Cannot ping the Gateway EPA126
–
Symptoms:
Cannot ping the Gateway EPA126 or cannot contact/reach Gateway EPA126
–
Action:
•
Check speed and link LED on Gateway EPA126 front interface are on (speed
should be sold and link LED may be blinking)
•
Make sure network connection to Gateway EPA126 is good/stable - Gateway
EPA126 to switch
•
Confirm if switch port supports 10/100 speed
•
Ensure that your computer has access to network segment of the Gateway
EPA126 IP segment
Gateway EPA126 displaying an alarm
–
Red Alarm LED on
–
Symptoms:
Gateway EPA126 show a red alarm LED in front and rear of the Gateway EPA126
–
Action:
•
This is an indication of a sensor showing value exceeding the set threshold limit
•
Log into the Gateway EPA126
and check the Input Sensor screen for ‘Value’ vs
the ‘Limits’ fields
•
Based on the threshold violation, Panduit may have a policy in place for
recommended action (for example, what action to recommend to client if temp
is showing more than 95°F at
‘RD M Temp
’ sensor
). The recommendation could
be to lower the set point of the CRAC/CRAH or adjust air dampeners, etc.
Gateway EPA126 unit has been reset?
–
Symptoms:
Gateway EPA126 seems not working per spec, or configuration does not match default
–
Action: