46
Chapter 2
Basic Procedures
Connection to Terminal Block
Before starting the wiring work, be sure to turn off the power. If the power is not turned off, the system
may be shorted or damaged, and you may get an electric shock.
WARNING
Correctly connect wires to the terminal block. Miswiring may cause malfunction or damage of the system.
CAUTION
1.
Hook-up the crimp-style terminal to the cable.
2.
The crimp-style terminals having insulating sheath for copper wires are recommended.
3.
For the
SL-VTB□4
, use the general crimp-style terminals for M3. The dimensions of the crimp-style termi-
nals are not restricted.
<Applicable crimp-style terminals>
(Unit: mm)
Recommended crimp-style terminals (manufactured by J.S.T Mfg
Co., Ltd.):
Round crimp-style terminal with vinyl insulator (V2-S3.3)
Round crimp-style terminal with nylon insulator (N2-S3.3)
Y-shaped crimp-style terminal with vinyl insulator (V1.25-B3A, V2-N3A)
Y-shaped terminal
Round terminal
3.2 or more
6 or less
6 or more
20
or less
15.5
or less
6 or less
<When hooked-up>
o
6 or more
20
or less
15.5
or less
6 or less
6 or less
<When hooked-up>
3.2 or more
4.
Check the connect-to terminals and the cable, and then connect the cable using a screwdriver.
Tightening torque: 0.29 to 0.49N·m for controller
0.5N·m or less for I/O terminal
The terminal block is separated into two. Connect wires to the lower terminal block first.
Screwdriver
NOTE
Summary of Contents for S-LINK V
Page 2: ...2 ...
Page 5: ...5 Before Using This System ...
Page 12: ...12 Before Using This System MEMO ...
Page 13: ...13 Chapter 1 Designing System ...
Page 35: ...35 Chapter 2 Wiring ...
Page 60: ...60 Chapter 2 MEMO ...
Page 61: ...61 Chapter 3 Starting System ...
Page 71: ...71 Chapter 4 Specifications ...
Page 161: ...161 Chapter 5 Troubleshooting ...
Page 169: ...169 Appendix ...
Page 180: ...180 Appendix MEMO ...