SmartZone Gateway EP042 User Manual
-
51
-
Control Method
The Control Method parameter specifies which control methods are available to control
the outlets on PDUs attached to the unit.
HTTP + SNMP
The Web Management Interface and SNMP can be used to command PDU outlets.
HTTP Only
This option allows only the Web Management Interface to command PDU outlets. This
effectively disables SNMP PDU outlet control.
SNMP Only
This option allows only SNMP to command PDU outlets.
This effectively disables the Web Management Interface PDU outlet control.
RS232 Only
This option allows PDU control commands to be issued directly to a unit via the onboard
RS232 port. This option disables the Web Management Interface and SNMP control.
Cycle Up/Down Delay
This parameter specifies the interval in seconds between switching on and switching off
outlets when an entire PDU is cycled (all outlets commanded on or off).
Repeat Timer (on Comms Failure)
This parameter specifies the interval in seconds between when an initial PDU comms
failure trap is produced and a repeat trap is issued.
Reboot Delay
This parameter specifies how long (in seconds) an outlet remains off after a reboot
before switching back on.
Abort Cycle Delay
This parameter specifies how many seconds must elapse before a commanded cycle
begins on a PDU. This delay gives the user time to reverse the decision to cycle a PDU
before any outlet states are changed.