115
16.5.23
Four Way Valve Abnormality (F25)
Malfunction Decision Conditions:
1 During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C.
2 During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C.
Malfunction Caused:
1 Faulty
sensor.
2 Faulty
connector
connection.
3 Faulty outdoor unit PCB (noise filter/main).
4 Faulty four way valve.
Abnormality Judgment:
Continue 4 times in 30 minutes.