Panduit Corp. 201
4
OPERATION MANUAL
UPS003024024015
Page: 4 of 29
Model No. / Manufacture Date
Input / Output / Temp Ratings
Conformances
Warnings
Approvals
Installation
Top hat (DIN) rail EN 50022
Width: 81mm (3.2 in)
Depth: 178mm (7.0 in)
Height: 145mm (5.7 in)
Weight: 5 lbs, max.
Switch: Output On/Off, recessed
Terminals: screw type, accepts #12 to #18 AWG, stranded/solid/terminated
The device shall have control wiring along the top edge.
Output: Isolated, Form A contact, rated 30VDC at 1A maximum.
Input
Output
Charge Status
Control Output
0 VDC
0 VDC
N/A
Off
24 VDC
24 VDC pass through
Charging
On
24 VDC
24 VDC pass through
Charged
On
0 VDC
18-22 VDC backup
Discharging
On
0 VDC
0 VDC
Discharged
Off
Communications: RJ45 socket for Ethernet (10BaseT)
NOTE:
For use in Class I, Zone 2 environment, the UPS/LSM must be used in an enclosure certified for use
in Class I, Zone 2, Groups IIC and rated IP54 in accordance with IEC 60529. The enclosure needs to only
be accessible with the use of a tool. Provision shall be made to prevent the rated voltage being exceeded by
transient disturbances of more than 140% at the power supply terminals of the device. This device is to be
installed within an area of not more than pollution degree 2, as defined in IEC 60664-1.
NOTE:
This product is intended for use in a restricted location, such as inside a machine, control cabinet,
enclosure or similar structure. Restricted access can be provided by a door, cover or similar physical means
that requires the use of tools, keys or other secure methods to gain access. The level of security required
should determine the location, protection and access methods.
Not for use in a computer room as
defined in the Standard for the Protection of Information Technology Equipment, ANSI/NFPA 75.
Performance
Hold Time: 5 minutes, minimum at 35 W load
Extraction Efficiency: 83% minimum of stored energy
Voltage Drop: 500mV maximum from Input to Output when Input power is present
Output Transient: 5 msec max during which Output is < 18VDC at 35W load