List of Item Codes (Some item codes cannot be set due to the type of models.)
r
e
t
e
m
a
r
a
P
e
d
o
c
m
e
t
I
05
Silent level
1=Silent level1 2=Silent level2 3=Silent level3
07
Ignore capacity
0 = Disabled 1 = Ignores capacity ratio
0C
Forced operation of
indoor unit drain pump
0 = Disable
1 = 2 hours s 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = 20 minutes s 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = Always operating
(regardless of whether the unit is running or stopped)
4 = XX minutes (Setting of Item code "2B") operating
when the unit change to thermo off or stop from thermo on.
5 = XX minutes (Setting of Item code "2B") operating
when the unit change to stop (regardless of whether the unit
was thermo on or thermo off).
6 = Doing the action 4 and 5.
7 = During cooling only, Doing the action 6.
0=Heat pump 1=Cooling only
Cooling only
E
0
12
Silent mode
0=Disable(at shipment) 1=At any times 2=Capacity priority
3=Timer setting 4=2+3
13
22 = 22 o'clock (at shipment)
14
00 = 00 minute (at shipment)
15
28 = 28 o'clock (at shipment)
16
00 = 00 minute (at shipment)
1A
40
㧑
㨪
130
㧑
, -1(no control)
1B
40
㧑
㨪
130
㧑
, -1(no control)
1D
40
㧑
㨪
130
㧑
, -1(no control)
2B
Operating time of indoor unit drain pump
Current control level
Demand 1 Current
Demand 1 Current
Silent mode finishinging time (minutes)
Silent mode finishinging time (hour)
Silent mode starting time (minutes)
Silent mode starting time (hour)
0=20minutes
ޓ
1=30minutes
ޓ
2=40minutes
3=50minutes
ޓ
4=60minutes
* Figures in parentheses indicate the data at the time of shipment from the factory.