Interlock Block
5-13 Interlock block
Reset operation of this device is set.
Click and select the interlock block.
The combinations of overall resets and partial resets are
unavailable.
●
Overall reset
●
Partial reset (auto start) + Partial reset (auto start)
●
Partial reset (auto start) + Partial reset (manual start)
●
Partial reset (manual start) + Partial reset (auto start)
●
Partial reset (manual start) + Partial reset (manual start)
■ Overall reset
The outputs of two systems of this device are reset by one operation.
● Manual reset : Momentary type switch is connected to between INT11 and INT12.
Switching the switch contact from “Closed to Open” performs reset operation.
● Auto reset : Short-circuit is generated between INT21 and INT22.
If INT21-INT22 is not short-circuited when power is turned ON, manual reset is automatically
selected.
■ Partial reset
Each of the outputs of two systems of this device is reset individually.
● Manual reset : Momentary type switch is connected to between INT11 and INT12 and be
-
tween INT21 and INT22. Switching the switch contact from “Closed to Open”
performs reset operation.
● Auto reset : Short-circuit is generated between INT11 and INT12 and between INT21 and
INT22.
Also refer to “
”.