IMPORTANT! 
Please Read Before Starting

This air conditioner must be installed by the sales dealer 
or installer.
This information is provided for use only by authorized 
persons.

For safe installation and trouble-free operation, you must:

  Carefully read this instruction booklet before beginning.

  Follow each installation or repair step exactly as shown.

  This air conditioner shall be installed in accordance with 

National Wiring Regulations.

  Pay close attention to all warning and caution notices 

given in this manual.

WARNING

This symbol refers to a hazard or unsafe 
practice which can result in severe 
personal injury or death.

CAUTION

This symbol refers to a hazard or unsafe 
practice which can result in personal injury 
or product or property damage.

If Necessary, Get Help

These instructions are all you need for most installation 
sites and maintenance conditions. If you require help for a 
special problem, contact our sales/service outlet or your 
certified dealer for additional instructions.

In Case of Improper Installation

The manufacturer shall in no way be responsible for 
improper installation or maintenance service, including 
failure to follow the instructions in this document. 

SPECIAL PRECAUTIONS

 WARNING

   

When Wiring

ELECTRICAL SHOCK CAN 
CAUSE SEVERE PERSONAL 
INJURY OR DEATH. ONLY A 
QUALIFIED, EXPERIENCED 
ELECTRICIAN SHOULD 
ATTEMPT TO WIRE THIS 
SYSTEM. 

• Do not supply power to the unit until 

all wiring and tubing are completed or 
reconnected and checked.

• Highly dangerous electrical voltages are 

used in this system. 
Carefully refer to the wiring diagram and 
these instructions when wiring. Improper 
connections and inadequate grounding 
can cause 

accidental injury or death.

• Connect all wiring tightly. Loose wiring 

may cause overheating at connection 
points and a possible fire hazard.

 Provide a power outlet to be used 

exclusively for each unit.

 Provide a power outlet exclusively for 

each unit, and full disconnection means 
having a contact separation in all poles 
must be incorporated in the fixed wiring 
in accordance with the wiring rules.

 To prevent possible hazards from 

insulation failure, the unit must be 
grounded.

When Transporting

Be careful when picking up and moving 
the indoor and outdoor units. Get a partner 
to help, and bend your knees when lifting 
to reduce strain on your back. Sharp 
edges or thin aluminum fins on the air 
conditioner can cut your fingers.

When Installing…

Select an installation location which is 
rigid and strong enough to support or hold 
the unit, and select a location for easy 
maintenance.

…In a Room

Properly insulate any tubing run inside a 
room to prevent “sweating” that can cause 
dripping and water damage to walls and 
floors.

CAUTION

Keep the fire alarm and 
the air outlet at least 
1.5 m away from the unit.

…In Moist or Uneven Locations

Use a raised concrete pad or concrete 
blocks to provide a solid, level foundation 
for the outdoor unit. This prevents water 
damage and abnormal vibration.

…In an Area with High Winds

Securely anchor the outdoor unit down 
with bolts and a metal frame. Provide a 
suitable air baffle.

…In a Snowy Area (for Heat Pump-type 
Systems)

Install the outdoor unit on a raised platform 
that is higher than drifting snow. Provide 
snow vents.

…At least 2.5 m

Indoor unit of this air conditioner shall be 
installed in a height of at least 2.5 m.

…In laundry rooms

Do not install in laundry rooms. Indoor unit 
is not drip proof.

Pana̲indoor̲all.indb   2

Pana̲indoor̲all.indb   2

2013/12/16   15:15:11

2013/12/16   15:15:11

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Summary of Contents for S-36MU1E5A

Page 1: ...ocedere con l installazione Prestare particolare attenzione alla sezione IMPORTANTE all inizio della pagina NEDERLANDS Lees de installatie instructies zorgvuldig door voor u begint met de installatie U moet vooral het gedeelte waar BELANGRIJK boven staat heel goed lezen PORTUGUÊS Leia cuidadosamente as instruções de instalação antes de prosseguir com a instalação Em particular é necessário ler as ...

Page 2: ...ntal injury or death Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard Provide a power outlet to be used exclusively for each unit Provide a power outlet exclusively for each unit and full disconnection means having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring rules To prevent po...

Page 3: ...p the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced WARNING This product must not be modified or disassembled under any circumstances Modified or disassembled unit may cause fire electric shock or injury Do not clean inside the indoor and outdoor units by users Engage authorized dealer or specialist for cleaning In c...

Page 4: ...Connecting Tubing Between Indoor and Outdoor Units 5 3 Insulating the Refrigerant Tubing 5 4 Taping the Tubes 5 5 Finishing the Installation 6 HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH SPEC WIRED REMOTE CONTROLLER OPTIONAL PART 18 NOTE Refer to the Operating Instructions attached to the optional Timer Remote Controller or optional High spec Wired Re mote Controller 7 HOW TO INSTALL THE CE...

Page 5: ...ose Packing 1 Drain insulator 1 Clamper 3 Operating Instructions 1 Installation Instructions 1 Use M10 for suspension bolts Field supply for suspension bolts and nuts 1 3 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing 2 Foamed polyethylene insulation for copper...

Page 6: ...ct a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length L from the outdoor unit as detailed in the installation manual packed with the outdoor unit allow room f...

Page 7: ... The diagram and table Fig 3 3 and Table 3 2 show the relationship between the positions of the suspension fitting unit and panel Use the nut field supply and washer supplied for upper and lower position of the suspension lug Table 3 2 Unit mm Length Type A B C D E 22 28 36 45 56 60 73 90 121 171 256 180 130 106 140 160 121 171 319 180 130 Hole in anchor Hole in plug Concrete Insert Suspension bol...

Page 8: ... shown in Fig 3 5 Use 1 nut and 1 washer for the upper side and 2 nuts and 1 washer for the lower side so that the unit will not fall off the suspension lugs 4 Adjust so that the distance between the unit and the ceiling bottom is 12 to 17 mm Tighten the nuts on the upper side and lower side of the suspension lug 5 Remove the protective polyethylene used to protect the fan parts during transport 6...

Page 9: ... leakage Fig 3 6 2 Limitations of Drain Pipe Connection CAUTION Do not install the drain pipe with an upward gradient from the drain port connection This will cause the drain water to flow backward and leak when the unit is not operating Fig 3 7 Do not install an air bleeder as this may cause water to spray from the drain pipe outlet Fig 3 7 Do not provide U trap or bell shaped trap in the middle ...

Page 10: ...f the hard PVC socket and the hard PVC joint VP25 in the local supply 6 Connect the drain hose and the hard PVC joint so that the adhesive area of both sides can be overlapped Wipe off the protrusion adhesive with a soft cloth Drain port Do not use adhesive here Drain port may possibly be damaged if PVC adhesive is used After checking the drainage wrap the supplied packing and drain pipe insulator...

Page 11: ...heck the following items Checkpoint Symptom Check Remark 1 Make sure whether indoor and outdoor units are correctly installed Fall vibration noise 2 Make sure whether gas leakage is tested No cooling no heating 3 Make sure whether insulation is completed Refrigerant piping and drain piping Water leakage 4 Make sure whether drain water is running smoothly Water leakage 5 Make sure whether the power...

Page 12: ...ed it must be replaced by a repair shop designated by the manufacturer because special purpose tools are required 4 2 Recommended Wire Length and Wire Diameter for Power Supply System Indoor unit Type B Power supply Time delay fuse or circuit capacity 2 5 mm2 U1 Max 130 m 10 16 A Control wiring C Inter unit between outdoor and indoor units control wiring D Remote control wiring E Control wiring fo...

Page 13: ...er supply Unit control line Remote control line U1 Type U2 U1 R2 R1 L N R2 R1 R2 R1 R2 R1 2 1 2 1 U2 U1 L N U2 U1 L N U2 U1 L N 2 1 2 1 2 1 D E C B L N L N L N L N 2 1 B B B C D D C 2 1 L1 L2 L3 N 2 1 L1 L2 L3 N C L1 L2 L3 N L1 L2 L3 N U2 U1 Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Power supply 220 230 240V 50 60 Hz Remote controller ...

Page 14: ...ndoor unit Indoor unit Indoor unit Indoor unit NO Branch point 5 Use shielded wires for inter unit control wiring c and ground the shield on both sides otherwise misoperation from noise may occur Fig 4 6 Connect wiring as shown in Section 4 3 Wiring System Diagrams Fig 4 6 6 Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 1 5 mm2 flexible cor...

Page 15: ...using a screwdriver Fig 4 8 Examples of shield wires 1 Remove cable coat not to scratch braided shield Fig 4 9 2 Unbraid the braided shield carefully and twist the unbraided shield wires tightly together Insulate the shield wires by covering them with an insulation tube or wrapping insulation tape around them Fig 4 10 3 Remove coat of signal wire Fig 4 11 4 Attach ring pressure terminals to the si...

Page 16: ...g gas leaks Fig 5 4 Apply refrigerant lubricant Fig 5 4 3 For proper connection align the union tube and flare tube straight with each other then screw on the flare nut lightly at first to obtain a smooth match Fig 5 5 Flare nut Union Fig 5 5 Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a flare Cautions During...

Page 17: ...ent space to access the valves and to allow the panels to be attached and removed Taping the flare nuts Wind the white insulation tape around the flare nuts at the gas tube connections Then cover up the tubing connections with the flare insulator and fill the gap at the union with the supplied black insulation tape Finally fasten the insulator at both ends with the supplied vinyl clamps Fig 5 8 Fl...

Page 18: ... 4 Way Cassette Type U1 Type Accessories Ceiling panel 1 Washer head screws 4 M5 40 ø18 Installation notes 1 Screws 4 4 12 7 1 Preparation for Ceiling Panel Installation 1 Checking the unit position 1 Check that the ceiling hole is within this range 860 mm 860 mm to 910 mm 910 mm 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling ...

Page 19: ... corner with the correct positions on the unit When removing the ceiling panel push the temporary latches outward while holding the ceiling panel Fig 7 4 Fig 7 4 2 Align the panel installation holes and the unit screw holes 3 Tighten the supplied washer head screws at the 4 panel installation locations so that the panel is attached tightly to the unit Fig 7 5 Fig 7 5 4 Check that the panel is atta...

Page 20: ...nd change the directions according to customer s requests When attaching the air intake grille be careful that the flap lead wire does not become caught Be sure to attach the safety cord that prevents the air intake grille from dropping off to the ceiling panel unit as shown in the figure below With this ceiling panel the directions of the air intake grille lattices when installing multiple units ...

Page 21: ...se steps 1 Open the electrical component box cover then check the indoor unit control PCB 2 Connect the jumper connector 2P yellow which was supplied with the accessory to the correct connector pin on the indoor unit control PCB according to the setting number which was confirmed in Table for DC Fan Motor Tap Settings Setting No 3 Then connect the jumper connector to the connector pin TP3 2P yello...

Page 22: ...ttons to select the desired setting data Flap position 1 2 3 4 5 Fig 7 11 Setting data refer to Fig 7 11 Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay When the flap position is set to 4 or 5 and the unit is in the cooling or dry mo...

Page 23: ...apy water rinse it in clean water and dry it How to remove the filter 4 Way Cassette Type U1 1 Use a screwdriver to remove the bolt screw on each side for the two latches Be sure to reattach the two bolt screws after cleaning 2 Slide the latches of the air intake grille in the direction of the inside to open the grille 3 The air intake grille opens downward CAUTION When cleaning the air filter nev...

Page 24: ...mes rotates because of drying heat exchanger due to settings Wind direction changes while operating Wind direction setting cannot be made Wind direction cannot be changed When air discharge temperature is low or during defrost operation horizontal wind flow is made automatically Flap position is occasionally set up individually When wind direction is changed flap operates several times and stops a...

Page 25: ...f the inspection mark and the letters E F H L P in combination with the numbers appear on the LCD of the remote controller Tips for Energy Saving Avoid Do not block the air intake and outlet of the unit If either is obstructed the unit will not work well and may be damaged Do not let direct sunlight into the room Use sunshades blinds or curtains If the walls and ceiling of the room are warmed by t...

Page 26: ...26 NOTE Pana indoor all indb 26 Pana indoor all indb 26 2013 12 16 15 15 24 2013 12 16 15 15 24 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 27: ...F616390 DC1213 0 Printed in China Pana indoor all indb b Pana indoor all indb b 2013 12 16 15 18 07 2013 12 16 15 18 07 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Reviews: