Panduit Smartzone UPS INTELLIGENT NMC User Manual Download Page 1

 

 

 

 

User Manual 

UPS Network Management Card 

Version 1.1 

Summary of Contents for Smartzone UPS INTELLIGENT NMC

Page 1: ...User Manual UPS Network Management Card Version 1 1...

Page 2: ...d 16 Network Settings 19 System Management Information 23 Setting Time and Date on the NMC 26 Control Manage 28 Panduit s Smart Load Shedding 38 Email Setup 45 Event Log 48 Data Log 49 Web Interface A...

Page 3: ...ms 76 Secure Boot Protection 77 Firmware Update Protection 77 Other Features 77 Secure deployment 77 Warranty and Regulatory Information 80 Warranty Information 80 Regulatory Information 80 Panduit Su...

Page 4: ...INTELLIGENT NMC USER MANUAL 4...

Page 5: ...6 Web Access Configuration 20 Figure 17 SSH Configuration 21 Figure 18 Syslog Configuration 21 Figure 19 Network Time Protocol 22 Figure 20 Date Time Configuration 22 Figure 21 Time Zone Configuration...

Page 6: ...Figure 54 Data Log Configuration Panel 50 Figure 55 User Accounts 53 Figure 56 RADIUS Configuration 53 Figure 57 LDAP Configuration 55 Figure 58 Enable Role Privileges 56 Figure 59 SNMP Management 57...

Page 7: ...creen 78 Figure 77 Upload Firmware 98 Figure 78 Control Panel 100 Figure 79 Network Status and Tasks 101 Figure 80 Change Adapter Settings 102 Figure 81 Properties 102 Figure 82 Ethernet Properties 10...

Page 8: ...nd of the cable to the Network port on the router or another LAN device Figure 1 Ethernet Port for Network Connection From the factory the NMC defaults to DHCP and HTTPS connection If you are connecte...

Page 9: ...g the serial interface To discover the network setting perform the following steps 1 Connect PC to the NMC USB port See Figure 2 Serial In Port 2 Using a Terminal emulator program send read CLI comman...

Page 10: ...INTELLIGENT NMC USER MANUAL 10 Figure 3 Network information from CLI...

Page 11: ...sktop Mozilla Firefox Microsoft Edge and Apple Safari mobile and desktop Logging in to the Web Interface Open a supported web browser and enter the IP address of the NMC HTTPS If browser displays refu...

Page 12: ...n o If admin credentials are lost use Appendix C to factory reset the NMC Figure 6 Login Page Changing Your Password At initial login you are required to change the default password 1 Enter the userna...

Page 13: ...nging Your Password 2 Click Log In to complete the password change After the initial login change the password by the following steps 1 Click on the username and select Change Password Figure 8 After...

Page 14: ...ve alarms 3 This icon lets you select a Language There are seven languages available to choose from English French German and Spanish 4 This icon provides the logs of the UPS which can be viewed and d...

Page 15: ...ANUAL 15 Number Icon Description 8 This icon shows who is logged in user or admin Account passwords can be changed and user accounts managed through this page Menu Dropdowns Overview Alarms Language L...

Page 16: ...he Dashboard Power Summary Page Figure 10 Power Summary Page NUMBER DESCRIPTION 1 Power flow of the system The state will be Normal Bypass or On Battery None 2 The bypass component of the UPS 3 The AC...

Page 17: ...AC converter Inverter 6 The Output Load 7 The Battery 8 Alert Summary Clicking on the icon will give a summary of the system 9 Speaker Status If the audible alarm is enabled 10 Battery Status UPS Mon...

Page 18: ...onmental Monitoring Page PARAMETER DESCRIPTION Type Temperature Humidity Water Sensor Name User configurable sensor name Serial Number Sensor Serial number Value Sensor reading Status Normal Exceeds T...

Page 19: ...ttings The Network Settings allow management of IP Configuration DNS Web Access SSH Configuration Syslog Configuration Network Time Protocol NTP Date Time Configuration and Time Zone Configuration IP...

Page 20: ...L 20 DNS configuration Figure 15 DNS Configuration Web Access Configuration Web Access Configuration is used to set HTTP and HTTPS Also this section will be used to upload HTTPS Certificates Figure 16...

Page 21: ...INTELLIGENT NMC USER MANUAL 21 SSH Configuration Figure 17 SSH Configuration Syslog Configuration Figure 18 Syslog Configuration Network Time Protocol NTP...

Page 22: ...INTELLIGENT NMC USER MANUAL 22 Figure 19 Network Time Protocol Date Time Configuration Figure 20 Date Time Configuration...

Page 23: ...stinguish the UPS system s name and location inside the data center To configure the system management information select System Management under the gear icon Figure 22 System Management System Info...

Page 24: ...into the Contact Name section 4 Enter the email of the contact person into the Contact Email 5 Enter the phone number of the contact person into Contact Phone 6 Enter the location of the contact perso...

Page 25: ...positioned in Row Position 5 Enter the ID of the rack cabinet where the NMC is located into Rack ID 6 Enter the height of the rack cabinet where the NMC is located into Rack Height 7 Press Save Power...

Page 26: ...tical NMCs they are typically installed in the back 4 Enter the rack unit RU location into the Core U Position Vertical NMCs are usually installed in the 0 RU space 5 Press Save Setting Time and Date...

Page 27: ...ter 13 for 1 00pm 14 for 2 00pm etc 4 Press Save Configure Network Time Protocol NTP 1 Go to Network Settings and select Network Time Protocol NTP Figure 27 NTP Configuration 2 Click Enable to enable...

Page 28: ...timezone date time date time For more information on the POSIX time zone formats see Appendix F POSIX Time Zone Information Control Manage The control and manage section of the Web GUI will allow a us...

Page 29: ...ng the audible alarm will silence any alarm at the UPS 1 Select the Home Icon then Control Manage from the drop down menu in the Web GUI 2 From the UPS tab select pencil next to Audible Alarm Figure 3...

Page 30: ...mal Operation When the user desired the UPS to transition back to normal operation the user can exit bypass 1 Select the Home Icon then Control Manage from the drop down menu in the Web GUI 2 Select t...

Page 31: ...Manual Test Configuration 1 Select the Home Icon then Control Manage from the drop down menu in the Web GUI 2 From the UPS tab select pencil next to UPS Manual Test Figure 33 UPS Manual Test Configura...

Page 32: ...e from the drop down menu in the Web GUI 2 Select the Actions drop down menu and choose Start Test Figure 34 Start Test Example 3 The user will be asked to confirm they want to start the battery test...

Page 33: ...en initiate the test Periodic Battery Test The system can be enabled to automatically run a periodic battery test When the test is schedule to execute the system will run the minimum battery test Batt...

Page 34: ...e Home Icon then Control Manage from the drop down menu in the Web GUI 2 From the UPS tab select pencil next to UPS Main Output 3 Select the desired mode from the drop down menu 4 Then select Save Fig...

Page 35: ...individual outlet upon UPS power up 1 Select the Home Icon then Control Manage from the drop down menu in the Web GUI 2 In the Control Manage and select the Outlet Groups tab 3 Select the outlet group...

Page 36: ...ntrol or Disabled to disable manual outlet control Changing the state of the outlet group 1 Select the Home Icon then Control Manage from the drop down menu in the Web GUI 2 In the Control Manage and...

Page 37: ...utlet group Setting the Outlet Power On Off Delay for Panduit NMCs This is only applicable to outlet group switched UPS 1 Select the Home Icon then Control Manage from the drop down menu in the Web GU...

Page 38: ...allows the UPS to be configured to shed different loads depending on the configuration of the Shutdown Groups in order to maintain the battery for higher priority equipment Panduit s Smart Load Sheddi...

Page 39: ...et group If the Shutdown Group is the last remaining Shutdown Group turned on associated with the outlet group and any of the Shutdown Groups associated to that outlet have Request Group Off enabled t...

Page 40: ...ery Capacity The Shutdown Group will be shut down when the capacity drops below the configured capacity 6 Set the Time Time is the number of seconds after the system switches to the battery the Shutdo...

Page 41: ...tem transitions off the battery Smart Loads Configuration Smart Loads are connected devices to the UPS that would need to be shutdown gracefully before the system s battery is depleted To configure th...

Page 42: ...roup is shut down 5 The Name will allow the user to associate a more meaningful name to the device 6 Under Group select which Shutdown Group is associated to this Smart Load 7 The Shutdown Delay is th...

Page 43: ...t UserName The password will need to be entered twice d SSH Shutdown Agent Identity The SSH fingerprint For the highest level of security manually enter the SSH fingerprint It will be automatically up...

Page 44: ...ce at the configured date and time b Daily The shutdown will happen every day at the configured time c Weekly The shutdown will happen once a week at the configured time and day of week d First Week S...

Page 45: ...Finally the Duration The duration is how long the shutdown group will remain shutdown Email Setup The Panduit UPS NMC can be configured to send emails to specific users when an event occurs To do this...

Page 46: ...e SMTP server This is the address of the SMTP relay server that is going to accept the messages Set the Sender email address This is the email address that the email is sent from You could use a uniqu...

Page 47: ...nterval Between Sending Retires In Minutes This is the time in minutes the NMC will wait before retrying to send a failed message The default setting is 6 minutes Set the transmission Security o None...

Page 48: ...ss Enable 3 Press Save Note A maximum of 5 users can be entered to receive email alerts Event Log UPS events and NMC events or alarms are recorded in the event log Syslog can also be configured to rep...

Page 49: ...be configured from 1 to 1440 minutes As an example if a data log is in an interval of 60 minutes the entire data log contains 1000 records with up to 41 67 days of data Once the data log reaches the...

Page 50: ...Logging Out Users should logout after each session to prevent unauthorized changes to the system 1 Click the user name icon in the top right corner of the screen see Introduction to the Web Menu 2 Cl...

Page 51: ...ese Roles define the permissions granted to the user Role Default Permissions admin Full permissions that cannot be modified or deleted controller Can control the UPS system but cannot change any conf...

Page 52: ...ofile Modify user profile 1 Go to Settings and select Users 2 Click on the pencil next to the user to modify 3 Select Edit Make changes to the user profile 4 Select Save Delete user profile with the f...

Page 53: ...US user will have the viewer Role if one is not specified The administrator of the RADIUS server may configure a Panduit vendor 19536 dictionary with a User Role integer attribute set to User 1 or Adm...

Page 54: ...ecurity None for unencrypted transmission StartTLS to upgrade the connection after connect to a TLS connection TLS to start with TLS connection 7 In the Base DN field enter in the account to be used t...

Page 55: ...ference a group within the Active Directory AD 1 Within the Active Directory create a group for the users that you wish to be NMC administrators i e admins Note There are no limits to the number of ad...

Page 56: ...INTELLIGENT NMC USER MANUAL 56 Figure 58 Enable Role Privileges 4 LDAP authentication is ready to use...

Page 57: ...imple Network Management Protocol SNMP SNMP Management Configuration Setup SNMP 1 Access the Web interface and login 2 Under SNMP Managers select SNMP General or type SNMP in the search The SNMP Gener...

Page 58: ...General includes SNMP Access and Version Figure 60 SNMP General Setup SNMP Port 1 Access the Web interface and log in 2 Under SNMP Managers select SNMP Port The SNMP Port page displays Figure 61 SNMP...

Page 59: ...t and Trap Port Configuring Users for SNMP V1 V2c 1 Access the Web interface and log in 2 Under SNMP Manager select SNMP V1 V2c 3 In the SNMP V1 V2c panel select the SNMP V1 V2c manager to configure S...

Page 60: ...wildcard and all requests will be acted upon Read Community the read only community string to allow an SNMP V1 V2c manager to read a SNMMP object Write Community the write only community string to all...

Page 61: ...INTELLIGENT NMC USER MANUAL 61 Figure 65 SNMP v3 Manager 4 The Edit panel pop up displaying the configurable options...

Page 62: ...MANUAL 62 Figure 66 SNMP V3 Edit 5 Configure the SNMP username 6 Choose a Security Level from the dropdown menu NoAuthNoPriv No authentication and no privacy This is the default AuthNoPriv Authentica...

Page 63: ...with the privacy algorithm Repeat the privacy key below it in Confirm Password 10 Select the desired privacy algorithm AES 128 AES 192 AES 256 11 Click Enable and Save Configuring SNMP Traps The NMC k...

Page 64: ...to help distinguish the different receivers b The host name is the IP Address to which the traps are sent by the SNMP system agent c Community is the password on the SNMP management stations 4 Select...

Page 65: ...e is a user assigned name to help distinguish the different receivers b The host name is the IP Address to which the traps are sent by the SNMP system agent 4 Choose a Security Level from the dropdown...

Page 66: ...password below it in Confirm Password 6 Select the desired authentication algorithm MD5 SHA 7 Enter the Privacy Key from the SNMP Server for privacy algorithm Repeat the privacy key below it in Confir...

Page 67: ...NMC Initialization or NMC internal error condition Network LED The LED will change colors depending on the Ethernet link status and the speed Hardware version can be checked under Identification page...

Page 68: ...he following table lists available sensors as well as sensor count Sensor Description Sensor Count Temperature Sensor EA001 Monitors the temperature in the rack 1 Temperature Humidity Sensor EB001 Mon...

Page 69: ...leak detector by an additional 6m A total of four extensions can be added to the leak detection sensor for a total length of 30m N A SmartZone G5 Dry Contact Sensor ACC01 Input to the UPS NMC and des...

Page 70: ...Temperature Units Setting 3 Select the correct units and select Save Configuring Environmental Sensors To configure the sensor location alarms notifications and details open the WEB Interface 1 Open t...

Page 71: ...dialog box type the name of the sensor 5 Type value of high critical high warning low warning and low critical and check Enable box 6 Select Save to exit the sensor setup Figure 73 Temperature Sensor...

Page 72: ...Settings page Select Threshold to configure sensors Figure 74 Security Sensor Alarm Configuration view 3 Select pencil next to the desired sensors 4 In the Edit dialog box type the name of the sensor...

Page 73: ...INTELLIGENT NMC USER MANUAL 73 Figure 75 Dry Contact Sensor Edit dialog Deleting Sensors 1 Select Threshold from Settings menus 2 Select pencil next to the desired sensors 3 Check Delete box then save...

Page 74: ...h The flash encryption algorithm is AES 256 where the key is tweaked with the offset address of each 32 byte block of flash This means that every 32 byte block two consecutive 16 byte AES blocks is en...

Page 75: ...browser clients The product uses TLS 1 2 to communicate with LDAPS servers The product uses TLS 1 2 to communicate with SMTP STARTTLS and SMTPS servers The product provides a SSH server with these al...

Page 76: ...ripemd160 openssh com Network Configuration including Static IP addresses and addresses obtained by DHCP are exposed on Identification page and on a Network Configuration page to aid in network manage...

Page 77: ...oader to load the bootloader Firmware Update Protection The product uses industry standard cryptography to verify a firmware update package to establish authenticity and integrity The package contains...

Page 78: ...s Configuration Figure 76 SSL Certificate Load Screen Use SNMPv3c The Panduit UPS NMC comes with support for both SNMPv2c and SNMPv3 For a higher security deployment it is recommended to disable SNMPv...

Page 79: ...INTELLIGENT NMC USER MANUAL 79 Review Session management The NMC gives the customer the flexibility to change session management settings...

Page 80: ...Information Warranty Information https www panduit com Regulatory Information Safety and regulatory compliance For important safety environmental and regulatory information see Safety and Compliance I...

Page 81: ...ontact us html Europe Middle East Customer Service Price Availability Expedites 0044 0 208 6017219 or EMEA CustomerServices panduit com UPS Technical Support UPS Selection Competitor Cross references...

Page 82: ...ol GUI Graphical User Interface IP Internet Protocol kVA Kilo Volt Ampere kW Kilowatts kWh Kilowatt Hour LAN Local Area Network LCD Liquid Crystal Display LDAP Lightweight Directory Access Protocol SH...

Page 83: ...of the intelligent NMC Also the firmware can be updated with SmartZone mPower tool and the firmware can be bulk updated with the mPower tool 1 Open the User interface in a web browser by entering the...

Page 84: ...the controller will reset This will cause a reset of the NMC controller all configuration s will be retained To Default the controller to factory settings press and hold the Reset Button for at least...

Page 85: ...to the UPS via Ethernet without Bonjour Note Instructions refer specifically to Windows 10 Please refer to your operating system documentation if you are not using Windows 10 1 Type control into Windo...

Page 86: ...INTELLIGENT NMC USER MANUAL 101 2 In the Control Panel window select Network and Sharing Center Figure 79 Network Status and Tasks 3 Select Change adapter settings from the menu on the left...

Page 87: ...INTELLIGENT NMC USER MANUAL 102 Figure 80 Change Adapter Settings 4 Right click Ethernet and select Properties Figure 81 Properties...

Page 88: ...INTELLIGENT NMC USER MANUAL 103 Figure 82 Ethernet Properties 5 Select Internet Protocol TCP IP Version 4 you may need to scroll down Then click the Properties button...

Page 89: ...Power the NMC unit 10 Wait 10 seconds 11 The MAC address of the NMC is printed on a label on the NMC If you have the MAC address of the NMC skip to Step 12 a From the Start menu Run cmd exe b In the C...

Page 90: ...4 1 14 Use the Enter key to navigate to the web site 15 A Privacy Error or an error explaining that the certificate cert authority is invalid This message is presented when a device has the initial ce...

Page 91: ...redential from web UI Logging in using SSH protocol Identify IP address of the NMC Open a SSH program such as Putty Open connection to the NMC Use the same credential from web UI Changing Your Passwor...

Page 92: ...e accepted read Read stored data from the data model Parameter can be object name or individual item When queried with object name it will display all items in the object Example read status mfgData F...

Page 93: ...INTELLIGENT NMC USER MANUAL 108 Figure 85 Writing from CLI ls List all objects in the data model help Display all command list and usage logout quit Log out the user...

Page 94: ...VALUE Panduit User Role Control 3 END VENDOR Panduit 4 Load dictionary Panduit by appending the following line to etc freeradius 3 0 dictionary INCLUDE usr share freeradius dictionary Panduit 5 Add a...

Page 95: ...ed on any client restrictions that are enforced Usage radtest OPTS user passwd radius server port nas port number secret radtest radroleadmin 34567890 192 0 2 1 0 panduit 1 Sending Access Request of i...

Page 96: ...he first week and 5 for the last week in the month d 0 6 0 for Sunday and 6 for Saturday H 0 24 hour MM 00 60 minute SS 00 60 second Example 1 The US Central timezone is specified as follows CST6CDT M...

Page 97: ...INTELLIGENT NMC USER MANUAL 112...