If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
For WH-WDG05LE5, WDG07LE5 and WDG09LE5, avoid installations in areas where the ambient temperature may drop below-25°C.
A protective zone is defi ned for the area close around the product. See section "2 Protective zone".
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinary oil, etc), it lifespan maybe shorten.
Please follow the table below for water piping specifi cations.
Model
Water piping between outdoor unit and indoor unit
Inner diameter
Maximum
length
Insulator
thickness
Maximum
Elevation
WH-WDG05LE5
ø20
30 m
30 mm
or more
10 m
WH-WDG07LE5
ø25
WH-WDG09LE5
This outdoor unit is filled with R290(Extremely flammable gas, safety A3 group per ISO 817). Note that this refrigerant has a higher density
than air. In case of a refrigerant leak, the leaked refrigerant may accumulate near the ground.
Prevent accumulation of refrigerant in any way that is potentially dangerous, explosive or risk suffocation. Prevent refrigerant from entering
the building through building openings. Prevent accumulation of refrigerant in the drain grooves.
A protective zone is defined around this outdoor unit. There must be no building openings, windows, doors, light shafts, cellar entrances,
escape hatches, flat-roof windows or ventilation openings in the protective zone.
There must be no ignition sources, such as heat above
360°C
, sparks, open flame, plug sockets, light switches, lamps, electrical switches or
other permanent ignitions sources, in the protective zone.
The protective zone must not extend to adjacent buildings or public traffic areas (boundaries of neighbors, the public road, neighbor's private
roads, subsidence area, depressions, pump shafts, sewers intakes, waste water shafts and so on.).
In the protective zone, you are not permitted to make any subsequent structural alterations which infringe the stated rules for the protective
zone.
SELECT THE BEST LOCATION
1
PROTECTIVE ZONE
2
1) Protective zone for ground installation (or fl at-roof
installation) at the open areas
2) Protective zone for ground installation in front of a
building wall
3) Protective zone for ground installation in a building
corner
4) Protective zone for wall installation in front of a building
wall
5) Protective zone for wall installation in a building corner
The protective zone under the product extends to the fl oor.
A 1000 mm
A 2000 mm
B 3000 mm
C 300 mm
D 1000 mm
A 2000 mm
B 2500 mm
C 300 mm
D 500 mm
E 1000 mm
F
500 mm
G 1800 mm
A 2000 mm
B 3000 mm
C 300 mm
D 1000 mm
A 2000 mm
B 2500 mm
C 300 mm
D 500 mm
E 1000 mm
F
500 mm
G 1800 mm
The protective zone under the product extends to the fl oor.
A
A
B
C
D
A
B
A
B
C
D
E
F
G
C
D
A
B
B
C
D
E
F
G
A