7
2.3.
Tank Mode Operation (Page: 51)
2.4.
Heat + Tank Mode Operation (Page: 54)
[PHAAM] Printed in Malaysia
OLD
NEW
1. Water inlet temperature > X_INLETDT_1°C for continuous
X_INLETDT_2 sec, heat pump OFF and water pump OFF
1. Water inlet temperature > 52°C for continuous 60 secs, heat pump
OFF and water pump OFF
• [X_THEATTM_2] minutes from previous heater off.
• 20 minutes from previous heater off.
OLD
NEW
1. Water inlet temperature > X_INLETDT_1°C for continuous
X_INLETDT_2 sec, switch 3 ways valve to room side. End tank heat-up
interval and start count heating heat-up interval.
1. Water inlet temperature > 52°C for continuous 60 secs, switch 3 ways
valve to room side. End tank heat-up interval and start count heating
heat-up interval.