INTELLIGENT NMC USER MANUAL
60
4. The
Edit
panel pop up displays.
Figure 64: Edit V1/2c Manager
5. Set the following options:
•
IP Address: the IP address of the host for this SNMP V1/V2 manager. Only
requests from this address will be acted upon.
Note
: An IP address configured to 0.0.0.0 will act as a wildcard and all
requests will be acted upon.
•
Read Community: the read-only community string to allow an SNMP V1/V2c
manager to read a SNMMP object.
•
Write Community: the write-only community string to allow an SNMP V1/V2c
manager to write an SNMMP object.
6. Click
Enable
and
Save
.
Configuring Users for SNMP v3
1. Access the Web interface and log in.
2. Under Settings, select
SNMP Manager
.
3. In the
SNMP v3 Manager
panel, select the SNMP v3 manager to configure.
Select the
pencil
icon in the last column.