12.12 Three Way Valve Control
Purpose:
- 3 ways valve is used to change flow direction of hot water from heatpump between heating side and tank side
Control
contents:
1 3 ways valve switch Off:
o
During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2 3 ways valve switch On:
o
During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3 Stop
condition:
o
During stop mode, 3 ways valve will be in switch off position
12.13 Sterilization Mode
Purpose:
o
Boil tank temperature to customer set boiling temperature to operate sterilization.
Control start condition:
o
Tank connection set to YES by remote controller
o
Sterilization function selection is YES
o
Sterilization signal received from remote controller by timer.
Control
stop
condition:
o
After boiling timer completed. Boiling timer start counting once tank achieve boiling set temperature OR
o
After 4 hours of operation since sterilization function start OR
Control
content:
o
Once the sterilization function enable, set the target tank temperature to Boiling Set Temperature.
o
Booster heater will allow to ON during solar priority SET condition.
Booster heater OFF Temp. = Boiling Set Temperature 0°C
Booster heater ON Temp. = Boiling Set Temperature - 7°C
o
The sterilization set temperature may not achieve if tank booster heater function is deactivated.
o
Boiling timer which set by remote controller will start count after tank achieve boiling set temperature.
o
Sterilization
operation
will end after complete boiling timer or Max 4 hrs from function start.
o
Target tank temperature will set back to normal tank set temperature.
* Tank heater control is not affected by solar pump when solar priority set.
12.14 Quiet Operation
Purpose:
- To provide quiet operation compare to normal operation by reduces Mono bloc unit noise.
Starting
condition:
1
When quiet button is presses.
2
When quiet request ON time by weekly timer (Refer to remote control.)
When any of above mentioned condition is achieved, this control is activated.
New target FM speed = Present target FM speed - 80rpm
Minimum target FM speed = 200rpm
Cancellation
condition:
1
Cancel by press quiet button
2
Stop by OFF/ON button
3
When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
12.15 Anti Freeze Control
Anti freeze protection control can be select YES or NO from control panel. Default setting is YES.
In heatpump system, there are 2 types of anti freeze control:
1. Water pump circulation anti frost control
Water pump turns ON when
ALL
the below conditions are fulfilled:
o
Heatpump OFF (standby) OR water pump stop (Tank Mode) OR error occurs
o
Water flow switch is not abnormal
o
Outdoor ambient temp. < 3°C
o
Water inlet/outlet temp. < 6°C
o
After 5 minutes from previous water pump OFF
Summary of Contents for WH-MDC09C3E8
Page 15: ...15 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 2 Weekly Timer Setting ...
Page 21: ...21 4 1 2 3 Setting Up the Special Functions ...
Page 22: ...22 5 Dimensions 5 1 Mono Bloc Unit ...
Page 23: ...23 6 Refrigeration And Water Cycle Diagram ...
Page 24: ...24 ...
Page 25: ...25 7 Block Diagram 7 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Page 26: ...26 7 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Page 27: ...27 8 Wiring Connection Diagram 8 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Page 28: ...28 ...
Page 29: ...29 8 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Page 30: ...30 ...
Page 31: ...31 9 Electronic Circuit Diagram 9 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Page 32: ...32 ...
Page 33: ...33 9 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Page 34: ...34 ...
Page 35: ...35 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 36: ...36 10 1 2 Solar Printed Circuit Board Optional ...
Page 37: ...37 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 38: ...38 10 2 2 Noise Filter Printed Circuit Board ...
Page 39: ...39 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 40: ...40 Main Components ...
Page 52: ...52 ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 69: ...69 Heat Tank Mode Heating Priority Set Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 118: ...118 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 133: ...133 ...