Panasonic RG-C811A Installation Instructions Manual Download Page 6

Duct length, elbows and other factors increase static pressure which can hinder the performance of most ventilation 
fans. This fan utilizes Smart Flow™ microchip technology that monitors the static pressure in the system and speeds 
up or slows down the rpm of the fan depending upon the amount of resistance within the ducts. This feature allows 
the fan to perform as rated and avoid potential installation issues.  

These products are built using DC motor technology. The DC motor is 30% ~ 70% more energy 
efficient than the minimum ENERGY STAR requirements. 

Pick-A-Flow™ Feature:

This product comes with Pick-A-Flow™ speed 
options. The Pick-A-Flow™ switch on the face of the product allows the 
option to choose 80 or 110 CFM. 
This product can run continuously or intermittently, depending upon the 
needs of the owner. 

Pick-A-Flow™
switch

RG-C811A
RG-C811HA

80 CFM

80

80

110
110

Air volume (CFM)

Factory setting

6

80 CFM

CFM

130

150

0811 MODEL

80

110

1315 MODEL

Tape

Adaptor

Damper

WARNING

Disconnect power supply before 
installing the unit.

Please wear gloves to protect hands 
during the installation.

Remove the tape placed on the damper and 

adaptor before installation. Failure to do so

will cause the product to work inefficiently and

create a loud noise.

OPERATION (RG-C811HA only)

INSTALLATION (RETROFIT)

FEATURES

Power
switch

Conden-
sation
sensor

Product

ON

OFF

Stop

Run

Environment humidity

Humidity trigger setting

about 5 %RH 

Delay

1

operation

*

The product will continue to run for about 
20 minutes after the sensor detects that 
the humidity is ~5 % RH lower than the 
humidity setting before stopping.

1

*

Stop

Note:
1. The power switch should be left on at all times.
2. The product will also run when the humidity rises rapidly but does not reach the humidity trigger setting, and then stop after
     the time delay. 

3. The activation humidity settings on the dial are continuous from 30 %RH ~ 80 %RH.

4. The humidity detected by the sensor may differ from the value on your hygrometer. 

5. The product may cycle on and off if the humidity is constantly near the trigger point. This can be addressed by raising
    the humidity trigger setting on the dial. 

6. The fan will run for 20 minutes when power switch is first turned on, regardless of the humidity sensor settings. After 20 
     minutes, the fan will return to sensor mode. 

Summary of Contents for RG-C811A

Page 1: ...e risk of injury loss of life electric shock fire malfunction and damage to equipment or property always observe the following safety precautions WARNING CAUTION Denotes a potential hazard that could result in serious injury or death Denotes a hazard that could result in minor injury Denotes a hazard that could result in property damage The following symbols are used to classify and describe the t...

Page 2: ...trical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire rated construction Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel Ducted exhaust fans must always be vented to the outdoors If this unit is to be installed over a tub or shower it must be marked as appropriate for the applica...

Page 3: ...r ventilation Do not connect multiple units in parallel If two or more units are connected to one switch in parallel the units may not function Do not install the unit where ducts are configured as shown in below Bend close to duct adaptor Squeezed duct Successive bending Excessive bending Adaptor DESCRIPTION These products use a sirocco fan driven by a DC motor powered by an integral transformer ...

Page 4: ... Blade Grille Junction box Adaptor PCB box Pick A Flow switch Fan body Damper Flex Z Fast bracket Unit inches mm RG C811HA RG C811A UNPACKING DIMENSIONS SUPPLIED ACCESORIES 12 304 10 1 4 260 3 7 8 100 5 7 8 151 7 1 2 190 13 330 13 1 4 15 1 2 336 394 16 1 2 18 3 4 419 480 21 1 4 23 1 2 540 597 10 5 8 270 3 3 8 86 7 8 23 5 1 1 2 37 4 1 2 114 13 330 10 1 4 261 3 7 8 100 12 304 10 1 4 260 3 7 8 100 5 ...

Page 5: ...tion box Neutral White Black Live Fan Ground wire Green DC Motor Fan body Main control circuit Main control circuit Humidity sensor Selector Timer Humidity setting Humidity preset selector Timer preset selector Selector indications on blower unit Factory setting is around 50 Timer preset selector positions 13 330 10 1 4 261 3 7 8 100 Part name Part name No No Blade Grille Junction box Adaptor PCB ...

Page 6: ...es to protect hands during the installation Remove the tape placed on the damper and adaptor before installation Failure to do so will cause the product to work inefficiently and create a loud noise OPERATION RG C811HA only INSTALLATION RETROFIT FEATURES Power switch Conden sation sensor Product ON OFF Stop Run Environment humidity Humidity trigger setting about 5 RH Delay 1 operation The product ...

Page 7: ...apping screws Flex Z Fast bracket position can be adjusted from 16 to 24 406mm to 610mm between joists Install Flex Z Fast bracket Joist 2 Tapping screws ST4 2X20 Flex Z Fast bracket Align 2 Joist Flex Z Fast bracket Joist Align the edge of Flex Z Fast with the edge of the ceiling opening on the side where the adapter will be installed Drywall Flex Z Fast bracket 1 Joist Drywall Joist INSTALLATION...

Page 8: ...he screw does not strip or come in contact with Flex Z Fast bracket 2 3 Insert circular exhaust duct 1 2 4 Remove screw from junction box cover to remove the knock out hole and secure conduit or stress relief to junction box knock out hole Install the circular exhaust duct and secure it with clamps or ties and seal it with mastic or approved foil tape A 4 inch circular duct is needed to connect to...

Page 9: ...ring the installation Remove the tape placed on the damper and adaptor before installation Failure to do so will cause the product to work inefficiently and create a loud noise 1 Install Flex Z Fast bracket Flex Z Fast bracket position can be adjusted from 16 to 24 406mm to 610mm between joists Unit inches mm Joist Bend down 4 tabs 1 2 2 Tapping screws ST4 2X20 Flex Z Fast bracket Align 1 2 Align ...

Page 10: ...r over 140 F 60 C Do not use cleaning sprays solvents or water on or near the sensor 10 Follow steps from RETROFIT Installation 1 Follow the steps 4 to 7 on INSTALLATION RETROFIT Remove grille 1 Gloves Slot Grille Mounting spring 1 Remove grille by pulling down one mounting spring then pull the other Extend Joist 3 4 2 Tapping screws ST4 2X20 3 4 Extend bracket to the other joist Install bracket t...

Page 11: ...ps alignment and absorbs sound Clamps plus mastic or approved foil faced tape at all flex joints Insulation Foil tape tightly covers all metal duct joints glue PVC joints Model No Air direction Voltage V Frequency Hz Duct diameter inches Air volume at 0 1 WG CFM Noise sones Speed rpm Power W Weight lb k Exhaust Exhaust 80 80 110 110 0 5 0 5 0 3 0 3 824 984 824 984 6 5 11 1 6 5 11 1 9 3 4 2 9 5 4 3...

Page 12: ... how long an implied warranty lasts so the above exclusions or limitation may not apply to you Obtain Product Information and Operating Assistance locate your nearest distributor or make Customer Service and Literature requests by visiting our Web Site at us panasonic com ventfans or send your request by E mail to ventfans us panasonic com You may also contact us directly at 1 866 292 7299 Monday ...

Reviews: