62
13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 5 minutes.
Detection
conditions:
o
When detection of Tem above 30°C.
o
Calculation of average evaporation temperature (Tem).
o
Use outdoor low pressure sensor.
o
Tem use the value calculated for discharge temperature setting value
After
detection:
o
Compressor stops restart again after 3 mins.
o
When abnormalities continuously generated 60 times within 480 minutes
o
Protection
is
prohibited.
o
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control / Low Pressure Sensor
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 1 minute.
Detection
conditions:
o
When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
o
When abnormality is detected continue 5 seconds, unit stop operation.
o
OFF/ON control panel LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting
condition:
o
Heating
operation
o
Outdoor air temperature < -10°C
o
Actual
frequency
≥
50Hz
o
Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation
condition:
o
starting condition not fulfill.
o
Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C
Summary of Contents for WH-SHF09D3E8
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up the Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E8 ...
Page 22: ...22 8 1 2 WH SHF12D9E8 ...
Page 23: ...23 8 2 Outdoor Unit ...
Page 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E8 ...
Page 25: ...25 9 1 2 WH SHF12D9E8 ...
Page 26: ...26 9 2 Outdoor Unit ...
Page 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Noise Filter Printed Circuit Board ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 ...
Page 108: ...108 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 109: ...109 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 116: ...116 19 2 WH UH09DE8 WH UH12DE8 ...
Page 117: ...117 ...