacting a conductor, the connectivity test will fail and prevent the 
AVT from returning a Green Absence of Voltage indication. 

The connectivity test is performed by measuring the discharge time of a capacitor inside the Isolation Module that is electrically connected 
to the detection lead.  If the Detection Lead is electrically connected to the Termination Lead, the discharge time will be inside the desired 
range and the test will pass

.  

If the Detection Lead is not in contact with a conductor, the discharge time will be outside of the desired range 

and the test will fail.  If the connectivity test fails on any Detection Lead, the green absence of voltage indicator on the AVT will not illuminate.  

 

IMPORTANT:

 

If the detection lead is not properly terminated to a power conductor and comes in contact with a low impedance path to 

ground, the discharge time could be inside the desired range and the connectivity test would pass.  This would be a multi-fault scenario, 

but is possible if terminations are not made properly and secured.  An AVT installed on a single-phase system might only have one Detection 

Lead terminated to a power conductor. If the Detection Lead were to become loose and make contact with a low impedance path to ground, 

the connectivity test would pass.  However, voltage would not be detected because the termination lead does not detect voltage and the 

Detection Lead is no longer in contact with the power conductor.  This could result in a green absence of voltage indication, even though 

the power conductor is energized.   This would be less likely to occur with split-phase or three-phase systems as all Detection  Lead 

terminations would need to fail and each detection lead would have to make contact with a low impedance path to ground at the time of 

the test.  However, even the loss of a single detection lead termination on a multi-phase system could result in the scenario described above, 

if voltage was only present on a single phase. 

 

Utilization of the commissioning test described in this Instruction Manual will verify proper functionality of the AVT at the time of installation.  

The failure modes described in this section would be the result of Sensor Lead terminations not being maintained over time and Sensor Leads 

not being secured to the power conductors at time of installation.  This likelihood of this scenario can be reduced by securing the Sensor 

Leads to the power conductor or another nearby rigid feature to prevent movement in the event that the termination point failed.  Sensor 

Leads can be secured using cable ties, clamps, mounts or tape.  The sensor leads should be secured at multiple locations, including near the 

termination point.  Additionally, the Schematics section of this Instruction Manual provides redundant detection schematics for both single-

phase and DC installations to provide a redundant Detection Lead on the power conductor. 

 

 

                                  

 

  

Warning

:

 

 
Secure Sensor Leads to 
prevent accidental contact 
with ground.  

Summary of Contents for VS-AVT-C02-L03

Page 1: ...ca Tech Support techsupport panduit com Tel 1 866 405 6654 EU Tech Support emeatoolservicecenter panduit com Tel 31 546 580 452 Fax 31 546 580 441 www panduit com Asia Pacific Tech Support TechSupportAP panduit com Telephone Singapore 1 800 Panduit 7263848 Australia 1 800 Panduit 7263848 Korea 02 21827300 The VeriSafe Absence of Voltage Tester is a permanently mounted tester that is used to verify...

Page 2: ...nts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshooting 17 Maintenance 18 Battery Replacement 18 AVT System Cable Removal 19 O ring Replacement 19 Cleaning Instructions 19 Visual Inspection 19 Warranty 20 ...

Page 3: ...le shown in the Maintenance section of this instruction manual The product uses a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C incinerate or expose contents to water Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module Do not use a standard Ethernet cable Ba...

Page 4: ...uées dans le tableau indiqué dans la section Maintenance de ce mode d emploi Le produit utilise une batterie au lithium qui est un incendie une explosion et un grave risque de brûlure Ne pas écraser recharger démonter ou chauffer au dessus de 85 C incinérer ou exposer le contenu à l eau Utilisez uniquement le câble système AVT inclus ou les câbles de remplacement approuvés pour connecter le module...

Page 5: ...hen the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system as well as log when the absence of voltage was verified Recommended Wiring For redundant monitoring of output state Output Contact Specifications Two channel single pole normally open Relay closure upon absence of voltage verification 5000 Vrms Input Output Isol...

Page 6: ...l equipment Radio frequency disturbance characteristics Limits and methods of measurement IEC EN61000 3 2 IEC EN61000 3 3 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current 16 A per phase EN 61000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments KN 61000 6 2 KN 61000 6 4 In an industri...

Page 7: ...ree 3 Altitude Up to 5000 meters 3 1 miles Battery Type Industrial 3 6V Lithium AA see table in Maintenance section for list of compatible batteries Functional Safety Mode of operation Continuous High Demand Failure Rate ʎSD ʎSU ʎDD ʎDU SFF 65 371 152 10 98 3 Supported Safety Integrity Levels SIL3 Demand Response Time 10 1 Seconds Device Type Type A Systematic Capability SC 3 Error Handling Respon...

Page 8: ... 7 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on top as shown in the image MOUNTING HOLES 3 Units inches mm Units inches mm ...

Page 9: ...ry or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground the connectivity test can be defeated resulting in a false absence of voltage indication Ensure that a...

Page 10: ...N MANUAL VeriSafe AVT B21052_08 Page 9 of 20 7 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire Neutral PE DC System 2 Wire PE ...

Page 11: ... Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21052_08 Page 10 of 20 7 2018 DC System 2 Wire PE Redundant Detection Lead ...

Page 12: ...nce limits Effect on Short Circuit Current Rating SCCR AVTs listed to UL 1436 are required to operate as a secondary circuit that is isolated from the circuit conductors by use of a transformer optical isolator or limiting impedance or other similar means This is intended to reduce the risks of both electric shock and thermal hazard These isolation circuits allow very limited current flow if any t...

Page 13: ...nected to the detection lead If the Detection Lead is electrically connected to the Termination Lead the discharge time will be inside the desired range and the test will pass If the Detection Lead is not in contact with a conductor the discharge time will be outside of the desired range and the test will fail If the connectivity test fails on any Detection Lead the green absence of voltage indica...

Page 14: ... false absence of voltage indication Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact Before installation verify that after power is removed from the circuit to be monitored the potential measured between each line and ground is less than 1 3 V 1 Insert the Indicator M...

Page 15: ...or leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contacting ground if the termination fails Refer to the Installation Considerations section for additional information 8 Route Sensor Leads and AVT System Cable to avoid sharp edges pinch points and prevent...

Page 16: ...bel Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the Test Button to initiate the test The yellow Caution Indicator should flash rapidly to indicate the test is in progress followed by the Absence of Voltage Indicator illuminated green Review the Operating I...

Page 17: ...of voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check using a known voltage source to test the tester to verify that the AVT is functioning testing for AC and DC voltage phase to phase and phase to ground and verifying the sensor leads are in contact wit...

Page 18: ... test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If panel has a stored energy source wait several minutes then re test to see if energy has dissipated 4 Proper installation of the sensor leads could not be verified Warning The enclosure may be energized F...

Page 19: ...f batteries approved for use with the AVT Do not discard the battery in the trash take it to an appropriate battery recycling facility Manufacturer Model Number Size Description Tadiran TL 5903 AA ER14505 3 6 Volt Lithium Battery Xeno Energy XLP 060F Saft LS14500 Table 1 Approved VeriSafe AVT batteries 1 Grip the Indicator Module Cap 2 Twist the Indicator Module cap counterclockwise approximately ...

Page 20: ...gh alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Module that is external to the electrical enclosure is approved for wash down as specified by NEMA 4 and IP66 standards Before a wash down operation ensure the O rings are in good condition the faceplate...

Page 21: ...t to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any third party software or firmware which may be incorporated into a Panduit product and or resold or sublicensed by Panduit To the extent any warranties extended to Panduit by t...

Reviews: