Panduit VS-AVT-C02-L03 Instruction Manual Download Page 1

 

VeriSafe AVT 

 

B21052 

Rev: 08  7-2018 

Absence of Voltage Tester 

Instruction Manual 

Models: VS-AVT-C02-L03, VS-AVT-C02-L03A, VS-AVT-C02-L03E, VS-AVT-C02-L10, 

VS-AVT-C08-L10, VS-AVT-C08-L10A, VS-AVT-C08-L10E 

© Panduit Corp. 2018 

 

Original Instructions 

 

 

 

 

 

TO REDUCE THE RISK OF INJURY, USER 
MUST READ INSTRUCTION MANUAL 

 

 

 
NOTE: In the interest of higher quality and value, Panduit
 products are 
continually being improved and updated. Consequently, pictures may vary 
from the enclosed product.  
 
NOTE: Updates to this Instruction Manual may be available. Check 
www.panduit.com for the latest version of this manual. 
 

North America Tech Support:  

[email protected] 

Tel: 1-866-405-6654  

  

EU Tech Support :  

emeatoolservicecenter 

@panduit.com 

Tel: +31-546-580-452 

Fax: +31-546-580-441 

 

www.panduit.com 

Asia Pacific Tech Support: 

TechSupportAP@ panduit.com 

 

Telephone:  

Singapore: 1-800-Panduit (7263848) 

Australia: 1-800-Panduit (7263848) 

Korea: 02-21827300 

The VeriSafe Absence of Voltage Tester is a permanently-mounted tester that is used to verify a circuit is 
de-energized prior to opening an electrical enclosure. Once installed, a push of a button enables qualified 
electrical workers to verify the absence of voltage and see an active indication when the absence of voltage is 
confirmed. The Indicator Module is designed for a 30-mm notched panel knockout and the Isolation Module can 
be mounted to DIN rail or surface mounted using screws. 

Summary of Contents for VS-AVT-C02-L03

Page 1: ...ca Tech Support techsupport panduit com Tel 1 866 405 6654 EU Tech Support emeatoolservicecenter panduit com Tel 31 546 580 452 Fax 31 546 580 441 www panduit com Asia Pacific Tech Support TechSupportAP panduit com Telephone Singapore 1 800 Panduit 7263848 Australia 1 800 Panduit 7263848 Korea 02 21827300 The VeriSafe Absence of Voltage Tester is a permanently mounted tester that is used to verify...

Page 2: ...nts 4 Output Contacts 4 Technical Specifications 5 Dimensions 7 Schematics 8 Installation Considerations 11 Installation Instructions 13 Commissioning Checklist 15 Operating Instructions 16 Troubleshooting 17 Maintenance 18 Battery Replacement 18 AVT System Cable Removal 19 O ring Replacement 19 Cleaning Instructions 19 Visual Inspection 19 Warranty 20 ...

Page 3: ...le shown in the Maintenance section of this instruction manual The product uses a lithium battery that is a fire explosion and severe burn hazard Do not crush recharge disassemble or heat above 85 C incinerate or expose contents to water Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module Do not use a standard Ethernet cable Ba...

Page 4: ...uées dans le tableau indiqué dans la section Maintenance de ce mode d emploi Le produit utilise une batterie au lithium qui est un incendie une explosion et un grave risque de brûlure Ne pas écraser recharger démonter ou chauffer au dessus de 85 C incinérer ou exposer le contenu à l eau Utilisez uniquement le câble système AVT inclus ou les câbles de remplacement approuvés pour connecter le module...

Page 5: ...hen the green Absence of Voltage Indicator is illuminated By wiring to these contacts the AVT can be used as an input to a control system as well as log when the absence of voltage was verified Recommended Wiring For redundant monitoring of output state Output Contact Specifications Two channel single pole normally open Relay closure upon absence of voltage verification 5000 Vrms Input Output Isol...

Page 6: ...l equipment Radio frequency disturbance characteristics Limits and methods of measurement IEC EN61000 3 2 IEC EN61000 3 3 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions equipment input current 16 A per phase EN 61000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments KN 61000 6 2 KN 61000 6 4 In an industri...

Page 7: ...ree 3 Altitude Up to 5000 meters 3 1 miles Battery Type Industrial 3 6V Lithium AA see table in Maintenance section for list of compatible batteries Functional Safety Mode of operation Continuous High Demand Failure Rate ʎSD ʎSU ʎDD ʎDU SFF 65 371 152 10 98 3 Supported Safety Integrity Levels SIL3 Demand Response Time 10 1 Seconds Device Type Type A Systematic Capability SC 3 Error Handling Respon...

Page 8: ... 7 2018 Dimensions Isolation Module Indicator Module Panel Knockout Units inches mm The Indicator Module is designed for use with a standard 30 mm knockout with notch The notch should be positioned on top as shown in the image MOUNTING HOLES 3 Units inches mm Units inches mm ...

Page 9: ...ry or death Sensor leads of the same color should be terminated on the same conductor Each conductor should have at least one sensor lead set as shown on the schematic diagrams If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground the connectivity test can be defeated resulting in a false absence of voltage indication Ensure that a...

Page 10: ...N MANUAL VeriSafe AVT B21052_08 Page 9 of 20 7 2018 Single Phase 2 Wire PE Single Phase 2 Wire PE Redundant Detection Lead Single Phase 3 Wire PE Corner Grounded DELTA 3 Wire PE High Leg DELTA 3 Wire Neutral PE DC System 2 Wire PE ...

Page 11: ... Panduit Corp 2018 INSTRUCTION MANUAL VeriSafe AVT B21052_08 Page 10 of 20 7 2018 DC System 2 Wire PE Redundant Detection Lead ...

Page 12: ...nce limits Effect on Short Circuit Current Rating SCCR AVTs listed to UL 1436 are required to operate as a secondary circuit that is isolated from the circuit conductors by use of a transformer optical isolator or limiting impedance or other similar means This is intended to reduce the risks of both electric shock and thermal hazard These isolation circuits allow very limited current flow if any t...

Page 13: ...nected to the detection lead If the Detection Lead is electrically connected to the Termination Lead the discharge time will be inside the desired range and the test will pass If the Detection Lead is not in contact with a conductor the discharge time will be outside of the desired range and the test will fail If the connectivity test fails on any Detection Lead the green absence of voltage indica...

Page 14: ... false absence of voltage indication Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact Before installation verify that after power is removed from the circuit to be monitored the potential measured between each line and ground is less than 1 3 V 1 Insert the Indicator M...

Page 15: ...or leads with a splice Use approved connection methods and follow local codes and standards when terminating the sensor leads Secure the sensor leads to the conductors to prevent the leads from contacting ground if the termination fails Refer to the Installation Considerations section for additional information 8 Route Sensor Leads and AVT System Cable to avoid sharp edges pinch points and prevent...

Page 16: ...bel Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed Record changes to panel documentation Close panel and secure doors covers Press the Test Button to initiate the test The yellow Caution Indicator should flash rapidly to indicate the test is in progress followed by the Absence of Voltage Indicator illuminated green Review the Operating I...

Page 17: ...of voltage push the Test Button A B Absence of Voltage Test Each time the Test Button is engaged the absence of voltage test sequence will be activated The test sequence includes running a self check using a known voltage source to test the tester to verify that the AVT is functioning testing for AC and DC voltage phase to phase and phase to ground and verifying the sensor leads are in contact wit...

Page 18: ... test 2 Voltage detected above the threshold Warning This indicates that the enclosure is energized Follow safety procedures and use the appropriate PPE when investigating the source of voltage If panel has a stored energy source wait several minutes then re test to see if energy has dissipated 4 Proper installation of the sensor leads could not be verified Warning The enclosure may be energized F...

Page 19: ...f batteries approved for use with the AVT Do not discard the battery in the trash take it to an appropriate battery recycling facility Manufacturer Model Number Size Description Tadiran TL 5903 AA ER14505 3 6 Volt Lithium Battery Xeno Energy XLP 060F Saft LS14500 Table 1 Approved VeriSafe AVT batteries 1 Grip the Indicator Module Cap 2 Twist the Indicator Module cap counterclockwise approximately ...

Page 20: ...gh alkaline cleaners Do not leave cleaners on the device for a long period rinse immediately Do not apply cleaners in direct sunlight or elevated temperatures The section of the VeriSafe Indicator Module that is external to the electrical enclosure is approved for wash down as specified by NEMA 4 and IP66 standards Before a wash down operation ensure the O rings are in good condition the faceplate...

Page 21: ...t to Buyer whichever is longer 4 No Warranty for Third Party Products Panduit makes no representations and disclaims all warranties of any kind express or implied relative to any third party product or services including any third party software or firmware which may be incorporated into a Panduit product and or resold or sublicensed by Panduit To the extent any warranties extended to Panduit by t...