95
Input Select
5-11 Select Input
5-11-1 Types of Inputs
■ 2NC
Used to connect the safety device of 2NC contact output.
■ 1NO / 1NC
Used to connect safety device of 1NO / 1NC contact output.
■ PNP×2 (equ.)
Used to connect safety devices (PNP semiconductor out-
put × 2). The safety device to be used is a type that turns
“ON-OFF” two outputs simultaneously.
■ Muting input (equ.)
Used as an input of mute sensor when it is selected as “Parallel muting” or “Sequential muting”
in control block 1.
This connects two mute sensors (equ.), each of which has two NO contacts or output [PNP
semiconductor output].
When “Sequential muting” is set in control block 1, both “Muting input (equ.)” and “Muting input
(dif.)” cannot be used at a time.
■ Muting input (dif.)
Used as the input of mute sensor when it is selected as “Parallel muting” or “Sequential muting”
in control block 1.
This connects two mute sensors (dif.), each of which has NO and NC contacts or output [PNP
semiconductor output].
When “Sequential muting” is set in control block 1, both “Muting input (equ.)” and “Muting input
(dif.)” cannot be used at a time.
■ Override
Used as the input of override switch when it is selected as “Parallel muting” or “Sequential mut-
ing” in control block 1.
Connects a momentary type switch for 1NO / 1NC contact.
■ Key selector
Used as the input of key selector switch when “Input select” is selected in control block 1.
Connects an alternate type key switch (with a forced breaking contact) for 1NO / 1NC.
■ Test
When test input is effective, the control output is turned into OFF status.
The switch for 1NC contact or PNP semiconductor output (normally set to ON) is connected.
● Contact “Close” or output ON : Test input invalid
● Contact “Open” or output OFF : Test input valid
The input block with this input selected is not connected to connection tab, control block, or out-
put block. If connected, the input block is judged to be erroneous by the software tool.