background image

8

ENGLISH

Replace The Remote Controller Cover

 

Replace the existing Remote controller cover with Remote controller 
cover 

6

 to close the hole left after remove the Remote controller.

1.  Release the Remote controller cover’s hooks from behind the 

front plate.

Front plate

Hook (6 places)

Existing Remote 
controller cover

2.  Press from front to fi x the Remote controller cover 

6

 on the 

front plate.

Front plate

Hook (6 places)

Remote 
controller 
cover 

6

CHARGING THE WATER

8

 

Make sure all the piping installations are properly done before 
carry out below steps.

1.  Turn the plug on the Air Purge Valve 

9

 outlet anticlockwise by 

one complete turn from fully closed position.

Air purge valve 

Plug (turn 
anticlockwise by 
one complete turn)

2.  Set the Pressure Relief Valve 

c

 level “DOWN”. 

Pressure relief 
valve 

c

Lever

Turn up

Pressure relief valve 

c

3. Start fi lling water (with pressure more than 0.1 MPa (1 bar)) to 

the Indoor Unit via water inlet. Stop fi lling water if the free water 
fl ow through Pressure Relief Valve drain hose.

4.  Turn ON the power supply and make sure Water Pump 

f

 is 

running.

5.  Check and make sure no water leaking at the tube connecting 

points.

Mounting The Remote Controller

For exposed type

Preparation:

 Make 2 holes for screws using a driver.

UP

Cut here with 
a nipper and 
remove the burr 
with a fi le.

Mount the top case.

 

Align the claws of the top 
case and then align the claws 
of the bottom case.

Hole for screw

Screw 
(fi eld supply)

Claw (2 places)

Pass through 

the hole

Bottom case 

(Back side)

Top case 
(Back side)

Remote controller terminal board

Remove the coating. Approx. 6 mm

Remove the sheath. Approx. 180 mm.
Make sure the wiring connection is in the 
correct direction.

Clamper 

(fi eld supply)

Claw (2 places)

Wall to which 
the remote 
controller is 
fi xed

Mount the bottom case to 

the wall.

Connect the remote control 

wiring

 

Arrange the wires along the groove 
of the case.

For embedded type

Preparation:

 Make 2 holes for screws using a driver.

UP

Avoid the wire 
being caught.

Mount the top case.

 

Align the claws of the top 
case and then align the claws 
of the bottom case.

Hole for 
screw

Screw 
(fi eld supply)

Claw (2 places)

Bottom case 

(Back side)

Top case 
(Back side)

Remote controller 
terminal board

Remove the coating. 

Approx. 6 mm

Make sure the wiring 
connection is in the correct 
direction.

Claw (2 places)

Mount the bottom case 

to the wall.

 

Pass the wire through the hole 
in the centre of the bottom case.

Connect the remote 

control wiring

Summary of Contents for SXC09 3E5 Series

Page 1: ...of other components i e heater etc Overloaded wiring or wire connection points may cause electrical shock or fire Do not add or replace refrigerant other than specified type It may cause product damage burst and injury etc Do not use joint cable for Indoor Outdoor Unit connection cable Use specified Indoor Outdoor Unit connection cable refer to instruction 6 CONNECT THE CABLE TO THE INDOOR UNIT an...

Page 2: ...work carried out on the Indoor Unit after removing any panels which is secured by screws must be carried out under the supervision of authorized dealer and licensed installation contractor This unit must be properly earthed The electrical earth must not be connected to a gas pipe water pipe the earth of lightening rod or a telephone Otherwise there is a danger of electrical shock in the event of a...

Page 3: ...eld supply accessories listed in above table Pipe Position Diagram Main Components 892 500 340 427 326 5 141 5 58 5 62 53 153 285 FRONT VIEW BOTTOM VIEW SIDE VIEW a b c d f e 1 Cabinet front plate 2 Cabinet side plate 2 pieces 3 Remote controller 4 PCB 5 1 Single Phase RCCB ELCB Main Power 5 2 Single Phase RCCB ELCB Backup Heater 6 Control board cover 7 Control board 8 Flow sensor 9 Air purge valv...

Page 4: ... licensed electrician water system installer only Work behind the front plate secured by screws must only be carried out under supervision of qualified contractor installation engineer or service person Please follow the steps below for take out front plate Before removing the front plate of indoor unit always switch off all power supply i e indoor unit power supply heater power supply and Tank Un...

Page 5: ... to this indoor unit ensure the pipes are clean before water pipe installation is carried out Be sure to use two spanners to tighten the connection Tighten the nuts with torque wrench 117 6N m Torque wrench Indoor unit Spanner If non brass metallic piping is used for installation make sure to insulate the pipes to prevent galvanic corrosion Make sure to insulate the water circuit pipes to prevent ...

Page 6: ...minals on the Indoor Unit L N L1 N1 1 2 3 Power Supply Cord Terminals on the isolating devices from power supply Disconnecting means L N L1 N1 Indoor Unit Outdoor Unit connection Power Supply 1 Power Supply 2 CUTTING AND FLARING THE PIPING 1 Please cut using pipe cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping en...

Page 7: ...71 at the interface Please liaise with supply authority to ensure that the power supply 2 is connected only to a supply of that impedance or less INSTALLATION OF REMOTE CONTROLLER AS ROOM THERMOSTAT 7 4 Location near heat source 5 Uneven surface Keep distance of 1 m or more from the TV radio and PC Cause of fuzzy image or noise Remote Controller Wiring 1 2 Terminal for Remote Controller wiring Rem...

Page 8: ...eaking at the tube connecting points Mounting The Remote Controller For exposed type Preparation Make 2 holes for screws using a driver UP Cut here with a nipper and remove the burr with a file Mount the top case Align the claws of the top case and then align the claws of the bottom case Hole for screw Screw field supply Claw 2 places Pass through the hole Bottom case Back side Top case Back side ...

Page 9: ... 0121 60 0 0171 70 0 0228 80 0 0291 90 0 0360 Adjustment of the initial pressure of the expansion vessel when there is a difference in installation height If the height difference between the indoor unit and the highest point of the system water circuit H is more than 7m please adjust the initial pressure of the expansion vessel Pg according to the following formula Pg H 10 30 kPa CHECK RCCB ELCB ...

Page 10: ...oor Unit is not in operation standby enter the Service setup menu in the Remote Controller and select Pump down operation to turn it ON See APPENDIX for detail 2 After 10 15 minutes after 1 or 2 minutes in case very low ambient temperatures 10 C fully close 2 way valve on Outdoor Unit 3 After 3 minutes fully close 3 way valve on Outdoor Unit 4 Press the OFF ON switch on the Remote Controller 3 to ...

Page 11: ...ve remote controller from indoor unit and install it in the room where floor heating is installed This is an application that uses remote controller as Room Thermostat 3 External Room Thermostat Outdoor Room Thermostat Field supply Floor heating Indoor Connect floor heating or radiator directly to indoor unit Remote controller is installed on indoor unit Install separate external Room Thermostat f...

Page 12: ...ting operation separately This system requires optional PCB CZ NS4P Outdoor Radiator Thermistor 1 Thermistor 2 Buffer tank Pump 2 Pump 1 Mixing valve 1 Indoor Floor heating Connect floor heating or radiator to 2 circuits through buffer tank as shown in figure Install pumps and thermistors specified by Panasonic on both circuits Install mixing valve in the circuit with lower temperature among the 2...

Page 13: ...ontroller Indoor Outdoor Simple 2 zone Floor heating Radiator Thermistor 2 Thermistor 1 Pump 2 Mixing valve Indoor Outdoor Radiator This is an example of simple 2 zone control without using buffer tank Built in pump from indoor unit served as a pump in zone 1 Install mixing valve pump and thermistor specified by Panasonic on zone 2 circuit Please be sure to assign high temperature side to zone 1 a...

Page 14: ...at accumulation operates automatically by comparing the temperature of tank thermistor and solar thermistor During winter season solar pump for circuit protection will be activated continuously If does not want to activate the solar pump operation please use glycol and set the anti freezing operation start temperature to 20 C This system requires optional PCB CZ NS4P Buffer tank connection Outdoor...

Page 15: ...integration in the system complies with applicable legislation Make sure the return water temperature from the heating circuit to the indoor unit does NOT exceed 55 C Boiler is turned off by safety control when the water temperature of the heating circuit exceed 85 C Setting of remote controller Installer setting System setup Optional PCB connectivity Yes Bivalent Yes Turn ON outdoor temp Control ...

Page 16: ... 1 By connecting optional PCB 2 Zone temperature control can be achieved Please connect mixing valves water pumps and thermistors in zone 1 and zone 2 to each terminals in optional PCB Temperature of each zone can be controlled independently by remote controller 2 Pump zone 1 and zone 2 cable shall be 2 x min 1 5 mm of type designation 60245 IEC 57 or heavier 3 Solar pump cable shall be 2 x min 1 ...

Page 17: ...or booster heater Zone 1 room sensor Outdoor air sensor Tank sensor External control Remote controller Boiler contact Extra pump Booster heater H C N L C O N C O N Optional Thermostat 1 3 way valve 2 way valve Signal inputs Optional Thermostat L N AC230V Heat Cool Thermostat heat Cool terminal It does not function when using the optional PCB OLP for booster heater Dry contact Vcc Bit1 Vcc Bit2 ope...

Page 18: ...unt it on the water piping by using the stainless steel metal strap and contact paste both are included 93 70 35 Dimensions mm 3 Outdoor sensor PAW A2W TSOD If the installation location of the outdoor unit is exposed to direct sunlight the outdoor air temperature sensor will be unable to measure the actual outdoor ambient temperature correctly In this case optional outdoor temperature sensor can b...

Page 19: ... CN CNT cable Without Optional PCB CN CNT cable With Optional PCB 2 Insert a flat head screwdriver into the slot on the top of the adaptor and remove the cover Connect the other end of the CN CNT cable connector to the connector inside the adaptor Slot Connector 3 On the wall near the Indoor Unit attach the adaptor by screwing screws through the holes in the back cover Screws 4 Pull the CN CNT cab...

Page 20: ...g Set room temp Compensation curve Set direct water temp Set pool temp 4 Display Heat temp Display current heating temperature it is set temperature when enclosed by line 5 Display tank temp Display current tank temperature it is set temperature when enclosed by line 6 Outdoor temp Display outdoor temp 3 1 Remote Controller Outline A B C D G F E Name Function A Main screen Display information B Me...

Page 21: ... If initial setting is not performed it does not go into menu Set language confirm Clock format 12 00 Mon 24h am pm Select Confirm When language is set setting screen of time display appears 24h am pm Set time display confirm Date time 12 00 Mon Year Month Day Hour Min 2015 01 01 12 00 Select Confirm YY MM DD Time setup screen appears Set YY MM DD Time confirm 17 26 Wed Start Back to initial scree...

Page 22: ...A B 9 Alternative outdoor sensor Yes No 10 Bivalent connection Yes No Bivalent setup 11 External SW 12 Only when the selection for optional PCB is Yes Solar connection 13 Only when the selection for optional PCB is Yes External Error signal 14 Only when the selection for optional PCB is Yes Demand control 15 Only when the selection for optional PCB is Yes SG ready 16 Only when the selection for op...

Page 23: ...or cooling setup 25 Auto Outdoor temp for Heat to Cool Heat Cool change temp setup 26 Outdoor temp for Cool to Heat Cool Heat change temp setup 27 Tank Floor operation time max Max operation time for Heat Cool mode setup 28 Tank heat up time max Max operation time for Tank mode setup 29 Tank re heat temp Tank re heat temp setup 30 Sterilization Sterilization day and temp and time setup 31 Service ...

Page 24: ... 2 select sensor CAUTION In 2 zone system pool function can be set at zone 2 only 3 Heater capacity Initial setting Depend on model System setup 17 26 Wed Optional PCB connectivity Zone Sensor Heater capacity Anti freezing Select Confirm If there is built in Heater set the selectable heater capacity CAUTION There are models which cannot select heater 4 Anti freezing Initial setting Yes System setu...

Page 25: ... tank External A setting which is using booster heater installed on DHW tank to boil the tank The permissible heater capacity is 3kW and below The operation to boil the tank with heater is as below In addition be sure to set suitable Tank heater ON time Internal A setting which is using backup heater of indoor unit to boil the tank The operation to boil the tank with heater is as below 65 53 HP th...

Page 26: ...oiler temp ON Setting 8 C setting from remote controller Although heat pump operates but water temperature does not reach this temperature for more than 30 mins setting from remote controller operate heat pump only 10 C setting from remote controller operate boiler and heat pump simultaneously For DHW tank Outdoor temp AND time Tank setting temp 30 min setting from remote control If actual tank te...

Page 27: ...95 2 7 30 25 6 3 9 8 2 8 6 4 6 6 65 9 9 100 2 9 3 1 30 6 7 70 65 A minimum operating current is applied on each model for protection purpose 0 2 voltage hysteresis is provided The value of voltage after 2nd decimal point are cut off 3 2 35 30 6 8 3 3 6 9 7 1 70 3 4 3 6 35 7 2 75 70 3 7 40 35 7 3 3 8 15 SG ready Initial setting No System setup 17 26 Wed Solar connection External error signal Demand...

Page 28: ...C 5 C 15 C 55 C Hot water temperature compensation curve Outdoor temperature Decide temperature of 4 points as shown in diagram Set target water temperature to operate heating operation Compensation curve Target water temperature change in conjunction with outdoor ambient temperature change Direct Set direct circulation water temperature In 2 zone system zone 1 and zone 2 water temperature can be ...

Page 29: ...e Setting range is 1 C 15 C Auto 25 Outdoor temp for Heat to Cool Initial setting 15 C 15 C Heat Cool Outdoor temp rising Set outdoor temp that switches from heating to cooling by Auto setting Setting range is 5 C 25 C Timing of judgement is every 1 hour 26 Outdoor temp for Cool to Heat Initial setting 10 C 10 C Heat Cool Outdoor temp dropping Set outdoor temp that switches from Cooling to Heating...

Page 30: ...ally setting is not necessary Please adjust when need to reduce the pump sound etc Besides that it has Air Purge function 32 Pump down Service setup 17 26 Wed Pump down ON Confirm Service setup 17 26 Wed Pump down ON Confirm Pump down operation in progress OFF Operate pump down operation 33 Dry concrete 30 C 1 2 3 4 5 6 35 C 35 C 40 C 40 C 45 C Stage Operate concrete curing operation Select Edit s...

Page 31: ...t is not used 3 Sensor setup offset gap of detected temp of each sensor within 2 2 C range CAUTION Please use only when sensor is deviated It affects temperature control 4 Reset password Reset password Custom menu Setting method of Custom menu Custom menu 17 26 Wed Cool mode Back up heater Reset energy monitor Select Confirm Please press for 10 sec Items that can be set 1 Cool mode Set With Withou...

Reviews: